American Standard YCC018F-L Installation Operation & Maintenance Download Page 13

Dwg. No. X664209 P01

Page 13

IMPORTANT:  Before making the gas pipe connection give
serious consideration to providing the required clearance nec-
essary to remove the access panels on the unit
(e.g., economizer and filter access panels).

NOTE: In the absence of local codes, the installation must
conform with American National Standard--Z223.1--National Fuel
Gas Code, Latest Revision.

The available gas supply must agree with the required gas supply
marked on the unit nameplate.  Minimum permissible gas supply
pressure for purpose of input adjustment must be at least 5.0" W.
C. (inches Water Column) for natural gas and 11' W.C. for propane.

PIPE DELIVERY SCHEDULE  (NATURAL GAS ONLY)

NOTE:    The following procedure and tables below apply to
Natural Gas only.

1.Obtain from the gas company the heating value and specific

gravity of the gas delivered.

2.Determine the exact length of pipe needed.

3.Read the BTUH input nameplate on the furnace.

4.Use the multiplier opposite the specific gravity of the gas given in

Table 1 below and insert in the following formula:

TABLE 1

GAS PIPING INSTALLATION

  CFH =

Furnace Input in BTUH

Gas Heat Content in BTU/Cu. Ft. X Multiplier

This will give the factor for columns 2 through 6 in Table 2.

5.Using Table 2, select the pipe length nearest to yours.

6.Follow this line vertically down to the exact CFH found in Step 4

above or the next highest value.

7.Read horizontally to the left of this column for the required pipe

size diameter.

TABLE 2

NATURAL GAS ONLY

TABLE OF CUBIC FEET PER HOUR OF GAS

FOR VARIOUS PIPE SIZES AND LENGTHS

PIPE
SIZE

(inch)

LENGTH OF PIPE (feet)

10

20

30

40

50

60

70

1/2

132

92

73

63

56

50

46

3/4

278

190

152

130

115

105

96

1

520

350

285

245

215

195

180

1-1/4

1050

730

590

520

440

400

370

  THIS TABLE IS BASED ON PRESSURE DROP OF 0.3 INCH W.C. AND 0.6 SP.GR. GAS

NOTE:  If this is an propane application, consult your propane
supplier for pipe sizes and deliveries.

GAS PRESSURE SET-UP PRECAUTIONS

IMPORTANT:  The furnace and its individual shut-off valve
must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures
exceeding 1/2 psig (3.48 kPa).

The furnace must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures less than
or equal to 1/2 psig (3.48 kPa).

GAS SUPPLY LINE PRESSURE  (ALL FUELS)

Before connecting the unit to the gas supply line, be sure to
determine the gas pressure in the line.

If the gas supply pressure is excessive (above 13.8 inches water
column or 1/2 psig), install a pressure regulator either at the supply
source or in the branch circuit serving the unit.  Once the regulator
is installed, set it to provide a maximum pressure of 13.8" W.C. to
the gas valve for natural gas with a minimum supply pressure of 5.0"
W.C. Maximum supply pressure of 13.8" W.C. to the gas valve for
propane with a minimum pressure of 11.0" W.C.

NOTE:  Maximum pressure to the gas valve for natural gas
is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
pressure to the gas valve for propane is 13.8"W.C. Minimum
pressure to the gas valve is 11.0" W.C.

If the supply line pressure is below the minimum supply pressure
indicated on the unit nameplate, contact the gas supply company.

Follow these steps to complete the installation of the unit gas piping.
See Figure 14.

1. Install a tapped, Style A (1/8-inch NPT tap) shut-off gas cock at

the end of the gas supply line near the unit.  Be sure the tapped
gas cock is downstream of the pressure regulator, if used.

SPECIFIC

GRAVITY

MULTIPIER

MULTIPIERS TO BE USED

WHEN THE SPECIFIC

GRAVITY OF THE GAS IS

OTHER THAN 0.60

.50

1.10

.55

1.04

.60

1.00

.65

.962

DEALER INSTALLED

GROUND UNION

1/8" N.P.T.PLUGGED

ACCESS FOR TEST

GAUGE CONNECTION

FROM

GAS SUPPLY

DRIP LEG

FIELD SUPPLIED MAIN

GAS VALVE, MUST BE

INSTALLED BY DEALER

OUTSIDE UNIT.

UNIT

TO MAIN

CONTROL

VALVE

6"

MIN

r

WARNING:

 

NEVER USE AN OPEN FLAME 

TO TEST FOR GAS LEAKS: AN EXPLOSION COULD 
OCCUR, CAUSING INJURY OR DEATH.  

Summary of Contents for YCC018F-L

Page 1: ...ly with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Package Convertibl...

Page 2: ...ed application The power supply must be adequate for both the unit and all accessories 3 Check to be sure the refrigerant charge has been retained during shipment Access to 1 4 flare pressure taps may...

Page 3: ...AIR DUCT ROOF MOUNTING CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIED SUPPORTS AT EACH END OF CURB ROOFING ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY AIR DUCT RETURN AIR DUCT ROO...

Page 4: ...08 92 1 113 7 358 55 1 4 36 29 3 16 18 9 16 11 1 16 6 9 16 6 13 16 17 20 3 4 25 13 16 17 1 2 10 3 4 7 16 YCC036F L 78 3 68 3 95 6 109 7 352 19 3 4 24 13 16 YCC036F M 86 67 6 93 2 115 13 364 YCC036F H...

Page 5: ...4 CONDUIT YCC036F L YCC036F M YCC036F H 62 3 4 36 29 3 16 14 1 2 27 1 2 KNOCKOUTS FOR 3 4 AND 1 1 4 CONDUIT YCC042F M YCC048F M YCC048F H 64 5 16 45 33 3 8 14 13 16 27 15 16 KNOCKOUTS FOR 3 4 AND 1 1...

Page 6: ...ICE CLEARANCE LINES A B C D SUPPLY AIR RETURN AIR NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARD THE OUTSIDE OF THE UNIT TO DISENGAGE THE BACK ATTACHMENT RETURN...

Page 7: ...to be inadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and...

Page 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing...

Page 9: ...th a perimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 i...

Page 10: ...OP APPLICATION WITH FRAME YCC018 060F 9 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure...

Page 11: ...ine downward away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to...

Page 12: ...State of California law Proposition 65 WARNING This product contains fiberglass wool insulation Fiberglass dust and ceramic fibers are believed by the State of California to cause cancer through inha...

Page 13: ...PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures...

Page 14: ...t six 6 inches in depth next to the union as shown in Figure 14 This drip leg is required to collect any sediment that may be deposited in the line 4 Before connecting the piping circuit to the unit b...

Page 15: ...instructions to test unit s function 10 Mark an X below the new input column on unit nameplate Attach conversion label to the unit below the nameplate NOTE Do not convert to high fire when the units a...

Page 16: ...ed within the unit Otherwise a filter rack must be installed by the installer in the duct work Affix the filter label supplied with the unit adjacent to the filter area TABLE 4 Filters must be install...

Page 17: ...vers and access doors before leaving the unit or turning on the power to the unit ELECTRICAL WIRING i After all electrical wiring is complete set the thermostat system switch in the OFF position so th...

Page 18: ...rge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant char...

Page 19: ...ulator located on the front side of the unit s gas valve b Turn the adjusting screw clockwise to increase manifold pressure or counterclockwise to decrease manifold pres sure 3 Check the temperature r...

Page 20: ...e gas valve GV is de energized instantly The ignition control module IGN then enters the retry mode The retry mode allows the control IGN to purge for 60 seconds Following this time period the valve i...

Page 21: ...on Pressure Too High Suction Pressure Too Low Liquid Refrigerant floodback TXV System Liquid Refrig floodback Cap Tube System I D Coil Frosting Compressor Runs Inadequate or No Cooling Compressor O D...

Page 22: ...iring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operati...

Page 23: ...e labor and diagnosis calls are not included This limited warranty does not cover failure of your combination gas electric air conditioner if it is damaged while in your possession damage caused by un...

Page 24: ...or warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for t...

Reviews: