background image

Appendix B

Wiring Diagram – Annunciator

NOTE: 

Amico recommends max. 50 ft. to power up buzzer from any Amico devices (alarm/manifold). More 

than 50 ft., a A3P-Power-V4 is required to supply voltage for the manifold buzzer. 

  

   

www.amico.com 

   

 25

Summary of Contents for Alarm Valve Combo Unit

Page 1: ...Installation and Maintenance Manual Alarm Valve Combo Unit Alert 1 v1 6...

Page 2: ...ciator Module 8 Alarm Valve Display Module 8 Sensor Module 8 Installation of Alarm 9 10 Local Sensor Only 9 Standing Pressure Test 9 Frame Module Assembly 9 Sensor 10 Local 10 Remote 10 Wiring 11 Syst...

Page 3: ...p Switches 16 Troubleshooting Guide 17 19 Table of Error Codes 17 19 Error Code Messages on the Display Module 19 Model Numbers 20 21 Spare Parts Numbers 22 Dimensions 23 Appendix A Wiring Diagram Aut...

Page 4: ...Corporation or their distributors All alarms should not be repaired or altered without prior written or verbal approval of Amico Corporation or its distributors Failure to comply will void all warran...

Page 5: ...HI and LOW set points on display module Available in 1 to 7 display modules Built in relay for remote annunciator applications Introduction The Alarm Valve Combo Unit is a 2 in 1 design which combine...

Page 6: ...ool remove rags 3 Test the system per appropriate standards to ensure that the intended gas and vacuum services are connected to the appropriate lines WARNING Misconnection of the gases could lead to...

Page 7: ...lose shutoff valves in the event of fire explosion or damage to the pipeline systems or equipment In Alarm Valve Combo Unit boxes the Shutoff Valve handles become accessible after the window has been...

Page 8: ...Appendix B for connection to another Amico alarm or a building management system Alarm Valve Display Module The module provides a digital display of the actual pressure vacuum of a gas being monitored...

Page 9: ...the brazing of pipe stubs has been completed the system can be pressure tested Standing Pressure Test Perform a standing pressure test on the piping system as per NFPA 99 Health Care Facilities or CSA...

Page 10: ...so that it makes a good seal CAUTION The microprocessor circuitry on the alarm valve unit contains sophisticated integrated semiconductors If it becomes necessary to remove a module PLEASE hold the bo...

Page 11: ...nd attach it to terminal Sensor on the display module Take the black wire from the sensor and attach it to terminal Sensor The terminal block on the display module is clearly marked for proper connect...

Page 12: ...ensor from Area Module v4 0 P a g e 1 6 FIELD ADJUSTMENTS THE ANNUNCIATOR MODULE NOISE LEVEL CONTROL Factory Default 90 Decibles To decrease noise level 1 Locate jumper at J5 Move jumper to LVL1 90 dB...

Page 13: ...desired value 3 Set switch 7 to the OFF position 4 The LED will display LO followed by the current set point Indicating the system is ready to accept a new Low set point Adjust set point using the UP...

Page 14: ...HI followed by the current set point Indicating the system is ready to accept a new High set point Do not adjust this set point since the High set point is not used 3 Set switch 7 to the OFF position...

Page 15: ...the repeat alarm function is disabled the alarm will not repeat Enable Enable Mode Factory Default 30 min when enabled Set switch 5 to the ON position PLEASE NOTE The module with the lowest set Repea...

Page 16: ...TCH TAMPERING WITH THESE POSITIONS WILL RESULT IN AN ERROR MESSAGE BEING DISPLAYED EO2 AND WILL DISABLE THE ELECTRICAL INTERLOCK FROM THE GAS SPECIFIC SENSOR CHANGES TO THESE SWITCHES SHOULD ONLY BE D...

Page 17: ...h on the power supply module is turned ON AC wiring not connected Check the building electrical breaker to ensure that the power is ON Check the voltage at the terminal block above the transformer Ens...

Page 18: ...le signal will not silence Faulty display module Disconnect the ribbon cable from the back of the faulty display modules and replace the module s Connection of the DC power cable from system power sup...

Page 19: ...tion Page E01 No sensor is connected or board failure Connect a sensor and check circuit board 26 27 E02 Sensor and Display Module mismatched Ensure that the Sensor and Display Module are for the same...

Page 20: ...1 2 deep valve box are the same as the 3 7 8 deep valve box When comparing height measurements consider the gap above the 2 valve Example a valve box with 1 2 valve 2 valve and a power supply would be...

Page 21: ...ALERT 2 SENSOR MODULE USA AIR ENG ALERT 2 SENSOR MODULE USA OXY ENG ALERT 2 SENSOR MODULE USA VAC ENG ALERT 2 SENSOR MODULE USA WAG ENG ALERT 2 SENSOR MODULE USA INSTRUMENT AIR ALERT 2 AVC DISPLAY MO...

Page 22: ...ARM VALVE COMBO DIVIDER PLATE FOR 3GAS ALARM VALVE COMBO DIVIDER PLATE FOR 4GAS ALARM VALVE COMBO DIVIDER PLATE FOR 5GAS ALARM VALVE COMBO DIVIDER PLATE FOR 6GAS ALARM VALVE COMBO P S COVER FOR ALARM...

Page 23: ...Dimensions Vertical Alarm Valve Combo Unit Remote Sensor approximate can vary 1 88 48 Wrench Flats 1 25 DISS CONNECTOR 1 2 Conduit Connection Inch mm 1 2 14 NPSM 13 see thread specs www amico com 23...

Page 24: ...witched off prior to working on the alarm 2 Risk of electric shock disconnect power at the circuit breaker before removing power supply shield AC Supply 115 to 220 VAC DC Power Cable Connect to Annunc...

Page 25: ...ing Diagram Annunciator NOTE Amico recommends max 50 ft to power up buzzer from any Amico devices alarm manifold More than 50 ft a A3P Power V4 is required to supply voltage for the manifold buzzer ww...

Page 26: ...y 115 to 220 VAC Power Supply L Live N Neutral G Ground Toggle Switch ON OFF Ground G N L 6 8 0 1 m 0 2 m 22 gauge stranded shielded twisted pair cable supplied Sensor Module Sensor Module Sensor Modu...

Page 27: ...Alarm and sensors 6 8 0 1m 0 2 m 22 gauge stranded shielded and twisted pair cable supplied Marrette the sensor cable in a junction box supplied by others to the installation cable supplied by others...

Page 28: ...C NO HIGH ALARM COM NC NO LOW ALARM AC Supply 115 to 220 VAC Power Supply L Live N Neutral G Ground Toggle Switch ON OFF Ground G N L 6 8 0 1 m 0 2 m 22 gauge stranded shielded twisted pair cable supp...

Page 29: ...less or other interference cable installation MUST be placed in metallic conduit Signal 30 VDC 1 0 Amps 60 VDC 0 3 Amps 125 VAC 0 5 Amps AVC Display Module to Master Module Distance Maximum 10 000 fee...

Page 30: ...nnecting sensors or master alarms to source equipment 8 To protect from static electricity ensure to discharge body static before installing the Medical Gas Alarm and Sensors 9 Do not ground the shiel...

Page 31: ......

Page 32: ...rporation 85 Fulton Way Richmond Hill ON L4B 2N4 Canada 71 East Industry Court Deer Park NY 11729 USA Toll Free Tel 1 877 462 6426 Tel 905 764 0800 Fax 905 764 0862 Email info amico com www amico com...

Reviews: