Signal Test Unit STU-20
By activating the button „Reference“ the measurment can be triggered on the
reference signal of the encoder.
Interpretation of the measuring results
4.7.3
The measured signal accuracy will be displayed at the bar graph „System accu-
racy“.
Results higher than 0,7 indicates a high signal accuracy.
Results inbetween 0,7 and 0,4 indicates that signal accuracy is good but can be
increased by improving the mechanical mounting conditions.
Results less than 0,4 indicates a low signal accuracy maybe caused by moun-
ting conditions that are out of tolerance.
The interpretation of the measuring results can differ from that stated above and
depends on the type of axis, kind of drive etc.