background image

Calibration

11

Section  4:  Calibration

This section contains the calibration information for the 

Z-tron III Level Control.

CAUTION:
Do not open enclosure cover or make/break any 

electrical connections without first disconnecting 

electrical power at the source.  Ensure that area is 

non-hazardous. Ensure that wiring, electrical fittings 

and conduit connections conform to the electrical 

codes for the specific location.  

The Z-tron III level control is a general purpose device 

and is not agency approved for use in hazardous 

locations.  If agency approval is required, contact your 

local AMETEK  Drexelbrook representative or call  

1-800-553-909

4.1  Calibration in Conducting Material

All Z-tron III controls  are factory set to switch in water-

based conducting materials [setpoint adjustment is set to 

full clockwise (CW) position].  No calibration adjustment is 

necessary.
If this instrument had been previously adjusted for use in a 

insulating materials, and is now intended for use in a 

 

conducting material, use a small screwdriver to turn the 

setpoint adjustment to the full clockwise (CW) position. No 

other adjustment is necessary.

4.2  Calibration in Insulating Material [Horizontal Mount]

Use the following procedure:

1.  Be sure the material level is well below the sensing 

element.  

See Figure 4-1.

2.. Turn the setpoint adjustment to the full 

counterclockwise (CCW) position.

This 20-turn potentiometer does not have a 

mechanical stop.  Turn 20 times to assure that you are 

at the extreme end.  No damage will occur.
The LED (on) indicates that the relay is energized or 

in normal condition (not alarm).

3.  Turn setpoint adjustment slowly clockwise (CW) until 

the relay just operates.  (LED changes state).

4.  Increase the material level until it is well above the 

sensing element.  

See Figure 4-2.

  (LED changes state).

5.  Mentally note the position of the screwdriver.
6.  Counting the number of turns, turn the setpoint 

adjustment slowly clockwise (CW) until the relay once 

again just operates.

Summary of Contents for Z-tron III

Page 1: ...America 215 674 1234 Installation and Operating Instructions Series Z0X 2 Z tron IIITM Level Control U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 21...

Page 2: ...n this manual including but not limited to implied warranties or fitness for a particular purpose Drexelbrook shall not be liable for errors contained herein or for incidental or consequential damages...

Page 3: ...2 LM Issue 11 205 Keith Valley Road Horsham PA 19044 U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 215 674 2731 E mail drexelbrook info ametek com We...

Page 4: ...Table of Contents...

Page 5: ...Start up 10 Section 4 Calibration 11 4 1 Calibration in Conducting Material 11 4 2 Calibration in Insulating Material Horizontal Mount 11 4 3 Calibration in Insulating Material Vertical Mount 12 Secti...

Page 6: ...Section 1...

Page 7: ...ctive applications or the probe and the vessel wall insulating applications increases This is due to the dielectric constant k of the material which causes a bridge misbalance The signal is demodulate...

Page 8: ...l 700 0206 201 14bar 121 C 316SS Purpose 200psi 250 F PEEK Cote ShieldTM Length A 10 inch 254mm B 3 5 inch 88 9mm C 2 inch 51mm I 6 inch 150mm Insertion Length IL A 6 inch 152mm B 12 inch 305mm C 18 i...

Page 9: ...n Ambient temperature should be between 40 F and 145 F 40 C to 63 C It may be mounted either vertically or horizontally See Figures 2 1 and 2 2 Avoid mounting closer than 1 inch to any tank structure...

Page 10: ...d up does not extend past first insulator Cote shield must extend through nozzle and wall build up by 2 Wrong Nozzle too long Cote shield too short Factory supplied Cote shield extends through nozzle...

Page 11: ...Introduction 5 Figure 2 3 Mounting Dimensions Integral Z tron III Level Control 2 3 Mounting Dimensions Use a pipe wrench in this area for mounting to the process connection on the vessel...

Page 12: ...ntact your local AMETEK Drexelbrook representative or call 1 800 553 9092 Refer to Figures 2 5 through 2 7 for the appropriate power wiring and use the following procedure to wire the Z tron III level...

Page 13: ...the 120 VAC Electronic Unit Relay Connections HOT L2 Neutral L1 Ground GND Power Connections 240Vac 240 VAC Use 12 28 gauge wire 2 4 Power Wiring continued Relay Connections HOT L2 Neutral L1 Ground...

Page 14: ...ON HIGH LEVEL FAIL SAFE LED ON TANK EMPTY HIGH LEVEL FAIL SAFE LED OFF ALARM TANK FULL LOW LEVEL FAIL SAFE LED OFF ALARM NORMAL NORMAL NORMAL TANK EMPTY LOW LEVEL FAIL SAFE TANK FULL 1 2 3 4 5 6 7 8...

Page 15: ...a single operating point adjustment used to control the level at which the relay operates See Figures 2 8 3 1 This adjustment is an 20 turn potentiometer and does not have a mechanical stop When in H...

Page 16: ...etermines the condition of the relay upon loss of power or upon the failure of most components The failsafe mode may be selected in the field by changing the position of slide switch 1 located on the...

Page 17: ...ment had been previously adjusted for use in a insulating materials and is now intended for use in a conducting material use a small screwdriver to turn the setpoint adjustment to the full clockwise C...

Page 18: ...ure that you are at the extreme end No damage will occur The LED on indicates that the relay is energized or in normal condition not alarm 1 Set the level to a point on the active section of the sensi...

Page 19: ...tor switch Fig 3 1 If LED does not change state along with relays Electronic Unit has failed 3 Remove power from unit loosen hold down screws then remove unit Remove Blue screw from top of sensing ele...

Page 20: ...ed Lug 600 ohms Red Lug to Housing 300 ohms 6 Resistance values lower than this could mean Extremely conductive coating on probe which is an application problem You may wish to call the factory for su...

Page 21: ...osed with high or low level Refer to Figures 2 10 and 5 2 2 Relay operation may generally be heard as an audible click when the background noise is not too high Use one of the methods shown in Figure...

Page 22: ...c Improper wiring d Improper calibration e Electronic unit malfunction a Need longer Cote Shield Consult factory b Need longer insertion length Consult factory c See Section 2 d See Section 4 e See S...

Page 23: ...gth Original Purchase Order Number Material being measured Temperature Pressure Agitation Brief description of the problem Checkout procedures that have failed 5 7 Field Service Trained field servicem...

Page 24: ...se all chemicals and decontaminate the sensing element To obtain a return authorization RA contact the Service department at 1 800 527 6297 US and Canada or 215 674 1234 International Please provide t...

Page 25: ...ce Center to Ground 1500 ohms Center to Shield 750 ohms Shield to Ground 750 ohms Failsafe Field adjustable to either High Level Fail Safe HLFS or Low Level Fail Safe LLFS Output DPDT relay closure Co...

Page 26: ...ved for Class I Groups A B C and D Div 1 or 2 and Class II Groups E F and G Div 1 or 2 FM approval on housing only If agency approval is required use the Drexelbrook PXL The Point instrument for point...

Page 27: ...ge 5 Protect electronics from any heat Shortening The bare metal center rod of the sensing element can be shortened with a hacksaw Be careful not to cut either of the two insulators See Figure on this...

Page 28: ...not transfer any intellectual property rights to Buyer unless Seller specifically agrees to do so in writing Seller shall retain ownership of all applicable patents trademarks copyrights and other int...

Page 29: ......

Page 30: ...d Horsham PA 19044 U S and Canada 1 800 553 9092 24 Hour Service 1 800 527 6297 International 1 215 674 1234 Fax 1 215 674 2731 E mail drexelbrook info ametek com Website www drexelbrook com An ISO 90...

Reviews: