27
Installation
Smoke Detector - (ReliaTel™ only)
Customer Low Voltage Wiring-
When interlocking System Sensor smoke detectors to-
gether, all of the detectors must be powered from the same
power supply. If the smoke detectors are powered up by dif-
ferent power supplies, harmonics are set up and will fry the
boards in some, if not all, of the detectors.
If multiple smoke detectors are required, all detectors must
be disconnected from the HVAC unit power supply and con-
nected together from another single source supply.
Note: Do not interconnect any smoke detectors
together that have separate power supplies. Do not
exceed ten smoke detectors on one power supply.
Note: Multiple System Sensor smoke detectors are
connected together using terminals 1 and 12 on
each detector.
If you have supply and return smoke detectors in all HVAC
units, you can connect a maximum of 5 HVAC units (10 de-
tectors) up to one power supply. See the following field wir-
ing example below.
If you have more than 5 HVAC units, you can connect all the
supplies together on one power supply (up to 10 HVAC
units), and all the returns together (up to 10 HVAC units) on
another power supply. See the following field wiring ex-
ample below.