Installation & Commissioning of Control & Monitoring Add On’s
Page: 4
3
Adding Control and Monitoring Facilities
A combination of
one of each type
of board / card, but not all of them, can be mounted on the
back pan or the front panel of the FACP to provide additional features to a standard panel. All
board inputs or outputs are programmable to any combination of zones.
±
Relay Board, BRD25EWRB –A or with a change of on board components it can
also be installed remotely on the external communications bus as a Remote
Relay Board BRD25EWRB -B
±
Input Board BRD25SIPB -.
±
Sounder Board BRD25SOPB.
±
Brigade Interface Board BRD25BBA.
±
Fire Fan Module consists of a Termination Board ( BRD25FTB and front panel
card BRD25FCB -.
±
Agent Release Module consists of a Termination Board ( BRD25ATB ), front
panel card ( BRD25ARB–A ) and if required a remote local control station
(BRD25ARB–B).
±
General
Indicator
Card. BRD25GIB -A
±
Switch and Indicator Card BRD25GIBA
±
Zone Mimic Indicator Card ( Internal Power ) BRD25GIB -C
±
Zone Mimic Indicator Card (External Power normally remote) BRD25GIB -D
Note:
To add or remove Cards from the FACP programming go to the SYSTEM Menu.
3.1
Internal Communications Connector (RS485)
PCB mounted connectors provide serial communications to internal ancillary boards. CN9 on the
Main Card cables to CN1 or 2 on the front panel boards and CN5 on the Main Card cables to
CN1 or 2 on the back pan boards
3.2 Programming
Refer to the Operation and Programming Manual to program the above options into the FACP.
Note: The Configuration label should be updated once the panel has been upgraded.
4
Installation and Wiring of Add On Cards and Boards
CAB1925 to Batteries
CAB1902
CAB1905
CAB1911 TO MAINS EARTH
CN1
CN2
CN2
CN1
ALARM 2
N/C
COM
N/0
BATT FAIL
N/C
C OM
N/0
ISOLATE
N/C
COM
N/0
FAULT
N/C
C OM
N/0
ALARM 1
N/C
C OM
N/0
TB1-TB5
POWER
0V
+27V
0V
+2
7V
CN2
CN1
CN3
CN4
PO
W
E
R
+2
7V
0V
CN1
CN2
+27v Power fitted when Relay or Termination Boards are fitted
CN1
CN2
CN5
CN9
CN1
CN2
CN2 CN1
CAB2200
CAB2117
CAB1905
CAB2200
CN6
PO
W
E
R
+2
7V
0V
CN1
CN2
PO
W
E
R
+2
7V
0V
CN1
CN2
MAIN CONTROL CARD
OPTIONAL CARDS
AGENT RELEASE
FAN CONTROL
GENERAL INDICATOR
OPTIONAL BOARDS
AGENT TERMINATION
RELAY
FAN TERMINATION
INPUT
SOUNDER TERMINATION
A BATT BOX IS REQ
IF THESE BRDS ARE FITTED
OTIONAL
BRIGADE BOARD
CAB2200
CAB2200
BRD25ARB PCB0783 (AGENT RELEASE MODULE)
BRD25ATB PCB0787 (AGENT TERMINATION BOARD)
BRD25BBA PCB0779 (BRIGADE BOARD)
BRD25EWRB PCB0770 (8 WAY RELAY BOARD)
BRD25FCB PCB0783 (FIRE FAN MODULE )
BRD25FTB PCB0780 (FAN TERMINATION BOARD)
PSU1887
C N3
CN4
C N3 C N4
C N3
C N4
BRD25GIB PCB0781 (GENERAL INDICATOR CARD)
BRD25MCB PCB0769 (MAIN CONTROL CARD)
BRD25PSU PCB0813 (POWER SUPPLY UNIT)
BRD25SIPB PCB0778 (SINGLE INPUT BOARD)
BRD25SOPB PCB0772 (SOUNDER OUTPUT BOARD)
OPTIONAL CARDS
AGENT RELEASE
FAN CONTROL
GENERAL INDICATOR
OPTIONAL BOARDS
AGENT TERMINATION
RELAY
FAN TERMINATION
INPUT
SOUNDER TERMINATION
A BATT BOX IS REQ
IF THESE BRDS ARE FITTED
OPTIONAL BOARDS
AGENT TERMINATION
RELAY
FAN TERMINATION
INPUT
SOUNDER TERMINATION
A BATT BOX IS REQ
IF THESE BRDS ARE FITTED
BUS 1
BUS 2
BUS 3
BOARD
IDENTIFIERS:
CN8
CN10