background image

62

DISCHARGE PIPE

TEMPERATURE-PRESSURE

RELIEF VALVE

Figure 59

If  the  Temperature-Pressure  Relief  Valve  on  the  water  heater 

weeps  or  discharges  periodically,  this  may  be  due  to  thermal 

expansion.

note:

  Excessive  water  pressure  is  the  most  common  cause 

of Temperature-Pressure Relief Valve leakage. Excessive water 

system pressure is most often caused by "thermal expansion" in 

a "closed system." See Thermal Expansion and Closed Water 

Systems on page 14. The Temperature-Pressure Relief Valve 

is not intended for the constant relief of thermal expansion.
Temperature-Pressure Relief Valve leakage due to pressure build 

up in a closed system that does not have a thermal expansion 

tank installed is not covered under the limited warranty. Thermal 

expansion tanks must be installed on all closed water systems.

do not plug the temperature-pressure relief 

ValVe opening. this can cause property damage,  

serious injury or death.

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

Vent system

Examine the vent system once a year. Points of inspection are 

as follows:
1.  Check for obstructions and/or deterioration of the intake air 

and/or vent piping and the intake air and vent terminations. 

Replace immediately where needed.

2.  The  debris  screens  in  the  intake  air  and  vent  terminations 

should  be  should  be  cleaned  of  foreign  material  and  soot. 

See Figure 22 on page 26.

note:

 Do not reach inside the vent hood when the heater 

is in operation.

3.  Check all vent system connections for leakage and repair or 

reseal as necessary.

table 15

un-lime® professional delimer

part number

description

9005416105

4 - 1 gallon (case)

9005417105

1 - 5 gallon

powered anode rods

To  insure  a  long,  trouble-free  operating  life,  the  water  heaters 

covered  in  this  manual  are  factory  equipped  with  a  powered 

anode system. The anode rods (2) are of a permanent design 

and  do  not  need  replacing  unless  damaged.  Inspection  and 

cleaning should be performed once a year.

note:

 Follow the instructions to drain the water heater storage 

tank on page 60 first. Remove the powered anodes from the water 

heater  by  loosening  the  3/4"  NPT  bushing  that  forms  the  top 

of  the  anodes.  Do  not  disassemble  the  retaining  nut  and  wire 

terminal  from  the  top  while  installed  in  the  water  heater,  the 

anode's  electrode  may  fall  inside  the  tank.  Remove  the  entire  

anode rod from the water heater prior to inspection. Clean the 

anode rods with a soft cloth and reinstall. Follow the instructions 

for filling the water heater on page 50 when finished.

drain ValVe and access panels

The water heaters covered in this manual are equipped with a 

drain valve, see Features And Components on page 7 for location. 

The water heaters covered in this manual are also equipped with 

a  cleanout  opening  for  sediment  and  lime  scale  removal.  See 

Figure 58 on page 61.

temperature-pressure relief ValVe test

Burn hazard.

Hot water discharge.

Keep clear of Temperature-

Pressure Relief Valve

discharge outlet.

It is recommended that the Temperature-Pressure Relief Valve 

should  be  checked  to  ensure  that  it  is  in  operating  condition 

every 6 months.
When checking the Temperature-Pressure Relief Valve operation, 

make sure that (1) no one is in front of or around the outlet of the 

Temperature-Pressure Relief Valve discharge line, and (2) that 

the water discharge will not cause any property damage, as the 

water may be extremely hot. Use care when operating valve as 

the valve may be hot.
To  check  the  relief  valve,  lift  the  lever  at  the  end  of  the  valve 

several times, see Figure 59. The valve should seat properly and 

operate freely.
If after manually operating the valve, it fails to completely reset 

and  continues  to  release  water,  immediately  close  the  cold 

water inlet to the water heater and drain the water heater, see 

Draining And  Flushing  on  page  60.  Replace  the Temperature-

Pressure Relief Valve with a properly rated/sized new one, see 

Temperature-Pressure Relief Valve on page 15 for instructions on 

replacement.

Summary of Contents for (A)HCG3 130T 300

Page 1: ...N SERVICE MAINTENANCE LIMITED WARRANTY PO Box 1597 500 Princeton Road Johnson City TN 37605 WARNING If the information in these instructions is not followed exactly a fire or explosion may result caus...

Page 2: ...6 Water Piping Diagrams 67 Limited Warranty 74 Table Of Contents Safe Installation Use and Service 3 General Safety Information 4 Precautions 4 Introduction 6 Qualifications 6 Preparing For The Instal...

Page 3: ...use cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause...

Page 4: ...as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the time it is open General Safety Information Read and understand this instru...

Page 5: ...ment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or ser...

Page 6: ...indicated in the piping Introduction diagrams as these are necessary for checking the operation of the water heater The principal components of the water heater are identified in Features And Componen...

Page 7: ...ITER COMBUSTION BLOWER FLAME SENSOR MAIN BURNER radial design BLOWER FLANGE INTAKE AIR combustion air CONNECTION 4 INCH PVC Figure 2 Hot Surface Igniter The control system energizes the Hot Surface Ig...

Page 8: ...14 15 17 1 18 16 10 8 FRONT Top View Components 1 Water Heater s 120 VAC on off switch 2 Powered anode rods The water heater s covered in this manual are equipped with two powered non sacrificial ano...

Page 9: ...e 16 and Condensate Drain Installation on page 36 Side Views 1 Cleanout access panel covers water heater cleanout opening 2 CCB enclosure see Figure 3 on page 8 for description 3 120 VAC junction box...

Page 10: ...F 30 F 40 F 50 F 60 F 70 F 80 F 90 F 100 F 110 F 120 F 130 F 140 F Btu hr kW C 11 C 17 C 22 C 28 C 33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C A HCG 130T 300 Natural 300 000 88 GPH 1746 1164 873 699...

Page 11: ...page 21 Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition sources if you smell gas Do not store or use gasoline or other flammable v...

Page 12: ...e Circulation Pump Wiring Diagrams on page 66 for electrical hookup information Install in accordance with the current edition of the National Electrical Code NFPA 70 or the Canadian Electrical Code C...

Page 13: ...um supply gas pressure readings are taken while gas is not flowing static pressure AND while gas is flowing dynamic pressure Supply pressure must never fall below the minimum values Supply gas pressur...

Page 14: ...e burns instantly resulting in severe injury or death Children the elderly and the physically or mentally disabled are at highest risk for scald injury Feel water before bathing or showering Temperatu...

Page 15: ...emperature pressure relief valve must be installed in opening provided Can result in overheating and excessive tank pressure Can cause serious injury or death This water heater is provided with a prop...

Page 16: ...in Installation on page 36 Combustible Material Storage Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition sources if you smell gas D...

Page 17: ...rea through a design of louver or grille or screen is known it shall be used in calculating the size of opening required to provide the free area specified Where the louver and grille design and free...

Page 18: ...egate input rating of all appliances installed in the enclosure When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum di...

Page 19: ...section of the manual are a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Venting Installati...

Page 20: ...inal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructio...

Page 21: ...ce or if the pipe cannot move freely through a wall penetration the pipe may be stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such...

Page 22: ...n the back cover of this manual to order 4 Concentric Termination Part 9006328005 6 Concentric Termination Part 9006144005 Venting Requirements Approved Materials Approved vent and intake air pipe mat...

Page 23: ...r heater components 10 All vent exhaust pipes must be pitched a minimum of a 1 4 inch per foot back to the water heater to allow drainage of condensate 11 If installing 4 inch vent pipe connect the ve...

Page 24: ...g in a Power Vent configuration vertically through the roof the following instructions must be followed The vent termination must be oriented facing downward as shown in Figure 19 and Figure 20 on pag...

Page 25: ...ns must be a minimum of 12 inches 30 cm 18 inches 45 cm in Canada above the average or expected snow level as shown in Figure 19 and Figure 21 on page 25 6 When the intake air and or vent piping from...

Page 26: ...eter hole for 6 inch pipe where the pipe s will pass through the wall Note Beware of concealed wiring and piping when cutting through the wall 8 Cut a length s of pipe being installed 3 5 inches 8 9 c...

Page 27: ...ll or structure as shown in Figure 24 and Figure 25 Note If this required distance to a parapet vertical wall or structure cannot be maintained standard terminations must be used See Vertical Terminat...

Page 28: ...assembly and secure it to the roof 5 Seal around the plumbing boot or roof flashing 6 Cement the vent cap onto the vent pipe Alternately a field supplied stainless steel screw may be used to secure th...

Page 29: ...IED LENGTH 25 3 8 INCHES 64 cm MAXIMUM ALLOWABLE LENGTH 45 3 8 INCHES 115 cm MINIMUM ALLOWABLE LENGTH 12 INCHES 30 cm VENT CAP STAINLESS STEEL VENT TERMINAL WITH SCREEN INTAKE AIR PIPE INTAKE AIR CONN...

Page 30: ...tions are maintained Ensure multiple terminations are arranged or grouped as required Note These clearances must be maintained to prevent the recirculation of vent exhaust gases to the intake air Clea...

Page 31: ...ALL ROOF Figure 39 Multiple Concentric Termination Arrangements The illustrations on this page show some of the installation arrangements for multiple concentric terminations that are allowed See Mult...

Page 32: ...32 Venting Arrangements Power Vent Vertical Figure 40 Direct Vent Vertical Figure 42 Power Vent Horizontal Figure 41 Direct Vent Horizontal Figure 43...

Page 33: ...g Arrangements Direct Vent Vertical Vent Horizontal Intake Figure 44 Direct Vent Vertical Concentric Figure 46 Direct Vent Horizontal Vent Vertical Intake Figure 45 Direct Vent Horizontal Concentric F...

Page 34: ...to building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 36 i...

Page 35: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30 kW...

Page 36: ...your distributor or Service Agency Field supplied materials required for installation include Approved PVC cement and PVC primer 1 2 inch PVC pipe minimum length to equal the distance between the wate...

Page 37: ...SHUTOFF VALVE TEE FITTING PIPE CAP SEDIMENT TRAP DIRT LEG Figure 52 Ensure all gas pipe is clean on the inside before installation To trap any dirt or foreign material in the gas supply line a sedime...

Page 38: ...ff the Main Gas Shutoff valve to the water heater Gas Line Leak Testing Fire and Explosion Hazard Leak test before placing the water heater in operation Disconnect gas piping and main gas shutoff valv...

Page 39: ...heater caused by freezing temperatures is not covered under the limited warranty Electrical Wiring All electrical work must be installed in accordance with the National Electrical Code ANSI NFPA 70 or...

Page 40: ...ixing Valves on page 14 2 Dishwashing Machines on page 14 3 Temperature Pressure Relief Valve on page 15 4 Closed Systems and Thermal Expansion on page 14 5 For multiple water heater installations see...

Page 41: ...erature Probe two red wires see Figure 3 on page 8 for location The ECO switch contacts will open when the water temperature reaches approximately 202 F 94 C and close at approximately 140 F 49 C If t...

Page 42: ...the control system The ECO energy cut out flame sensor pressure switches and temperature probes are monitored by the control system The Combustion Blower igniter 24 VAC Gas Valve and anode rods are a...

Page 43: ...See Figure 3 on page 8 for Blower Prover Switch location The Hot Surface Igniter is being energized See Figure 2 on page 7 for Hot Surface Igniter location The igniter has been energized and the cont...

Page 44: ...from the combustion chamber at the end of a heating cycle Fault The control system has detected a Fault condition Heating operation is disabled until the Fault condition is corrected Power to the wat...

Page 45: ...ll control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen press the Operational Button under SELECT to enter the Temperatures menu If the...

Page 46: ...obe Offset 0 F CHANGE BACK HELP Temperatures Bottom of Menu Differential 8 F Tank Temperature 120 F Upper Temperature 122 F Lower Temperature 118 F Heater Regulated to Tank Upper Probe Offset 0 F Lowe...

Page 47: ...ulated time the control system water heater has been energized Burner On Time Total accumulated time the control system has been in the heating operating state burner run time Cycle Count Total accumu...

Page 48: ...event will replace the oldest Press the Operational Button under VIEW to view details for each Fault or Alert message stored 1 Blocked Air Intake A7 51 mins ago 2 Blocked Exhaust A8 54 mins ago 3 Low...

Page 49: ...is menu item Show Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons...

Page 50: ...as leaks see Gas Line Leak Testing on page 38 and repair any leaks found Initial Start Up Required Test Equipment Two U tube manometers recommended ranges 0 14 W C 0 3 5 kPa and 0 35 W C 0 8 7 kPa or...

Page 51: ...d allow the manifold gas pressure to stabilize for several minutes before making further adjustments 4 Replace the gas pressure regulator cover screw 5 Cycle the burner on and off several times to che...

Page 52: ...al Adjustment on page 45 2 When the water heater has completed its shut down sequence and enters the standby mode turn the water heater s on off switch to the off position 3 Push in the gas control kn...

Page 53: ...lt in fire or explosion Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control syste...

Page 54: ...devices If the tank temperature drops below the Operating Set Point minus the Differential setting the control will automatically return to Step 2 and repeat the operating cycle Troubleshooting Insta...

Page 55: ...tem Igniter is energized for warm up period 24 Volt Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monitors the flame sensor Control System Locks Out...

Page 56: ...disable circuit disabling heating operation See Enable Disable Circuit on page 39 The heating capacity of the water heater has been exceeded the water heater is unable to meet demand Operational Probl...

Page 57: ...gthening the time required to heat water to desired temperature Hot water piping leaks open faucets water heater drain valve leaking or open Sediment or lime scale accumulation may be affecting water...

Page 58: ...ow the required minimum pressure see Table 4 on page 13 Supply gas is turned off at the Main Shutoff Valve Supply gas pressure is dropping when other gas fired appliances on a common supply gas line a...

Page 59: ...for switch location Excessive equivalent pipe length exceeded the maximum number of 90 elbows or wrong pipe size used in the intake air piping system see Venting Requirements on page 22 Balance plate...

Page 60: ...General Keep appliance area clear and free from combustible materials gasoline and other flammable vapors and liquids See Locating The Water Heater on page 11 Water heater maintenance includes period...

Page 61: ...Ensure the drain hose is secured before and during the entire flushing procedure Flushing is performed with system water pressure applied to the water heater 6 Open the water heater drain valve to flu...

Page 62: ...d with a powered anode system The anode rods 2 are of a permanent design and do not need replacing unless damaged Inspection and cleaning should be performed once a year Note Follow the instructions t...

Page 63: ...numbers 1 4 On the other side of the dipswitch is the word OPEN The dipswitches are rocker type switches if one side of the rocker is down the other side will be up Pressing a rocker down on the side...

Page 64: ...VALVE B CENTRAL CONTROL BOARD C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER INSIDE CCB ENCLOSURE 50VA GROUND STRIP BURNER GROUND BURNER BOLT ON OFF SWITCH GROUND 120 VAC NEUTRAL...

Page 65: ...R PROVER 24 VAC GAS VALVE B C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER 50VA GROUND STRIP BURNER GROUND BURNER BOLT LOW GAS PRESSURE SWITCH 1 BLACK RED 2 WHITE 1 BLACK 2 BLACK...

Page 66: ...IRCUIT DO NOT SHARE POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD S...

Page 67: ...eview the following 1 See Mixing Valves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 ONE WATER HEATER SINGLE TEMPERATURE WITH BUILDING RECIRCULAT...

Page 68: ...es on page 14 3 See Temperature Pressure Relief Valve on page 15 ONE WATER HEATER TWO TEMPERATURE WITH HIGH TEMPERAURE LOOP RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF...

Page 69: ...ve on page 15 ONE WATER HEATER SINGLE TEMPERATURE WITH VERTICAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING...

Page 70: ...WATER HEATER SINGLE TEMPERATURE WITH HORIZONTAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN FUL...

Page 71: ...llowing 1 See Mixing Valves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 TWO WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND...

Page 72: ...Mixing Valves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 THREE WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE...

Page 73: ...ves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 FOUR WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RE...

Page 74: ...ve method of controlling thermal expansion is also installed at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method...

Page 75: ...75...

Page 76: ...PO Box 1597 500 Princeton Road Johnson City TN 37605 Phone 800 456 9805 Fax 800 999 5210 www americanwaterheater com...

Reviews: