Housekeeping

Visually inspect the pilot.
To ensure sufficient ventilation and 

combustion air supply, proper clearances 

must be maintained. 

When installed in a closet, DO NOT block 

or obstruct any of the combustion air inlet 

openings located around the perimeter of the 

water heater.   A minimum of 1” is required 

between these combustion air inlet openings 

and any obstruction.

DO NOT obstruct or block the Flammable 

Vapor Sensor.  The sensor does not 

require any maintenance or cleaning.  DO 

NOT expose to cleaning agents.

!

DANGER: Combustible 

materials, such as clothing, 

cleaning materials, or 

flammable liquids, etc., must 

not be placed against or next 

to the water heater.

Burner Inspection

Visually inspect the pilot flame and main 

burner annually.
Through the sight glass, inspect the pilot 

and burner lighting.  If any unusual pilot 

or burner operation is noted, the water 

heater should be shut off until qualified 

service assistance can be obtained.
The burner operates in radiant mode 

and glows bright orange when burning 

correctly.  Allow approximately 30 

seconds after turning on for the burner to 

reach the radiant mode

!

CAUTION: For your safety, cleaning of 

the burner must be performed only by 

qualified service personnel, as it involves the 

disconnection of gas piping and leak testing. 

The burner chamber is a sealed area.  If the 

burner access door is removed, the burner 

access door gasket must be replaced.

For cleaning, remove the burner from the 

water heater. A vacuum cleaner can be 

used on the burner and floor shield inside 

the water heater.  The burner can also be 

cleaned by scrubbing with mild detergent.

Proper burner flame pattern

Venting System Inspection

The water heater’s internal flue must be 

inspected annually to be certain it is clean 

by removing the blower assembly and flue 

baffle.
When reinstalling the flue baffle make 

certain it is hung securely by its hanger at 

the top of the flue way.
Reinstall the blower assembly.
Inspect plastic vent pipe.  Make certain 

that all joints are secure and that vent 

pipe supports are all in place.  Check 

the outdoor vent terminal to see that it is 

free of obstructions, and that there is no 

damage nearby caused by condensate.

Inspect dilution air holes.  Make certain no 

blockage exists.  Clean any lint, dirt or oil 

accumulation that may exist.
Test for spillage at the dilution air holes 

after 5 minutes of burner operation.  Place 

a blown out match or candle close to the 

dilution are holes.  The smoke from the 

candle or match should be drawn into the 

dilution air holes.  If the smoke is pushed 

away from the dilution air holes, the 

blower or vent system may be blocked.  

Contact qualified service personnel.

Location of Dilution Air Holes

Gas flame

 should be visible 

on entire burner 

surface.

Summary of Contents for PowerVent

Page 1: ...r This manual also includes a parts list It is very important that all persons who are expected to install operate or adjust this water heater read the instructions carefully so they may understand ho...

Page 2: ...re on your part can save you time and money over the life of your water heater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips...

Page 3: ...nts paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water h...

Page 4: ...for Hot Water SCALDS The illustration below details the approximate water temperature for each mark on the Gas Control Thermostat Temperature Dial D A N G E R HOT Water temperature over 125 can cause...

Page 5: ...LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look...

Page 6: ...installation For residential water heaters of a capacity greater than 52 gallons consult the local building jurisdiction for acceptable bracing procedures Have the installer show you the location of t...

Page 7: ...r heater to ignite until examined by a Qualified Service Technician DO NOT obstruct or block the flammable vapor sensor Rheem Water Heating FVIR certified gas water heaters can be installed on a resid...

Page 8: ...than one square inch per 4000 Btuh of the total input rating of all the appliances in the enclosure If horizontal ducts are used to communicate with the outdoors each opening must have a minimum net...

Page 9: ...dition and eliminating the repeated operation of the relief valve Other methods of controlling thermal expansion are also available Contact your installing contractor water supplier or plumbing inspec...

Page 10: ...cealed and should be protected from freezing No valve of any type restriction or reducer coupling should be installed in the discharge line To Fill the Water Heater Make certain that the drain valve i...

Page 11: ...pe gas shut offs are used they shall be T Handle type Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP gas Use compound sparingly on male thread...

Page 12: ...detailed in this manual have been met Carefully inspect the entire venting system for any signs of cracks or fractures particularly at the joints between elbows or other fittings and the straight len...

Page 13: ...rtical pipe one 1 90 elbow and two 2 feet of horizontal pipe Number of 90 elbows with Vent Number of 45 Elbows Maximum Vent Pipe Length in Feet ft 0 Maximum Altitude See chart on upper left One 1 None...

Page 14: ...reeze on the exterior wall under the eaves and on surrounding objects Some discoloration to the exterior of the building is to be expected However improper location or installation can result in sever...

Page 15: ...nal fitting and connect it as shown to the vent pipe on the exterior of the building Complete the rest of the vent pipe installation to the water heater s vent connector fitting on the blower outlet I...

Page 16: ...the joint with a rag Allow 15 minutes before handling Cure time will vary according to fit temperature and humidity NOTICE Stir the solvent cement frequently while using Use a natural bristle brush or...

Page 17: ...local codes or in the absence of local codes in accordance with latest edition of the National Electric Code ANSI NFPA No 70 Refer to the figures below for water heater internal wiring NOTE It is not...

Page 18: ...om the use of such unauthorized devices CAUTION If local codes require the application of an external insulation blanket to this water heater pay careful attention to the following so as not to restri...

Page 19: ...tion Air holes see diagram to the left DON T remove the Burner Access Door unless absolutely necessary This should only be done by a qualified service technician A new burner access door gasket must b...

Page 20: ...and free of leaks Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for possible gas l...

Page 21: ...Heating Installation Spring loaded check valve in heating unit hot water supply line and cold water return line not supplied with water heater NOTE This check valve is incorporated in some heating un...

Page 22: ...e Set the valve thermostat dial to LOW This appliance has an automatic spark ignition system DO NOT attempt to light the pilot by hand Wait five 5 minutes to clear out any gas If you smell gas stop Fo...

Page 23: ...ermostat setting to prevent contact with HOT water Water Temperature Setting The temperature of the water in the water heater can be regulated by turning the knob on the front of the gas control therm...

Page 24: ...ise young children or others who are incapacitated The gas control thermostat is constructed with a built in safety shut off device designed to shut off the gas supply to the burner if the main burner...

Page 25: ...er flames 8 The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to clear combustion gases from the water heater...

Page 26: ...and pressure relief valve on the water heater discharges periodically this may be due to thermal expansion in a closed water system Contact the water supplier or your plumbing contractor on how to cor...

Page 27: ...d leak testing The burner chamber is a sealed area If the burner access door is removed the burner access door gasket must be replaced For cleaning remove the burner from the water heater A vacuum cle...

Page 28: ...Gas Caution in the Operating Instructions Anode Rod This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank The anode rod is slowly consumed thereby elimin...

Page 29: ...Use a water heater size that meets the requirements heater will cause of your needs condensation Yellow flame Scale on top of the burner Contact a qualified service technician to remove scale or soot...

Page 30: ...ion Shutoff System Contact a qualified service technician tripped Water is too hot The gas control thermostat See the Water Temperature Setting of The Water is set too high Heater section of this manu...

Page 31: ...open 1 Replace gas valve control Six One Flash three second pause Failed trial for ignition Insufficient gas supply unstable pilot carbon buildup on electrode or wire pilot tube damage 1 Check gas sup...

Page 32: ...the rating plate Specify type of gas natural or LP as marked on the rating plate Part description as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of gas piping...

Page 33: ...arts The kit provides extra speed clips and tamper resistant screws Burner Access Door Assembly Burner Access Door Gasket Burner Pilot Bracket Screws Pilot Bracket Pilot Screw Burner Hex Nuts Pilot Tu...

Page 34: ...34 Notes...

Page 35: ...35 Notes...

Page 36: ...rbon monoxide detec tor with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completi...

Reviews: