Installation and Maintenance Manual
Chapter 3: Programming
Programming Reset-to-Preset Value
The Reset-to-Preset Value is programmed by entering the following:
A)
Unit must be in the Program mode.
B)
The Reset-to-Preset must first be enabled before you can store any values. To accomplish this,
depress . A zero (0) disables a
ENT
CIR# - 1 - 6
6
-
-
(0 or 1)
-
ENT
-
function and a one (1) enables it.
C)
Once the Reset-to-Preset has been enabled, you can store a value in memory. This is accom-
plished by depressing
ENT
CIR# - 1 - 6
0
-
-
(Desired Reset Value)
-
ENT
-
NOTE:
Valid numbers for CIR# 160 are zero (0) through the programmed scale factor, less one (1).
.
3.15: Motion Detector
A programmable Motion Detect output will energize a relay when the transducer speed exceeds the
customers preprogrammed value.
The motion detector is set by entering the following:
A)
Unit must be in the Program mode.
B)
The motion detect must first be enabled before you can store any values. To accomplish this,
depress . A one (1) will enable the motion
ENT
CIR# - 5 - 5 -
(0 or 1)
-
ENT
-
detect output circuit, and LS6 will now be your motion detect output relay. If a zero (0) is
entered, the motion detect feature is disabled and LS6 will function as a normal limit switch.
C)
To set the value at which the motion detect relay energizes, depress
D)
To set Speed Displayed Resolution, depress
Sets Speed measurement intervals to .050 second increments.
Display reads speed resolution in Scale Factor increments.
ENT
CIR# - 1 - 7
6
-
-
Scale Factor Increments/Sec.
-
ENT
-
NOTE:
A CIR #176 can only be entered if the motion detect option is enabled.
.
0
CIR# - 1 - 9 -
CIR ON
-
ENT
-
ENT
-
(Speed/Sec)
-
0
CIR# - 1 - 9 -
CIR OFF
-
ENT
-