IMPORTANT:  Read before wiring this Explosion-proof Blower 

This AMETEK Rotron Explosion-proof Regenerative Blower may be equipped with Pilot Duty 
Thermal Overload (PDTO) or Automatic Thermal Overload (ATO) protection.  When properly 
wired to a motor starter, this protection limits the motor winding temperature rise per the 
National Electric Code (NEC) article 500.  Failure to properly wire this blower is an NEC 
violation and could cause an explosion.  AMETEK Rotron assumes no responsibilities for 
damages incurred by negligent use of this product, and will not warranty a blower on which the 
PDTO is not properly connected.  Some blowers 1 HP and under do not require PDTO and 
have built in ATO.  Consult the factory if verification of wiring connections is required. 

In all cases, follow the motor controller manufacturer’s instructions.  The following schematic is 
for conceptual understanding only, and may not apply to all motor/controller combinations. 

The manufacturer’s wiring diagram found on the motor takes precedent over reference 
diagrams supplied by AMETEK Rotron Technical Motor Division. 

The schematic is shown for a 
three phase motor.  For a 
single phase motor disregard 
L3 and M3.  Pushing the 
START button completes the 
auxiliary control circuit, 
allowing current to flow 
through the magnetic coil.  
The contacts are 
magnetically closed, starting 
the motor and latching the 
auxiliary circuit.  The motor 
will continue to run until the 
STOP push button is 
depressed, the motor 
reaches the overload 
temperature, or the current 
sensing overloads trip out. 

If you have any questions, contact AMETEK Rotron at 914-246-3401 for the location of your 
area representative. 

EXPLOSION-PROOF BLOWERS

A1

A2

L1

L2

L3

Push Start 

Push Stop 

Magnetic Coil

Current 

Overloads

Contacts

Auxiliary 
Power 

J

M1

M2

M3

J

J – Pilot Duty Thermal Overload Protection wires 
L – Power leads from circuit breaker box 
M – Motor leads (refer to wiring diagram inside T’box or on motor nameplate) 

Motor

Schematic

Summary of Contents for EN101

Page 1: ...ment SERVICE AND PARTS MANUAL FOR BLOWER MODEL EN101 EN404 AMETEK Dynamic Fluid Solutions 100 East Erie St Kent Ohio 44240 Telephone 330 673 3452 Fax 330 677 3306 email dfs information ametek com inte...

Page 2: ...l not be covered AMETEK Rotron will then notify you of your options Any failed unit that is tampered with by attempting repair or diagnosis will void the warranty unless authorized by the factory Term...

Page 3: ...at the blower outlet or inlet Also if problems do arise the Rotron Field representative will need to know the operating pressure suction to properly diagnose the problem 6 Excess Air Bleed excess air...

Page 4: ...and add filter 3 Change bearings Performance Below Standard 1 Leak in piping 2 Piping and air passages clogged 3 Impeller rotation reversed 4 Leak in blower 5 Low voltage 1 Tighten 2 Clean 3 Check wir...

Page 5: ...er pads over the screens 3 Reassemble by reversing the procedure NOTE On DR068 models with tubular mufflers it is necessary to remove the cover and impeller accessing the muffler material from the hou...

Page 6: ...the flange face to the motor shaft shoulder B Impeller Thickness C Measurements A and B are made by laying the parallel bar across the housing flange face and measuring to the proper points Each meas...

Page 7: ...roller manufacturer s instructions The following schematic is for conceptual understanding only and may not apply to all motor controller combinations The manufacturer s wiring diagram found on the mo...

Page 8: ...n has a complete line of regenerative blowers with explosion proof motors Division 1 2 Class I Group D Class II Groups F G requirements are met with these standard explosion proof blowers AMETEK Rotro...

Page 9: ...ERSE ROTATION K 3 9 WIRE 230 VAC 460 VAC LINE 1 LINE 1 LINE 7 2 LINE 3 2 LINE 8 4 7 3 LINE 9 5 8 4 5 6 6 9 INTERCHANGE ANY TWO LEAD LINES TO REVERSE ROTATION M 1 230 VAC SINGLE VOLTAGE 1 LINE 5 4 LINE...

Page 10: ...W VOLTAGE 1 3 2 8 J J 4 5 LINE A LINE B THERMAL PROTECTION LEADS MUST BE USED THERMAL PROTECTION LEADS MUST BE USED LINE A LINE B J J 2 4 5 8 3 1 COLORS 1 BLUE 2 WHITE 3 ORANGE 4 YELLOW 5 BLACK 8 RED...

Page 11: ...ASSEMBLY DIAGRAM EN101 EN404...

Page 12: ...516990 B14 6 155514 120232 155514 5 pcs 155129 155129 B16 1 510355 510355 510355 510355 510355 B17 Not Used Not Used Not Used Not Used Not Used B18 1 Not Used Not Used Not Used Not Used 510444 1 Not...

Page 13: ...M2 EN101AG91L 038019 510449 510449 EN101AG58L 038171 Motor Specific Parts Wiring Diagram EN202AA58L 038022 510449 510449 EN202AA91L 038021 EN303AG58L 038172 510449 510449 EN303AG91L 038026 EN353BT72L...

Reviews: