AMP mounting and user manual, Pumps 2022-1   

page 4 of  14 

 

3.0 OPERATION DIRECTIONS 

 
3.1 WATER CONNECTION

 

Water connection to the pump uses a regular water hose minimum 3/4” in diameter and minimum 
1,5 bar pressure (The pump itself just need more than 0 bar). The water is lead into the pump 
through low pressure filters.

 

Flow direction is indicated by an arrow on the filter housing.

 

Please 

check the filters for impurities by routine. Filter house is delivered with a standard 5µm cartridge 
filter inside.  

 
3.2 START/STOP PROCEDURE 
 
Start

 

Observe that the stop button on the electrical box is set to “OFF” to assure it is turned off. 
Turn on the water supply and turn the power switch to “MAN”. Your system will now be filled with 
water. Now the pump system is ready for manual or automatic operation.  

 
Stop

 

Stop the pump system by turning the power switch to “OFF” and pump system will stop 
immediately.  

 
3.3 PRESSURE REGULATION

 

The pump has a pressure regulation. Factory settings are max. 70 bar. This basic adjustment must 
not be changed. Pressure regulation is automatic with different numbers of nozzles. 

 
3.4 FUNCTION

 

The pump system is provided with a manual and an automatic mode. 

 
MAN: 

Used when the pump system must run continuously (manual), such as soaking etc.  
In the manual position, there is no security system for pressure, bleed-off etc. 

 
OFF:         

Pump system is turned off. 

 
AUTO:  

Used when the pump system must run automatically (normal position). Can start the pump system 
by external thermostat, timer, or other control systems. If the pump system does not reach operating 
pressure within a given period of 20 sec., it will turn off. Before re-starting the pump system, the 
cause of failure must be found. This function is controlled by a 25-bar pressure switch. 
To restart – turn off the switch and return to “AUTO” mode again.

 

 

V-belt drive: 

After few hours of operation, make a control, that the operation in total is OK including an extra 
control, that the pulley is tensioned and in the right position. 
Inside the belt house, you find an extra V-belt – for service if needed. 

 
 
 

 

 

Summary of Contents for AMP 21x-2

Page 1: ...nting and user manual Pumps 2022 1 page 1 of 14 AMP User manual for 70 bar aqua misting pump system for cooling and humidifying This unique type plate is placed both inside the cabinet and on the head...

Page 2: ...20xD46 Dimension wall W cm W65xH90xD42 W65xH90xD42 W60xH120xD42 W60xH120xD46 Weight all incl approx 51 kg 55 kg 65 kg 72 kg Dimension shipment 80x60xH55 cm 80x60xH55 cm 80x60xH55 cm 80x60xH55 cm Noise...

Page 3: ...ump system must not be operated if cable or safety devices are damaged The pump system may only be used for humidifying of air it may not be used as a high pressure cleaner Water pressure from the pum...

Page 4: ...has a pressure regulation Factory settings are max 70 bar This basic adjustment must not be changed Pressure regulation is automatic with different numbers of nozzles 3 4 FUNCTION The pump system is...

Page 5: ...ose and the high pressure hose pipe Pipe system and couplings should be cleaned for dust and sand no particles inside pipes To empty the pump for water Disconnect the hose pipe before and after the pu...

Page 6: ...provide sufficient water flow Water supply more than 0 bar specification 1 5 bar High pressure more than 40 bar Pressure is unstable and bumping Water supply is insufficient or clogged Water inlet fil...

Page 7: ...y max 500 hours or once every year Control of the V belt Push with 1 kg pressure on center of V belt through inspection hole and the belt should move from 4 to 6 mm If more than 6 mm you need to tight...

Page 8: ...AMP mounting and user manual Pumps 2022 1 page 8 of 14 Delivery and mounting the pump Delivery Demounting from transportation pallet...

Page 9: ...able to handle capacity down to 0 0 l h with a temperature safety system The pump and low pressure solenoid valve operate simultaneously A non return valve ensures that water remains in the main pipe...

Page 10: ...AMP mounting and user manual Pumps 2022 1 page 10 of 14 Wall mounting Mounting details close up...

Page 11: ...re used for simple start up and as a main safety circuit breaker High pressure connection with Stainless steel pipe Normal connection A ball valve not allowed B Free distance without pipe hanger from...

Page 12: ...of 14 How to replace a pump service pump View of the replacement pump Demount the high pressure pipe Demount the by pass hose Demount the high pressure set Demount the filter set The pump is ready for...

Page 13: ...V belts are properly tensioned again Be sure that the V belt are OK tightened Control of the V belt Push with 1 kg pressure on center of V belt through inspection hole and the belt should move from 4...

Page 14: ...hose 4 Make a manual start of the pump be sure the pump works OK and makes the right pressure without any disturbing sounds 5 Open the end of the high pressure pipe one by one if more pipelines 6 Star...

Reviews: