SX1200i

 

 

 
 

Installation Instructions:

 

 
 

Caution:

 

 

The  SurgeX

®  

1200  series  products  permit  a  maximum

 

16A (SX1216  models), 15A (SX1215  models), 13A (SX1213 
models)  or  10A  (SX1210  models)  total  output  load  with 
a  maximum  10A  load  per  outlet.  Please  check  and  make 
sure that each load connected to the unit does not exceed

 

10A.  Also  make  sure  that  the  total  does  not  exceed  your 
mains receptacles current limit.

 

 

For  safety  please  plug  your  SurgeX

®  

unit  into  a  fused 

receptacle (T20AL 250v fuse recommended).

 

 

SurgeX

®  

Series  Mode

®  

Protection  is  Live-Neutral  only,  if 

the polarity indicator is illuminated when connected to the 
mains please replace the plug observing correct polarity.

 

 

Mounting

 

 

The  SurgeX

®  

SX1200  series  are  designed  to  be  installed  in 

a  19  inch  equipment  rack  and  require  one  unit  (1-U)  of  rack 
space. Remove the product from its packaging and slide it into 
place in the rack being careful to feed the power cord into the 
rack first and guide it so that it does not get caught or jammed 
as the product is installed.

 

 

240 Volt Connections

 

 

Connect  power  to  the  unit  by  plugging  the  cord  into  a  240V 
mains  receptacle.  The  SX1200  series  must  be  plugged  into 
the  appropriate properly polarized receptacle.

 

 

 Model       Standard   Total Load     Receptacle                         

 

table.  Plug  the  equipment  cords  into  the  always-on  and 
switched receptacles as needed to power the equipment.

 

 

The always-on and courtesy receptacles (where fitted) provide 

power as long as power is supplied to the SurgeX

®

. The eight 

switched  rear  receptacles  provide  power  only  when  the  front 
panel  switch  is  on and,  in  the  case  of  RTi products,  when  the 
remote control input is also activated.

 

 

Indicator Lights

 

 

The  SX1200  series  have  two,  three  or  four  indicator  lights  on 
the front panel and a polarity indicator lamp on the rear panel:

 

 

Amber  polarity  light  (Rear  panel,  all  products)

:  Indicates 

that live and neutral are reversed and your SurgeX product will 
not  work  as  intended.  If  you  are  using  an  SX1216  (European 
Cee7/7 connectivity) simply reverse the connection. If you are 
using an SX1210, SX1213 or SX1215 consult an electrician to 
correct and establish a proper polarity.

 

 

Red  Power  Light  (All  products)

:  indicates  that  power  is 

supplied to the unit and the power switch is turned on.

 

 

Green  Self-Test Light (All products)

: indicates  that power  is 

supplied  to  the  unit  and  the  internal  surge  protection  circuitry 
is fully functional.

 

 

Orange  Over/Under  Voltage  Protection  Light  (RTi  &  RLi 
products)

: indicates that the mains voltage is below 190 volts 

or above 280 volts.

 

 

Yellow  Remote  Light  (RTi  products)

:  indicates  that  the 

remote control is active and the rear switched receptacles are

 

SX1210

 

SX1213

 

SX1215

 

 

SX1216

 

AS3112

 

BS1363

 

BS546

 

 

Cee7/7

 

10A

 

13A

 

15A

 

 

16A

 

Australian style receptacle 
British style receptacle 
South African / Indian style 
receptacle

 

European style receptacle

 

on. (The power switch must also be on).

 

 

Lamp Connectors  (RLi Only)

 

 

The  RLi  version  has  provision  for  two  Task  Lamps.  Plug 

the  Lamps  into  the  two  three-pin  XLR  connectors  on  the

 

The  SX1200  series  have  a  total  of  10  rear  receptacles:  eight 
switched  and  two  always  on. The  SX1200  series  also  feature 
a  front  panel  courtesy  receptacle,  which  is  always  on.  Each 
receptacle  is  rated  for  a  maximum  load  of  10  amps,  but  the 
total  load  must  not  exceed  the  load  specified  in  the  above

 

front  panel  and  use  the  dimmer  to  set  a  suitable  brightness. 
Standard  or  HI  brightness  Lamps  can  be  used.  Each 
connector  can  supply  up  to  5  Watts  maximum.  LED  type 
Lamps  can  be  used  with  the  RLi  but  the  dimmer  must  be  set 
fully clockwise.

 