background image

Pub. No. 32-5022-10

Page 3

Upflow / Horizontal Furnace Filters

The Upflow/Horizontal furnace when installed horizontally re-
quires a horizontal filter kit.  The filters may be located remote
to the furnace or in the return air duct near the furnace.  Check
with your dealer for the location of your filters.

An upflow/horizontal furnace in horizontal return air filter
application, as shown, features two 16" x 20" x 1" filters in the 17-
1/2", 21" and 24-1/2" wide furnace cabinets.

UPFLOW/HORIZONTAL WITH FILTER KIT

To replace filters, remove the filter access door, lift the filter from
the lower bracket and shift the filter to the side to free the top
filter from the bracket and slide the filters out through the filter
access door.  After cleaning, replace the filters in the same
manner making sure that the filters are secured in place in both
top and bottom filter brackets. Replace filter access door.

Air filters may also be located outside of the furnace using a
remote filter grille

.  

The filter grille could be in a hallway, wall,

or in the ceiling.  Check with your dealer for the exact location of
your filter and the method of changing the filters.

UPFLOW (Vertical) FILTER TABLES

Downflow/Horizontal furnaces are factory supplied with 2 stan-
dard size permanent type air filters which may be located remote
to the furnace or in the return air duct.  Check with your dealer
for the location of your filters.

A downflow/horizontal furnace return air filter application, as
shown, features two 14" x 20" x 1" filter in the 17-1/2" wide
furnace cabinets; or two 16" x 20" x 1" filter in the 21" and 24-1/
2" wide furnace cabinets.

DOWNFLOW FILTER

A downflow/horizontal furnace return air filter application, as
shown, features two 14" x 20" x 1" filter in the 17-1/2" wide
furnace cabinets; or two 16" x 20" x 1" filter in the 21" and 24-1/
2" wide furnace cabinets.

DOWNFLOW/HORIZONTAL FILTER

DOWNFLOW  (Vertical) FILTER TABLE

REQUIRED FILTERS - BOTTOM

CABINET WIDTH

FILTER QUANTITY & SIZE

17-1/2"

1 - 17" X 25" X  1"

21"

1 - 20" X 25" X  1"

24-1/2"

1 - 24" X 25" X  1"

REQUIRED FILTERS - SIDE  **

CABINET WIDTH

FILTER QUANTITY & SIZE

17-1/2"

1 - 17" X 25" X  1"

21"

1 - 20" X 25" X  1"

24-1/2"

1 - 24" X 25" X  1"

** ON UPFLOW 5 TON AIRFLOW MODELS, IF THE
AIRFLOW REQUIREMENT EXCEEDS 1800 CFM, THESE
MODELS WILL REQUIRE FILTERS ON BOTH SIDES 

OR

 1

SIDE AND THE BOTTOM, 

OR

 JUST THE BOTTOM

REQUIRED FILTERS - DOWNFLOW

CABINET WIDTH

FILTER QUANTITY & SIZE

17-1/2"

2 - 16" X 20" X  1"

21"

2 - 16" X 20" X  1"

24-1/2"

2 - 16" X 20" X  1"

Summary of Contents for *UY Series

Page 1: ...use by individuals pos sessing adequate backgrounds of electrical and mechani cal experience Any attempt to repair a central air condi tioning product may result in personal injury and or prop erty damage American Standard Inc or seller cannot be responsible for the interpretation of this information nor can it assume any liability in connection with its use UnderstandthesignalwordsDANGER WARNING ...

Page 2: ...which are the same size as originally supplied How to remove your filter WARNING Disconnect power to unit before removing blower door Upflow furnaces use a high velocity type air filter which may be located within the furnace blower compartment in either a BOTTOM or SIDE left or right return air inlet The furnace may be secured with filter retaining brackets as shown or a filter retainer wire To r...

Page 3: ...d the method of changing the filters UPFLOW Vertical FILTER TABLES Downflow Horizontal furnaces are factory supplied with 2 stan dard size permanent type air filters which may be located remote to the furnace or in the return air duct Check with your dealer for the location of your filters A downflow horizontal furnace return air filter application as shown features two 14 x 20 x 1 filter in the 1...

Page 4: ...re power to blower and gas valve 7 Lockout 7 Turn power on off on off twice in 30 secs Insufficient Heating 1 Dirty air filters 1 Clean or replace filters Blower operates continuously 2 Blocked supply or 2 Make sure registers are open and return registers No obstacles blocking off the air No Heat Vent motor Restricted or plugged furnace 1 Remove drain clamps to condensate is running condensate dra...

Page 5: ... indicates that a service call is required For best operation burners must be cleaned annually using brushes and vacuum cleaner Turn off gas and electric power supply To clean burners remove top burner bracket and lift burner from orifice NOTE Be careful not to break igniter when removing burners Clean burners with brush and or vacuum cleaner Reassemble parts by reversal of the above procedure NOT...

Page 6: ... the casing of furnace must be kept free of obstructions which would restrict airflow thereby affecting efficiency and safe operation of your furnace Also air openings provided to the area in which the furnace is installed and the space around the furnace shall not be blocked or obstructed Keep this in mind should you choose to remodel theareawhichcontainsyourfurnace Furnacesmusthaveairfor proper ...

Page 7: ...off Valve May Be Located on the Right or Left Side Lighting instructions Your furnace is equipped with a hot surface direct ignition device WARNING Do not attempt to manually light the furnace 1 Please read all safety information in this book before operating furnace 2 Set thermostat to lowest setting Turn off all electric power to furnace 3 Remove control access panel 4 Turn gas cock knob on main...

Page 8: ...iginal installation of the furnace subject to proof of original purchase Warrantor WILL AT ITS OPTION provide either a heat exchanger including secondary heat exchanger without charge F O B nearest Parts Distribution point or allow a credit in the amount of the then current wholesale price of an equivalent heat exchanger toward the purchase price of a comparable heating unit Any local transportati...

Reviews: