background image

linoleum, you must place protection between the 
stove and the combustible material.
 
There are many floor and wall board manufacturers, 
and you should be very cautious in choosing the 
proper protection. The type board you choose should 
be U.L. rated and listed.  After examining the area you 
plan to place your stove and determining it requires 
a board, the next step is to select the proper size. The 
stove you choose will determine the size board that 
is required. The approved protector board should be 
large enough to provide a minimum of eight inches 
(8”) behind the unit, eight inches (8”) on either side 
and sixteen inches (16”) in the front where the door is 
located. Floor protection should also exist under the 
chimney connector, and should extend two inches 
(50 mm) beyond each side of the chimney connector. 

The type of board you choose must have an R-value 
of 0.84 or equivalent.

Installation on a Concrete Floor 

An appliance mounted on a concrete floor does not 
require floor protection. 
Carpeting and any other combustible material must 
not cover the Floor Protector. 
If a combustible surface is applied to the concrete 
floor, a clearance must be maintained equivalent to 
the area reserved for the floor protector. 

INSTALLATION APPLICATIONS

Illustration 1-b

Chimney Connector Systems and Clearances 

from Combustible Walls for Residential Heating 

Appliances

Minimum 3.5-in thick brick mansory all framed into 
combustible wall with a minimum of 12-in brick 
separation from clay liner to combustibles. The 
fireclay liner shall run from outer surface of brick wall 
to, but not beyond, the inner surface of chimney flue 
liner and shall be firmly cemented in place.

A

B

C

D

Solid-insulated, listed factory-built chimney length of 
the same inside diameter as the chimney connector 
and having 1-in or more of insulation with a minimum 
9-in. air space between the outer wall of the chimney 
length and combustibles.

Sheet steel chimney connector, minimum 24 gauge 
in thickness, with a ventilated thimble, minimum 24 
gauge in thickness, having two 1-in. air channels, 
separated from combustibles by a minimum of 6-in. 
of glass fiber insulation.
Opening shall be covered, and thimble supported 
with a sheet steel support, minimum 24 gauge in 
thickness.

Solid insulated, listed factory-built chimney length 
with an inside diameter 2-in. larger than the chimney 
connector and having 1-in. or more of insulation, 
serving as a pass-through for a single wall sheet steel 
chimney connector of minimum 24 gauge thickness, 
with a minimum 2-in. air space between the outer 
wall of chimney section and combustibles. Minimum 
length of chimney section shall be 12-in. chimney 
section spaced 1-in. away from connector using sheet 
steel support plates on both ends of chimney section. 
Opening shall be covered, and chimney section 
supported on both sides with sheet steel supports 
securely fastened to wall surfaces of minimum 24 
gauge thickness. Fasteners used to secure chimney 
section shall not penetrate chimney flue liner.

Pre-Manufactured Flue System: 

In the past few years pre-manufactured flue systems 
have become very popular, because this type system 
is easily installed and, when done correctly, is very 
safe. There are many pre-manufactured flue systems 
on the market, and when making your choice it should 
be U.L., B.O.C.A. or I.C.B.O. approved. Any of these 
systems are constructed of the proper materials and 
meet the proper safety standards. Your local dealer 
normally handles an approved brand of flue pipe. 
There are two very popular methods for installation 
of this type system. 

The 

first,

 most popular and least expensive is through 

the ceiling and out the roof. This is the most direct 
route and creates a good draw because it requires 
less pipe. It is less expensive because insulated pipe 
is needed only from the ceiling to the roof and above 
-- single wall chimney connect, 24 gauge or thicker 
is used from the unit to the ceiling; maintain 10.5” 
clearance between single wall chimney connector 
and any combustibles. 

The 

second

 method for installing a pre-manufactured 

system is to exit through the wall and run the system 
vertically up the outside of the structure. This method 
is more expensive because more insulated pipe is 
required -- you must use insulated pipe through the 
wall and up the outside of the structure. In either 
installation, proper clearances to combustibles should 
be maintained. Your flue pipe manufacturer furnishes 
a wall thimble or ceiling support box and, when 
installed properly, the correct clearances are achieved. 
If you are unable to install this type system your 
local dealer may be able to recommend a qualified 
contractor for this installation. It is the customer’s 
responsibility to ensure that his system is installed 
properly and is in good operating condition.  

FLOOR AND WALL 

PROTECTION 

1. Floor Protection 

You will not need any floor protection if your floor is 
constructed of a non-combustible material such as 
brick or concrete.  If your floor is constructed with a 
combustible material such as hardwood, carpet or 

Illustration 2

6

7

Summary of Contents for N 380

Page 1: ...h July 1990 Particulate emission standards Tested to UL 1482 2000 ULC S627 2000 OWNER S MANUAL MODEL NUMBER AMESTI N 380 Thank you for purchasing this product from a fine line of heating equipment fro...

Page 2: ...ite at www amesti cl for helpful information frequently asked questions parts accessory orders and more Technical Support 800 444 6742 OPERATION WHY THE CORRECT FLUE SIZE IS IMPORTANT 6 Draft is the f...

Page 3: ...amage caused by the malfunction of a stove due to improper installation Do not use makeshift methods or material which may compromise the installation The manufacturer will not be responsible for an a...

Page 4: ...for a single wall sheet steel chimney connector of minimum 24 gauge thickness with a minimum 2 in air space between the outer wall of chimney section and combustibles Minimum length of chimney sectio...

Page 5: ...u will need wall protection at least twelve inches 12 above the wall thimble i R value is given no conversion is needed ii k factor is given with a required thickness T in inches R 1 k xT iii C factor...

Page 6: ...tallation rigid 10 Maintain the required diameter flue for the entire installation 11 If you are connecting the stove to an old masonry flue besuretohaveitinspectedforcracksandgeneral condition Relini...

Page 7: ...inlet control until the fire is well established approximately 20 minutes being careful not to over fire 8 Readjust the air inlet control to the desired burn rate If excessive smoke fills the firebox...

Page 8: ...ufacturer includes a steel handle with each fireplace This handle must be used to open and close the door and to move the air control lever The handle must be stored away from the fireplace to prevent...

Page 9: ...60 of the fuel value of dry seasoned wood will deposit creosote on the inside of the stove and along to inside of the chimney 4 What does dry seasoned wood mean and what is considered to be hardwood...

Page 10: ...he parts in this fireplace referring to the materials and manufacturing will be free of defects at the time of purchase The manufacturer extends the following warranties Five Year Period Steel and wel...

Page 11: ...____ Dealer store Other ____________________________________________________ Where did you receive information about our product Please check one ___ Rec d info via phone ___ Dealer Name of dealer ___...

Page 12: ...sitez notre site web www amesti cl pour des informationsutiles questionsfr quentes commande de pi ces accessoires et plus Assistance Technique 800 444 6742 FONCTIONNEMENT POURQUOIUNETAILLECORRECTE DET...

Page 13: ...asresponsabledesaccidents dus au raccordement de l unit un syst me de chemin e d fectueux APPLICATIONS D INSTALLATION Illustration 1 Si vous rencontrez de tels probl mes consultez un expert local en c...

Page 14: ...vantde passage pour le connecteur mural de la chemin e en t le d acier de calibre 24 minimum d paisseur avec un espace d air de deux pouces 2 minimum entre la paroi ext rieure de la section de la chem...

Page 15: ...d au moins douze pouces 12 au dessus de la cartouche murale i la valeur R est donn e pas de conversion requise ii le facteur k est donn avec une paisseur T requise en pouces R 1 k xT iii le facteur C...

Page 16: ...un rev tement en acier inoxydable peut tre requis 12 Il est recommand que pas plus de deux coudes de 90 soient utilis s dans l installation du conduit Plus de deux coudes de 90 pourraient diminuer la...

Page 17: ...ce que le feu soit bien tabli environ 20 minutes faites attention la surchauffe 8 R ajustez l arriv e d air jusqu la vitesse de combustion d sir e Si un exc s de fum e remplit le foyer ouvrez l g reme...

Page 18: ...laporteetlaissezlecimentprendrependant trois quatre heures avant de rallumer un feu Assemblage de la Porte AMESTI N 380 POIGNEE FROIDE ET CONTROLE D ARRIVEE D AIR Le fabricant inclut une poign e d aci...

Page 19: ...ser comme bois de chauffage Du bois sec et dur doit tre utilis Evitez les bois verts ou non s ch s Le bois vert en plus de ne bruler qu 60 de la valeur nerg tique des bois secs d posera de la cr osote...

Page 20: ...A DATE D ACHAT AU PROPRIETAIRE ORIGINAL AMESTI garantit que toutes les pi ces de ce po le se r f rant des mat riaux et de fabrication seront exemptes de d fauts au moment de l achat Le fabricant tend...

Page 21: ...reporter l autocollant sur l int rieur des pieds du foyer pour compl ter cette partie Num ro de mod le_________________________ Date d achat _____________________________ Prix d achat ________________...

Page 22: ......

Reviews: