CAUTION: 

Do  not  repeatedly  turn  an  RTi  /  RLi  product 

on-off-on-off  with  a  heavy  load  connected.  The  ICE

®

 

circuitry  absorbs  the  inrush  energy  each  time  the  unit  is 

turned  on  and  may  overheat  if  this  is  done  repeatedly  in 

a  short  period of time. Wait one minute between repeated 

turn-ons.

 

 

 

Remote Control  (RTi Products Only)

 

 

Remote  control  connections  are  wired  to  the  green  7-pin 
plug-in  Phoenix  terminal  block  on  the  rear  of  the  unit  next  to 
the  power  cord.  The  terminal  block  is  shipped  with  a  jumper 
wire  between  pins  1  &  2  so  that the  unit  can  be  used  without 
a  remote  control  connection.  If  you  will  be  using  a  remote 
control you will first need to remove this jumper wire. You can 
unplug  the  terminal  block  to  make  connections  and  after  you 
have made the connections to the terminal block, plug it back 
into  the  connector  on  the  rear  of  the  unit.  Never  solder  (tin) 
wires before inserting into a terminal block 

– solder cold flows 

and you will eventually have loose connections!

 

 

 

The connections are as follows:

 

 

Pin 1 -- Contact Closure

 

Pin 2 -- Contact Closure / Applied V 

Pin 3 -- Applied Voltage -

 

Pin 4 -- Remote LED + 

Pin 5 -- Remote LED -

 

Pin 6 -- Aux Relay Contact

 

Pin 7 -- Aux Relay Contact

 

 

 

Control Connections

 

 

Control  of  the  switched  receptacles  can  be  accomplished  by 

using a switch (contact closure), another SurgeX

® 

RTi product, 

or  by  an  applied  voltage  (5  to  30  volts  DC).  When  using  a 
switch,  choose  a  switch  with  gold  contacts  for  the  best  long- 
term reliability.

 

 

Connections  are  made  to  terminal  block  pins  1,  2  &  3  as 
follows:

 

 

•      Connect switch contacts, a contact  closure,  or SurgeX

®

 

control to pins 1 and 2.

 

Remote Indicator LED

 

 

Connecting the Remote LED is optional. An LED connected to 
pins  4  and  5  will  indicate  when  the  switched  receptacles  are 
on.  10mA of  current  is  available  at  this  output,  but  you 

must 

use  a  series  resistor 

if  you  are  using  your  own  LED.  For 

most LEDs a 1K resistor will provide suitable brightness. If you 

need less  brightness  use  a larger  value of  resistor,  and  if  you 
need more brightness use a smaller value of resistor.

 

 

•      Connect the LED positive wire to Pin 4

 

•      Connect the LED negative wire to Pin 5

 

 

Auxiliary Relay Contacts

 

 

The  auxiliary  relay  contacts,  pins  6  &  7,  provide  a  way  to 
cascade units or to provide confirmation feedback to a central 
controller.  When  the  switched  receptacles  are  on,  the  aux 
relay  contacts  are  closed.  There  is  a  1  second  delay  before 

the  aux  relay  closes  which  gives  time  for  the  SurgeX

®   

Inrush 

Current  Elimination  (

ICE

®

)  circuit  to  operate.  This  short  delay 

in  combination  with  the  SurgeX

®  

ICE

®  

makes  it  unnecessary 

to  sequence  the  power  to  several  large  loads  (such  as 

amplifiers)  because  of  inrush  current.  SurgeX

®   

RTi  products, 

when  cascaded,  can  turn  on  a  bank  of  large  amplifiers  with 
no  inrush  current,  and  therefore  no  risk  of  blowing  a  circuit 
breaker.

 

 

To  cascade  two  or  more  RTi  products,  connect  the  aux  relay 
contacts  of  one  unit  to  the  contact  closure  input  of  the  next 
unit.  To  provide  confirmation  feedback,  connect  the  aux  relay 
contacts to an input on the central controller.

 

 

The relay contacts are rated for 1 amp at 30 V DC.

 

Or:

 

• 

Connect  an  applied  DC  voltage  to  pins  2  and  3.  The 

positive  must  be  connected  to  pin  2  and  the  negative 
must be connected to pin 3.

 