![Ametek Surgex SA-20-AR User Manual Download Page 17](http://html1.mh-extra.com/html/ametek/surgex-sa-20-ar/surgex-sa-20-ar_user-manual_2931340017.webp)
SA-20-AR User Manual
___________________________________________________________________________________________________________
© 2019 AMETEK Electronic Systems Protection | Technical Support 1-800-645-9721 | surgex.com
16
VI. COMMAND LINE INTERFACE (CLI) PROTOCOL
The Command Line Interface provides complete setup of all functions of the AR. The CLI may be accessed through the Telnet
protocol, and requires a Telnet client program. Some commands of the CLI require administrative rights; these are indicated in the
following tables.
Notes:
•
Telnet negotiations require sending these bytes when first connecting: (0x) FF FD 01 FF FD 03 FF FB 1F FF FB 18 FF FB 20
•
Every command must be followed by a Carriage Return and Line Feed: (0x) 0D 0A
Prompt
Description
User>
Prompts the user to enter the user name (either user or admin).
Password>
Prompts the user to enter the password.
Axess Ready>
Prompt displayed while logged in.
Axess Ready Reboot Required>
Prompt displayed after changes have been made that require a reboot. This prompt will
remain active until the AR has been rebooted.
Command
Description
Admin
Fact Def
get outlet
Returns the current status of the outlet.
No
set outlet < on | off | cycle >
Sets the outlet to the selected state.
No
Command
Description
Admin
Fact Def
get location
Returns the location ID.
Yes
Axess Ready
set location < 20-character max >
Sets the location ID.
Yes
get cycle
Returns the cycle time currently in use in seconds.
Yes
10
set cycle < 1-999 >
Sets the cycle time in seconds.
Yes
get upgrade enable
Returns the upgrade enable status.
No
Disabled
set upgrade enable < yes | no >
Enables or disables the ability to upload new firmware.
Yes
logout
Terminates the telnet session.
No
reboot
Reboots the AR.
Yes