Description: 

The LED Mimic (302-715), LED Mimic Display Board 
(302-733), and the 

FireFinder

 Controller Interface Card 

[CIC] (302-725) is designed to provide remote indication 
of the current status of an NZ 

FireFinder

 FACP. The 

mimic will indicate any zones, or sensors in alarm as 
well as providing common Fire, Defect, DBA, system 
Normal indication, and a General Purpose Relay 
Output. 

LED Mimic 302-715 Specifications 

Function Keys  Lamp Test 

Lamp Reset 

Buzzer Mute 

CPU Reset 

Address Switches 

System Switches 

Indicator 

(LED’s) 

Power On 

Normal 

Fault 

Power Supply 

TB1:

 20 to 28VDC @ 100 mA 

CN6:

 5 volt output (aux power) 

Outputs 

CN1, 2, 3 & 4:

 32 outputs for Zone 

indication  

CN5:

 5 outputs for Fire, Pre-Alarm, 

DBA, Defect and Normal indication 

CN5:

 1 buzzer output 

TB4:

 General Purpose Output, 1A 

Voltage-free changeover contacts 

Inputs 

CN5:

 5 inputs for Mimic Reset, Lamp 

Test, Buzzer Mute, Bell Isolate and 
Evacuate 

 

The LED Mimic derives power (Max 2 Amps) and 
RS485 comms from the 

FireFinder

 CIC (302-725). In 

small systems with 1, or 2 LED Mimics on cable runs of 
less than 400 meters suggested cabling is 2 Pair 
Twisted 100

 Shielded Data Cable (0.2mm² cores 

minimum) e.g. OLEX JECP87F5002, BELDEN 9804. In 
larger systems with more than two LED Mimics or long 
cable distances use 1 Pair Twisted 100

 Shielded Data 

Cable e.g. OLEX JECP87F5001, BELDEN 9841 for 
communications. It will be necessary to supply power to 
LED Mimics via separate cables. The size of the power 
cables will depend on the number of mimics used and 
the total distance Table 2. 

Operation of the LED Mimics is not monitored by the 
FACP. If communications to the LED Mimics fail, the 
LED Mimic will flash the 'Defect' LED rapidly to indicate 
a communication defect. Correct operation of the LED 
Mimic and FACP is confirmed by the 'Normal' LED 
flashing on the LED Mimic. 

Recommended Maximum Cabling Distances using 2 
Pair Data Cable. 

Number of LED Repeater Boards 

Max Distance 

1 400m 

2 200m 

Table 1 

Recommended Power Cable Sizes for Larger 
Systems 

Number 
of LED 
Mimics 

Distance
= <500m 

Distance
= 500m< 
>1Km 

Distance
= 1Km< 
>1.5Km 

Distance
=1.5Km< 
>2Km 

1 0.3mm² 

0.5mm² 

1mm² 

1.5mm² 

2 0.5mm² 

1mm² 

1.5mm² 

2.5mm² 

3 0.75mm² 

1.5mm² 

2.5mm² 

4mm² 

Table 2 

Installation: 

Controller Interface Card 302-7250 & LED Repeater 
Board 302-7150. 

Observe anti-static precautions at all times 

1.  Power system down, and remove batteries. 

2.  Mount the Controller Interface Card on standoffs in 

the left side of the panel. 

3.  To connect the CIC to the 

FireFinder

 Main Board 

302-674, plug one end of the sixteen-way cable 
provided into CN1 of the CIC and the other end into 
CN18 of the Main Board 302-674. Connect TB1 
and TB3 of the CIC to the external cabling. 

4.  Mount the LED Mimic Board 302-715 and the 

Expansion LED Board 302-733 on stand-offs within 
an enclosure. Connect TB1 of the 302-715 LED 
Mimic to the external cabling then connect as 
shown in Table 3. 

LED Mimic Board 

Expansion Board 

CN5 CN1 

CN1 CN2 

CN3 CN3 

Table 3 

5.  Set Switches as follows SW2-1 ON, SW2-2 OFF, 

SW2-3 OFF, SW2-4 OFF, SW2-5 OFF, SW2-6 
OFF , SW2-7 OFF, and SW2-8 OFF (All LED 
Mimic Boards are set to address No. 4). 

6.  Power up and test LED Mimic functions. 

 