ROOM TEMPERATURE
OHMS OF
RESISTANCE
°F
°C
40
4.4
26.1K
42
5.6
24.7K
44
6.7
23.4K
46
7.8
22.1K
48
8.9
21.0K
50
10.0
19.9K
52
11.1
18.9K
54
12.2
17.9K
56
13.3
17.0K
58
14.4
16.1K
60
15.6
15.3K
62
16.7
14.5K
64
17.8
13.8K
66
18.9
13.1K
68
20.0
12.5K
70
21.1
11.9K
72
22.2
11.3K
74
23.3
10.8K
76
24.4
10.2K
78
25.6
9.8K
80
26.7
9.3K
82
27.8
8.9K
84
28.9
8.5K
86
30.0
8.1K
88
31.1
7.7K
90
32.2
7.3K
92
33.3
7.0K
94
34.4
6.7K
96
35.6
6.4K
98
36.7
6.1K
100
37.8
5.8K
Table 1.
Sensor Resistance at Room Temperature.
Installer’s Guide
CALIBRATION
The Remote Indoor Temperature Sensor is calibrated at the
factory and cannot be recalibrated in the field.
The Remote Indoor Temperature Sensor response can be
calibrated at the Comfort Control. See the Installer’s Guide