If ENTER PASSWORD is selected, the password entry screen will be presented
allowing the user to enter the access level 3 passwords.
7.1.1
Passwords
The FACP will support 99 user programmable passwords. Each password includes an access level
which can be either 2 or 3 corresponding to the access levels and a unique ID which ranges from 1
to 99. There is also a facility in the access level 3 SETUP menu to add, edit or delete passwords.
Note:
Onsite programming only allows for the editing of ID1 and ID2 all other ID
’s need to be
set using the
LoopMaster
configuration tool
All passwords are a 4 digit numeric entry and the system default passwords are as follows:
ID
Password
Access Level
1
3333
3
2
User Defined
User Defined
Password Conditions
1. All password IDs that have not been assigned a password are set to access level 1 to
prevent false entries.
2. The entering of a password will be logged using the ID.
3. If no key is pressed for 5 minutes the access level will timeout to the default access level
being 2 or 1 depending on the key-switch position.
4. The access level timeout and key-switch operations will also be logged.
5. The intervals between key presses when entering the password must not exceed 30
seconds otherwise the password entry screen will timeout returning the panel to the default
access level.
6. The FACP can also be forced to the default access level by pressing the CANCEL key 4
times while default screen is displayed.
7.1.2
Misplaced Password
In the situation, where access to the panel is required, and the passwords are not available, there is
a facility for the appropriate service personnel to gain access to the panel.
The procedure is as follows:
1. The pas
sword “
#
,
,
,
,
,
#
” is entered.
2. The panel responds by displaying a unique 10 digit key
3. Contact the local Ampac Service Centre and they will issue a temporary password
4. The temporary password is entered, and access is gained to the panel. The operator can
now access the password menu and set the passwords up as appropriate for the installation
The temporary password will be deleted, the next time a password is successfully entered into the
FACP.