Installation & Commissioning of Control & Monitoring Add On’s
Page: 9
4.7
Switch and Indicator Card BRD25GIB - B
This Card can effectively perform 2 different functions. Firstly the indicators monitor the first 8
inputs of the 16 Way Input Termination Board while secondly the switches can be programmed to
manually operate a specific relay in the system.
Quiescent Current:
3.6mA
Card & PCB Securing Tabs
( Top & Bottom )
PCB
Clea
r Pla
stic C
lip In
Lab
el
Clip on
Plastic Surround
( Push down here and pull
out to remove and insert labels )
Note: As per AS 1668
lettering on any of the
slip in labels must be
at least 5mm in height.
Windows for
Slip in Label
Slip In Label
WINDOWS FOR
SLIP IN LABEL
K2 Termination
Link
In
Out
Address
Switch
Set to 1
1
2 3 4
ON
C
N
1
C
N
2
CN1: Communications & 27V IN
from CN2 off the previous Front
Panel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.
If Unsed the Termination Link Must be Inserted.
Top Front Panel Card &
PCB Securing Clips
Bottom Front Panel Card &
PCB Securing Clips
Figure 14: Front Panel Card & PCB Layout
4.8
Zone Mimic Indicator Card ( Int. Pwr. ) BRD25GIB -C
The internally powered Zone Mimic Indicator Card connects to the FACP 27 volt power supply
and the internal communications bus for indication control. The card provides remote visual
indication of any Zone in an Alarm and / or Fault / Isolate condition. A maximum of 8 of these
cards can be connected to, or daisy chained together, on any one system. Slip in labels identify
the monitored Zone. The Alarm LED’s flash for an un – acknowledged alarm and are steady for
acknowledged. The Fault / Isolate LED’s flash for a Fault condition and are steady if a Zone is
Isolated.
Quiescent Current:
14mA
Card & PCB Securing Tabs
( Top & Bottom )
Clip On
Plastic Surround
( Push down here and pull
out to remove and insert labels )
Lettering on slip in
labels must be at
least 5mm in height.
Slip In Label
PCB
Alarm
Isolate
Fault
Windows for
Slip in Label
K2 Termination
Link
In
Out
Address
Switch
Set to 1
1 2
3 4
ON
C
N
1
C
N
2
CN1: Communications & 27V IN
from CN2 off the previous Front
Panel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.
If Unsed the Termination Link Must be Inserted.
Top Front Panel Card &
PCB Securing Clips
Bottom Front Panel Card &
PCB Securing Clips
Figure 15: Front Panel Card & PCB Layout
Note:
Except for CN1 & 2 being fitted and TB1, HY1 the Buzzer and CN6 not being fitted the
underside of this card is the same as for the externally powered card.