26
MAN3038-2
DISCOVERY PRODUCT GUIDE
Features
•
15 evacuation tones and 15secondary or alert tones
•
7 volume levels
•
Software-defined group addressing
•
Alarm switching by individual device, by group or of all devices on loop
•
Independent control of sounder and beacon
•
Set-up and testing of devices at point of installation
•
Isolator status information
Product Description
EN54-3
Discovery Sounder Beacon Base with Indicator
45681-393AMP
White Base Sounder Cap
45681-292
Red Base Sounder Cap
45681-293
Technical Data:
Specifications are typical and given at 23°C and 50% relative humidity unless specified otherwise.
Audio/Visual Type:
Point type sounder/beacon for fire detection and alarm systems for
buildings
Operating Voltage:
17-28V d.c. (polarity sensitive)
Protocol Pulses:
5-9V
Current consumption at
24V:
Switch on surge, <1s = 1.2mA
Quiescent = 350µA
Device operated at maximum volume = 8mA
Maximum sound output
at 90°:
90±3dB(A) Sound pressure level data is published in Product Data Sheet
PDS201-9002
Operating Temperature:
-20°C to +60°C
Humidity (no
condensation or icing):
0-95%
IP Rating:
21D
Note; do not connect XP95 sounders if Discovery sounders are being used.