Ametek TELGUARD TG-PEM Quick Install Manual Download Page 2

Use the three provided mounting screws to secure the TG-PEM 
board onto the bracket. 

 

 

 

 

5. Connect the TG-PEM to TG-7 or TG-7FS 

 

Make sure there are no AC or DC power sources 
connected to the TG-7 or TG-7FS.  Connect power and 
ground from the TG-

PEM terminal labeled “TELGUARD 

POWER” to the terminal block on the TG

-7 or TG-7FS 

labeled DC and GND.  

Do not overtighten.

 

 

Connect ribbon cable (provided) from the connector on 
TG-

PEM labeled “TO HOST” to the 3x2 6

-pin header on 

the TG-7 series board as shown. The dark color edge of 

the ribbon cable should be oriented away from the 
antenna of the TG-7 or TG-7FS. 

 

6. Power Up and Configure 

 

Connect power and ground from the panel 

auxiliary output to the terminal labeled “PANEL 
POWER” on the TG

-PEM to provide power to the 

TG-PEM and TG-7 or TG-7FS. 

 

Complete the activation of the TG-7 or TG-7FS as 
outlined in the TG-7 series manual. 

 

If the TG-PEM was preconfigured, it should now 
be ready; otherwise, visit www.telguard.com to 
configure the TG-PEM. 

 

When the TG-PEM is configured and ready, LED 
D2 will be either solid amber (in power supply 
only mode) or solid green (in power supply and 
zone extender mode). 

 

7. Connect Zone Inputs 

(if using)

 

 

Temporarily disconnect the power while you 
connect any monitoring sensors to the zone 
inputs. 

 

For supervised zones, use a standard 2.2k

 EOL 

resistor (not included). 

 

Reconnect power, allow the TG-7 or TG-7FS to 
initialize, and check for proper operation. 

 
 

Optional:  Second TG-PEM Installation 

See full Installation Manual for mounting and wiring 
instructions. 

 

 

 

REFERENCE: 

 

LED 

D1 

LED 

D2 

STATUS 

DETAILS 

Off 

Green 

Ready, no 

activity 

TG-PEM is ready 

Off 

Off 

Shut down 

Power to TG-PEM is below 

minimum 

Any 

Amber 

flash 

Communicator 

activating 

TG is being activated 

Red 

Green 

Reportable 

event  

At least one enabled input is 
tripped or event(s) captured 

and waiting to be reported 

Red 

flash 

Green 

Event  

reporting 

Event(s) reporting or waiting 

for response 

Off 

Red 

flash 

Bootloader 

error 

Device failure, contact 

Technical Support 

Off 

Amber 

Power supply 

only or  

Not ready 

Power supply mode,  

TG-PEM waiting for 

configuration, or 

Communicator not enabled 

 

TO HOST  TO TG-PEM

D1   D2

Reset

TELGUARD 

POW ER

POW ER

PASS THRU

PANEL 

POW ER

DC  GND

ZONE INPUTS

1      C      2      3     C      4      5      C     6       7     C      8

G

N

D

  D

C

G

N

D

  D

C

```

TG-7FS 

LTE

3x2 6-pin header

Dark edge on right

LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8

DC            STC2   STC1   TRIP           BATT                AC

56051801 

– Rev A 

Note: At power-up, both LEDs will be on for 3 seconds then off for 3 seconds. 

Reviews: