Data and Alarm Channel Configuration

The

AMG5516

sends and receives data to/from an

AMG5515

single channel standalone transmit unit.

The physical data interface RS-485, RS-422 or RS-232 is individually selectable by the user with the
corresponding slide switch mounted on the main PCB inside the enclosure.

2 uni-directional alarms are also provided, each of which can receive an on/off signal from an

AMG5515

and are typically used to convey contact closure status. Each alarm output uses a Solid-

state relay, with a maximum load current of 150mA at 125Vac/dc and Ron < 6.5Ω. 

Data Channel Configuration

Each low speed data channel provides an RS-232, RS-422 (full duplex, four wire) or RS-485 (half
duplex, two wire) interface defined by the corresponding mode switch inside the enclosure. Every data
channel as shipped from the factory is set up for RS-485 operation unless otherwise requested.

The data input for both the RS-485 and the RS-422 modes detects a tri-state input condition by
monitoring the differential voltage level across the input. A differential level below 600mV positive or
negative will be detected as a tri-state condition. A level above 600mV positive or negative will be
detected as a logic 1 or logic 0 respectively. It is important therefore to terminate the RS-485 bus or

the RS-422 input bus using 120Ω if a pre-bias is present on the RS-485 or RS-422 bus.  

A large number of third party equipment manufacturers apply a pre-bias on their RS-485 bus. This pre-
bias is applied by pulling one arm of the RS-485 bus high (+5 volts) and the other arm low (0 volts)
using high value resistors within the third party equipment. In order to ensure that the AMG equipment

detects a tri-state condition, then these resistors should have a value above 5kΩ.  If the third party 
bias resistors are less the 750Ω the bus can be multiple terminated as required to ensure that a tri-

state level is detected.

Summary of Contents for AMG5516

Page 1: ...ta Channel and two Uni directional Alarms for a Singlemode Fibre Link The AMG5516 is a standalone system designed to receive two uni directional alarms and transmit and receive one data signal over a...

Page 2: ...Optical Connection 3 Connections 4 Optical Connections Singlemode 4 Power Connection 4 Data and Alarm Channel Connections 4 Front Panel Indicators 5 Power Opto LED 5 Low Speed Data LEDs 5 Alarm LEDs 5...

Page 3: ...roduction Unit Functional Schematic The AMG5516 transmits 1 data channel to and receives 2 uni directional alarm signals from the AMG5515 transmit unit It also receives 1 data channel transmitted from...

Page 4: ...0dB Power Connection Connector Type Removable 2 pin 3 81mm Screw Terminal Connector Partno Phoenix 1803578 Supply Voltage 12 to 15 Volts DC Maximum Power 2 5 Watts Data and Alarm Channel Connections N...

Page 5: ...n IN IN Data Present IN RS232 Green logic zero V present on input IN Red logic transitions present on input IN Off logic one V present on input IN IN corresponds to the data signals being transmitted...

Page 6: ...corresponding mode switch inside the enclosure Every data channel as shipped from the factory is set up for RS 485 operation unless otherwise requested The data input for both the RS 485 and the RS 42...

Page 7: ...middle RS 232 switch bottom 1 IN A IN 2 IN B 3 GND GND GND 4 5 6 7 IN OUT A OUT A 8 IN OUT B OUT B OUT Note A or B in brackets in the above table refers to RS 485 RS 422 data specification Alarm Chan...

Page 8: ...g screws on the rear panel and slide the PCB sufficiently out of the case to enable access to the switch To replace the PCB into the case slide the PCB gently into the case if necessary aligning the b...

Reviews: