Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to
change design and specifications without notice.

American Standard Inc.
6200 Troup Highway
Tyler, TX 75707

For more information contact
your local dealer (distributor)

ROOM TEMPERATURE

OHMS OF

RESISTANCE

°F

°C

40

4.4

26.1K

42

5.6

24.7K

44

6.7

23.4K

46

7.8

22.1K

48

8.9

21.0K

50

10.0

19.9K

52

11.1

18.9K

54

12.2

17.9K

56

13.3

17.0K

58

14.4

16.1K

60

15.6

15.3K

62

16.7

14.5K

64

17.8

13.8K

66

18.9

13.1K

68

20.0

12.5K

70

21.1

11.9K

72

22.2

11.3K

74

23.3

10.8K

76

24.4

10.2K

78

25.6

9.8K

80

26.7

9.3K

82

27.8

8.9K

84

28.9

8.5K

86

30.0

8.1K

88

31.1

7.7K

90

32.2

7.3K

92

33.3

7.0K

94

34.4

6.7K

96

35.6

6.4K

98

36.7

6.1K

100

37.8

5.8K

Table 1.

Sensor Resistance at Room Temperature.

Installer’s Guide

CALIBRATION

The Remote Indoor Temperature Sensor is calibrated at the
factory and cannot be recalibrated in the field.

The Remote Indoor Temperature Sensor response can be
calibrated at the Comfort Control. See the Installer’s Guide
or User’s Manual for details.

Summary of Contents for ZZSENSAL0400AA

Page 1: ...led pipes or ducts ii Drafts from fireplaces or other heat sources iii Convection or radiant heat from the sun or electrical equipment b Cold areas caused by i Concealed pipes or ducts ii Drafts from windows and doors iii Unheated areas on the other side of the wall location c Dead air areas i Behind doors furniture and curtains ii In corners and alcoves 4 Remove remote indoor sensor cover by gras...

Page 2: ... Do not route temperature sensor wiring with building power wiring next to control contactors or near light dimming circuits electric motors or welding equipment Avoid poor wiring connections Avoid intermittent or missing building earth ground CAUTION Disconnect power supply before connecting wiring Failure to do so may cause equipment damage Wiring must comply with applicable codes ordinances and...

Page 3: ...es See Table 1 The Sensor can be used to provide one remote input see Fig 3 or as a temperature averaging network with multiple Sensors connected as shown in Fig 5 CHECKOUT For best results leave the Remote Indoor Temperature Sensor at a stable room ambient for a minimum of twenty minutes before taking a resistance measurement With an accurate thermometer 1 F 0 5 C measure the temperature at the s...

Page 4: ...7 0K 58 14 4 16 1K 60 15 6 15 3K 62 16 7 14 5K 64 17 8 13 8K 66 18 9 13 1K 68 20 0 12 5K 70 21 1 11 9K 72 22 2 11 3K 74 23 3 10 8K 76 24 4 10 2K 78 25 6 9 8K 80 26 7 9 3K 82 27 8 8 9K 84 28 9 8 5K 86 30 0 8 1K 88 31 1 7 7K 90 32 2 7 3K 92 33 3 7 0K 94 34 4 6 7K 96 35 6 6 4K 98 36 7 6 1K 100 37 8 5 8K Table 1 Sensor Resistance at Room Temperature Installer s Guide CALIBRATION The Remote Indoor Temp...

Reviews: