Installing the Indoor Unit
12
115V Mini-Split
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the
manual could result in exposure to electrical, mechanical or other potential safety
hazards. Always refer to the safety warnings provided throughout this manual
concerning these procedures. When possible, disconnect all electrical power including
remote disconnect and discharge all energy storing devices such as capacitors before
servicing. Follow proper lockout/tag out procedures to ensure the power can not be
inadvertently energized. When necessary to work with live electrical components, have
a qualified licensed electrician or other individual who has been trained in handling live
electrical components perform these tasks. Failure to follow all of the recommended
safety warnings provided, could result in death or serious injury.
Mounting Location
1. Confirm the mounting location with the customer. Keep in mind the guidelines for a
safe installation location on page 11.
2. Place the wall-mounting frame on the wall and check that it is level. Mark the screw
holes to be drilled, ensuring they are in a place with adequate support.
3. Drill the holes on the wall according to the selected marks. If they are not drilled into
a solid backing, insert expanding plastic wall anchors to give added support.
4. Attach the wall-mounting frame with the supplied tapping screws and check to make
sure it is firmly attached. If any of the screws or anchors are loose, select another
point on the frame to re-drill and attach securely.
5. Be sure that the wall-mounting frame has been secured firmly enough to withstand
4 times the weight of the unit. The weight should be evenly shared at each fastening
point.
Left
Wall
Φ2 3/16 inch
Right
Mark in the middle of it
Level meter
Rear piping hole
Wall
Space
to the
wall
min.
6 inches
Space
to the
wall
min.
6 inches
Φ2 3/16 inch
Rear piping hole