Page 31
FIREFINDER SERIES II
INSTALLATION,
COMMISSIONING
&
OPERATION
The type of log, number and totals logged, date and time of the ALARM,
FAULT, ISOLATE, SYSTEM or I/O as well as device information will be
displayed. The SYSTEM screen displays events and watchdog activity. From these screens the
operator can select two other facilities, they are;
Press
PRINT ENTRY
will print out the displayed information if a printer is installed, or
SHOW OPTIONS
allows the operator to select how the Logs are viewed
.
Press
to
VIEW BY
ENTRY NUMBER
or
to
VIEW BY DATE
. In each case the screen will ask for
the appropriate information (ENTRY NUMBER or DATE) to be entered before the selected option
will be displayed.
NOTE:
it is possible to scroll through the alarms by using the PREVIOUS and NEXT keys.
8.5
The Function Test Facility
Press
TESTS:
prompts the operator to select either the
WALK
or
LOOP
test.
Press
WALK TEST;
the operator will be prompted to select either
ZONE
or
SENSOR
test.
Press
ZONE WALK TEST MENU;
This screen requires the operator to select a Zone or number of Zones to be tested, that is enter the
Zone number pres ENTER or enter the Zone number press TO then the next highest Zone
number o be tested EG. 2 TO 7 then ENTER.
The
TEST
MODE LED
will be illuminated for the duration of the test and the test will run until the
operator
RESETS
the system or the test times out [Time Out = 15 m 3 to 5 seconds].
Press
SENSOR WALK TEST MENU
This screen requires the operator to select a Zone and then a Sensor or (number of Sensors using
the TO key) to be tested then pressing ENTER to start the test.
The
TEST
MODE LED
will be illuminated for the duration of the test and the test will run until the
operator
RESETS
the system or the test times out [Time Out = 15 m 3 to 5 seconds].
Press
LOOP TEST
requires the operator to select a
LOOP
for
DIAGNOSTIC TESTING
Entering the LOOP number and pressing ENTER will initiate the
DIAGNOSTIC TEST
.
NOTE:
The LED’s on the Brigade Board will indicate which leg is being tested.
The tests displayed are;
TESTING SIDE A
IDENTIFING DEVICES on SIDE A, and
TESTING SIDE B
IDENTIFING DEVICES on SIDE B.
Once the testing is completed the final screen will display the number of devices found and tested on
the LOOP and a Reset is requested to return the system to normal.
NOTE:
If the data is not entered within 2 minutes the screen will time out and return to the
DEFAULT SCREEN.