American Standard YCC018F-L Installation Operation & Maintenance Download Page 15

Dwg. No. X664209 P01

Page 15

FIRING RATE SELECTION

GAS FLOW IN CUBIC FEET PER HOUR

2 CUBIC FOOT DIAL

Sec.

Flow

Sec.

Flow

Sec.

Flow

Sec.

Flow

  8

 900

  29

 248

  50

 144

  82

  88

  9

 800

  30

 240

  51

 141

  84

  86

 10

 720

  31

 232

  52

 138

  86

  84

 11

 655

  32

 225

  53

 136

  88

  82

 12

 600

  33

 218

  54

 133

  90

  80

 13

 555

  34

 212

  55

 131

  92

  78

 14

 514

  35

 206

  56

 129

  94

  76

 15

 480

  36

 200

  57

 126

  96

  75

 16

 450

  37

 195

  58

 124

  98

  73

 17

 424

  38

 189

  59

 122

 100

  72

 18

 400

  39

 185

  60

 120

 104

  69

 19

 379

  40

 180

  62

 116

 108

  67

 20

 360

  41

 176

  64

 112

 112

  64

 21

 343

  42

 172

  66

 109

 116

  62

 22

 327

  43

 167

  68

 106

 120

  60

 23

 313

  44

 164

  70

 103

 124

  58

 24

 300

  45

 160

  72

 100

 128

  56

 25

 288

  46

 157

  74

  97

 132

  54

 26

 277

  47

 153

  76

  95

 136

  53

 27

 267

  48

 150

  78

  92

 140

  51

 28

 257

  49

 147

  80

  90

 144

  50

TABLE 3

All units are capable of firing at a low or high rate. Check the unit
name-plate, to verify the firing rate of the unit as shipped from the
factory.

If the other input rate is desired, the conversion is made as follows:

1. Be sure the unit disconnect is open.

2. Be sure the gas valve is closed.

3. Remove furnace access panel.

4. Remove the presently installed gas orifices and replace with

the new gas orifices from the low fire kit. The orifices should extend
1/4 inch out of the manifold for burner support.

5. For low fire operation an OUTLET FLUE RESTRICTOR

(packed in the low fire kit) must be installed (see Figure 16 on page
14).  For high fire operation on a few models a different OUTLET
FLUE RESTRICTOR may have been required.

6. Reinstall the furnace access panel.

7. Open the gas valve.

8. Close the unit disconnect.

9. Follow the heating cycle instructions to test unit’s function.

10. Mark an “X” below the new input column on unit nameplate.

Attach conversion label to the unit below the nameplate.

NOTE: Do not convert to high fire when the units are applied above
2000 feet above seal level.

INPUT CHECK AND ADJUSTMENT

1. Make sure all gas appliances are off except the furnace.

2. Clock the gas meter with the furnace operating (determine the

dial rating of the meter) for one revolution.

3. Match the “Sec” column in the gas flow (in cfh) Table 3 with the

time clocked.

4. Read the “Flow” column opposite the number of seconds

clocked.

5. Use the following factors if necessary.

For 1 Cu. Ft. Dial Gas Flow CFH =

Chart Flow Reading / 2

For 1/2 Cu Ft. Dial Gas Flow CFH =

Chart Flow Reading / 4

For 5 Cu. Ft. Dial Gas Flow CFH =

10X Chart Flow Reading / 4

6. Multiply the final figure by the heating value of the gas obtained

from the utility company and compare to the nameplate rating.
This must not exceed the nameplate rating.

7. Changes can be made by adjusting the manifold pressure.

a. Attach a manifold pressure gauge.

HIGH ALTITUDE INSTALLATION

Unit nameplate ratings are based on equipment operation from sea
level to 2000 feet elevation above sea level.  If the unit installation
is from 2000 - 4500 feet elevation,  it will be necessary to change the
burner orifices to the noted sizes, (ref. National Fuel Gas Code, sec
8.1.2, Appendix F, Table F4).

b. Remove the slot screw on top of the gas valve for 1st stage

manifold pressure adjustment.

c. Turn the adjustment nut IN to increase the gas flow rate, and

OUT to decrease the gas flow rate using a 3/32" hex wrench.

GAS

TYPE

MANIFOLD

PRESSURE

( in. W.C. )

ORIFICE SIZE

0 - 2000 ft

ORIFICE SIZE

2000 - 4500 ft

NATURAL

( high input )

3.3

42

*

43

NATURAL

( low input )

3.3

44

45

PROPANE

10.0

54

55

*

 FACTORY SHIPPED

Summary of Contents for YCC018F-L

Page 1: ...ly with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Package Convertibl...

Page 2: ...ed application The power supply must be adequate for both the unit and all accessories 3 Check to be sure the refrigerant charge has been retained during shipment Access to 1 4 flare pressure taps may...

Page 3: ...AIR DUCT ROOF MOUNTING CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIED SUPPORTS AT EACH END OF CURB ROOFING ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY AIR DUCT RETURN AIR DUCT ROO...

Page 4: ...08 92 1 113 7 358 55 1 4 36 29 3 16 18 9 16 11 1 16 6 9 16 6 13 16 17 20 3 4 25 13 16 17 1 2 10 3 4 7 16 YCC036F L 78 3 68 3 95 6 109 7 352 19 3 4 24 13 16 YCC036F M 86 67 6 93 2 115 13 364 YCC036F H...

Page 5: ...4 CONDUIT YCC036F L YCC036F M YCC036F H 62 3 4 36 29 3 16 14 1 2 27 1 2 KNOCKOUTS FOR 3 4 AND 1 1 4 CONDUIT YCC042F M YCC048F M YCC048F H 64 5 16 45 33 3 8 14 13 16 27 15 16 KNOCKOUTS FOR 3 4 AND 1 1...

Page 6: ...ICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT RETURN...

Page 7: ...to be inadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and...

Page 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing...

Page 9: ...th a perimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 i...

Page 10: ...OP APPLICATION WITH FRAME YCC018 060F 9 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure...

Page 11: ...ine downward away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to...

Page 12: ...State of California law Proposition 65 WARNING This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inha...

Page 13: ...PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 14: ...t six 6 inches in depth next to the union as shown in Figure 14 This drip leg is required to collect any sediment that may be deposited in the line 4 Before connecting the piping circuit to the unit b...

Page 15: ...instructions to test unit s function 10 Mark an X below the new input column on unit nameplate Attach conversion label to the unit below the nameplate NOTE Do not convert to high fire when the units a...

Page 16: ...ed within the unit Otherwise a filter rack must be installed by the installer in the duct work Affix the filter label supplied with the unit adjacent to the filter area TABLE 4 Filters must be install...

Page 17: ...vers and access doors before leaving the unit or turning on the power to the unit ELECTRICAL WIRING i After all electrical wiring is complete set the thermostat system switch in the OFF position so th...

Page 18: ...rge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant char...

Page 19: ...ulator located on the front side of the unit s gas valve b Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pres sure 3 Check the temperature r...

Page 20: ...e gas valve GV is de energized instantly The ignition control module IGN then enters the retry mode The retry mode allows the control IGN to purge for 60 seconds Following this time period the valve i...

Page 21: ...on Pressure Too High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D...

Page 22: ...iring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operati...

Page 23: ...e labor and diagnosis calls are not included This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession damage caused by un...

Page 24: ...or warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for t...

Reviews: