background image

Page 19

START - UP

8. Set the thermostat at the desired temperature setting and the

unit will function automatically.

STARTING THE UNIT IN THE GAS HEATING MODE

1. Check to make sure all grilles and registers are open and all unit

access doors are closed before start-up.

2. Purge the gas supply line of air by opening the union ahead of

the unit.  When the odor of gas is detected, retighten the union
and wait five (5) minutes before proceeding.

3. Set the wall thermostat to its lowest position and place the fan

switch in the AUTO or ON position.

4. Open the main gas valve(s) and turn on the unit power supply.

5. Reset the heating temperature lever on the room thermostat at

the highest value above room temperature. The combustion
blower motor should energize. The main burners should light
within 20-25 seconds. Initial start may be delayed somewhat if
the unit has not been purged and air is trapped in the gas line.

NOTE:  Blue smoke produced by the heat exchanger during the
initial burner firing is caused by a thin film of oil on the surface
of the heat exchanger. This oil will burn off quickly.

6. Cycle the thermostat OFF and ON a few times at a rate of not

more than once every thirty (30) seconds. Check both the
control operation and the burner operating conditions.

MANIFOLD PRESSURE

1. Connect a manometer to the pressure tap at the outlet side of

the unit’s gas valve.  Read the manifold pressure with the main
burners firing.

2. If the manifold pressure reading does not match the value

indicated on the unit nameplate, the unit pressure regulator
must be adjusted as follows:

a. Remove the cover screw on the gas regulator located on the

front side of the unit’s gas valve.

b. Turn the adjusting screw clockwise to increase manifold

pressure or counterclockwise to decrease manifold pres-
sure.

3. Check the temperature rise during furnace operation to insure

that it falls within the range specified on the unit nameplate.

4. If the temperature rise noted is outside of the specified limits,

adjust the indoor air flow to cause the temperature rise of the
heat exchanger to fall within the required range.

Operation of the unit heating or cooling cycles is controlled by the
setting of the system switch on the room thermostat. Once the
system switch is placed either in the “HEAT” or “COOL” position,
unit operation is automatic. A fan switch on the thermostat also
provides for it continuous operation of the evaporator fan when
desired. The fan switch “ON” position provides continuous opera-
tion while the “AUTO” position provides operation during the heat-
ing or cooling cycles.

HEATING CYCLE
Thermostat call for heat ( 2-stage thermostat)

Call for 1st stage only:

(R) and (W1) thermostat contacts close signaling the control mod-
ule (IGN) to run its self-check routine. After the control has verified
that the pressure switch (PS) contacts are open, the limit switch
(TCO) contacts are closed, and the flame rollout (FL) switch is
closed, the induced draft blower (CBM) will be energized on high
speed for approximately 5 seconds.

After the induced draft blower (CBM) has come up to speed, the
control will verify that the pressure switch (PS) contacts are closed
and switch the induced draft blower to low speed for 10 second
prepurge.  The gas valve (GV) is energized in  the  first  stage  to
permit gas flow and the spark ignitor (IP) is energized. The flame
detector (FD) confirms that ignition has been achieved within the 7
second trial period.

As the flame detector confirms that ignition has been achieved the
delay to indoor fan on period begins timing and after approximately
45 seconds, the indoor blower motor (IDM) will be energized at low
speed and will continue to run during the heating cycle.

Call for 2nd stage after 1st stage:

(R) and (W2) thermostat contacts close signaling a call for second
stage heat. The induced draft motor (CBM) is energized on high
speed and the gas valve on second stage. After approximately 30
seconds the control energizes the indoor blower on high speed.
2nd stage satisfied, 1st stage still called:

(R) and (W2) opens, the induced draft blower is reduced to low
speed the gas valve is reduced to first stage. After aprox. 30
seconds the indoor blower motor is reduced to low speed.
1st stage satisfied:

(R) and (W1) opens, the gas valve (GV) will close. The induced draft
blower (CBM) will be de-energized after approximately 5 seconds
postpurge. The indoor blower motor (IDM) will continue to run for the
fan off period (field selectable 60 or 90 seconds [by dip switch]), then
will be de-energized by the control module.
Thermostat satisfied:

(R) and (W1/W2) (jumpered) contacts open signaling the control
module to close the gas valve and de-energize the induced draft
blower after approximately 5 second postpurge. The I.D. blower
motor will continue to operate at the current speed for 60  or 90
seconds after the flames are extinguished .

SAFETY SEQUENCES
This product is equipped with safety devices to protect against
abnormal conditions.

The temperature limit switch (TCO) is located in the gas com-
partment on the vestibule panel above the burner assembly. This
automatic reset device protects against excessive leaving air
temperature. If this device opens, the gas valve is immediately
closed and will not permit operation until the limit switch closes.

SEQUENCE OF OPERATION

Summary of Contents for BAYLIFT002A

Page 1: ...INSTALLATION OPERATION MAINTENANCE ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion of work Single Package Two Stage Gas Electric 16 SEER Convertible 3 5 Ton Model YCZ036F1 3M0B YCZ060F1 3M0B BAYLIFT002A LIFTING LUG KIT 18 EB21D4 2 Li...

Page 2: ...Installation and maintenance should be performed by qualified service technicians only NOTE Warnings and Cautions appear at appropriate places in this manual Your personal safety and the proper operation of this air conditioning product require that you follow them carefully The manufacturer assumes no liability for installations or servicing performed by unqualified personnel As shipped from the ...

Page 3: ...NG CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIED SUPPORTS AT EACH END OF CURB ROOFING ROOF INSULATION ROOF DECK FIELD SUPPLIED RIGID INSULATION SUPPLY AIR DUCT RETURN AIR DUCT ROOF MOUNTING CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIED SUPPORTS AT EACH END OF CURB ROOFING SEE NOTE 1 SEE NOTE 2 NOTES 1 The YCZ036F models extend out past this end of the curb ONLY 2 Only the YCZ060F models extend pas...

Page 4: ...G H J K L M N P 1 W 2 W 3 W 4 W G 6 3 0 Z C Y 1 6 1 6 0 1 4 0 1 7 5 1 8 2 5 4 6 6 3 6 1 3 9 2 6 1 9 8 1 6 1 1 1 1 6 1 9 6 8 1 1 1 7 1 2 1 8 1 2 1 5 2 2 1 7 1 0 1 3 4 3 8 G 0 6 0 Z C Y 5 9 1 9 2 1 2 3 1 9 9 1 6 5 6 8 1 5 6 5 4 8 3 3 3 6 1 1 1 2 6 1 1 5 1 6 1 5 1 4 8 1 9 6 1 5 1 1 2 4 3 2 2 2 1 5 2 0 2 4 1 2 1 3 6 1 5 8 YCZ036F YCZ060F ...

Page 5: ...H G I R 0 6 E D I S T N O R F 0 2 1 P O T 0 6 3 E C N A R A E L C E C I V R E S D E D N E M M O C E R K C A B 0 6 E D I S T F E L 0 0 3 E D I S T H G I R 0 4 2 E D I S T N O R F 0 2 4 Y R O S S E C C A R I A H S E R F H T I W 8 1 R E Z I M O N O C E H T I W 0 3 L E D O M A B C D M G 6 3 0 Z C Y 4 6 6 3 6 1 3 9 2 2 1 7 2 M G 0 6 0 Z C Y 8 1 5 6 5 4 8 3 3 3 6 1 5 1 7 2 ...

Page 6: ...E S O N L E D O M A B C D E F F 6 3 0 Z C Y 0 3 0 3 2 1 0 3 4 4 5 2 F 0 6 0 Z C Y 2 4 0 3 2 1 6 3 0 5 5 2 Y R O S S E C C A R I A H S E R F H T I W 8 1 R E Z I M O N O C E H T I W 0 3 HEATER EXCHANGER TUBES HORIZONTAL SUPPLY AIR COVER HORIZONTAL RETURN AIR COVER SHEET METAL SCREWS NOTE SUPPLY OPENING 1 REMOVE SCREW NEAREST TO THE OPENINGANDPULLTHEPANELFIRMLY TOWARDTHEOUTSIDEOFTHEUNITTO DISENGAGE T...

Page 7: ...nadequate should be reviewed with a local engineer 3 See the unit s nameplate for the absolute minimum clearance between the unit and any combustible surface s IMPORTANT 1 Remove the Flue and Air Inlet Hood with gasket from the return air section of the unit The screws that attach the flue and air inlet hood will be installed in their proper location at the factory Therefore they must be removed a...

Page 8: ...with Section 5 3 Air For Combustion and Ventilation of the National Fuel Gas Code ANSIZ223 1 Latest Revision or applicable provisions of the local building code PLACING AND RIGGING 1 Before preparing the unit for lifting check the outline drawing for center of gravity for lifting safety Because of placement of internal components the unit s weight may be unevenly distrib uted Approximate unit weig...

Page 9: ...rimeter drip lip that is lower that the unit base bar see Figure 7 inset A 2 Position the unit drip lip down over and in contact with the outside corner of the curb as illustrated in Figure 8 insert A Continue to lower the unit on top of the curb with the unit drip lip astraddle and in contact with both the end and side rail of the curb The unit should now rest on top of the curb 3 Take the two 2 ...

Page 10: ...ATION WITH FRAME YCZ036 060F 4 Place the unit on the frame or roof curb Refer to Figures 9 or 10 5 Secure the unit to the frame or roof curb 6 Insulate any ductwork outside of the structure with at least two 2 inches of insulation and then weatherproof There must be a weatherproof seal where the duct enters the structure 7 Complete the installation according to the instructions in the following se...

Page 11: ...ard away from the unit Avoid long horizontal runs See Figure 12 NOTE Do not use reducing fittings in the drain lines The condensate drain must be Made of 3 4 pipe size Pitched 1 4 per foot to provide free drainage to convenient drain system Trapped Must not be connected to closed drain system 2 Attach the supply and return air ducts to the unit 3 Insulate any ductwork outside of the structure with...

Page 12: ...ors to minimize noise and vibration transmission Elbows with turning vanes or splitters are recommended to mini mize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two feet from the unit to minimize noise and resistance DUCT ATTACHMENT METHODS The following warning complies with State of California law Proposition 65 WARNING This product contains...

Page 13: ...lt your LPG supplier for pipe sizes and deliveries GAS PRESSURE SET UP PRECAUTIONS IMPORTANT The furnace and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures exceeding 1 2 psig 3 48 kPa The furnace must be isolated from the gas supply piping system by closing its individual manual shut off valve during...

Page 14: ...ssure at the tapped shut off cock The pressure reading should not exceed 14 inches water column 5 Connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the pipe chase opening should be closed with the filler barrier plug provided MANIFOLD PRESSURE Check the manifold pressure at the ...

Page 15: ... e S w o l F c e S w o l F c e S w o l F c e S w o l F 8 0 0 9 9 2 8 4 2 0 5 4 4 1 2 8 8 8 9 0 0 8 0 3 0 4 2 1 5 1 4 1 4 8 6 8 0 1 0 2 7 1 3 2 3 2 2 5 8 3 1 6 8 4 8 1 1 5 5 6 2 3 5 2 2 3 5 6 3 1 8 8 2 8 2 1 0 0 6 3 3 8 1 2 4 5 3 3 1 0 9 0 8 3 1 5 5 5 4 3 2 1 2 5 5 1 3 1 2 9 8 7 4 1 4 1 5 5 3 6 0 2 6 5 9 2 1 4 9 6 7 5 1 0 8 4 6 3 0 0 2 7 5 6 2 1 6 9 5 7 6 1 0 5 4 7 3 5 9 1 8 5 4 2 1 8 9 3 7 7 1 4 2...

Page 16: ...er in the duct work Affix the filter label supplied with the unit adjacent to the filter area TABLE 4 THERMOSTAT HEAT ANTICIPATOR The thermostat heat anticipators should be set to 4 amps on single or two stage thermostats IMPORTANT Upon completion of wiring check all electrical connections including factory wiring within the unit make sure all connections are tight Replace and secure all electrica...

Page 17: ...s recommended that the sump heater be energized for eight 8 hours prior to starting After all electrical wiring is complete set the thermostat system switch in the OFF position so that the compressor will not run and then apply power by closing the system main disconnect switch This will activate the compressor sump heat Do not change ELECTRICAL WIRING 18 ...

Page 18: ...ures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS NOTE Do not use the pressures from the unit s SERVICE FACTS to determine the unit refrigerant charge The correct charge is shown on the unit nameplate To charge the system accurately weigh in the charge according to the unit nameplate VOLTAGE With the compressor operating check the line voltage at the unit...

Page 19: ...peration during the heat ing or cooling cycles HEATING CYCLE Thermostat call for heat 2 stage thermostat Call for 1st stage only R and W1 thermostat contacts close signaling the control mod ule IGN to run its self check routine After the control has verified that the pressure switch PS contacts are open the limit switch TCO contacts are closed and the flame rollout FL switch is closed the induced ...

Page 20: ...t 3 seconds to check if the Y2 may also be calling the board will energize CC1 and the outdoor fan relay for low speed and the G thermostat contact to G IGN and to G1 on the ICMC is energized The status light is flashing and the Y1 light is on The energized compressor contactor CC1 completes the circuit to the compressor CPR1 If the compressor safety controls are closed the compressor CPR1 will op...

Page 21: ... Hums But Will Not Start Compressor Cycles on IOL I D Blower Won t Start CHECKOUT PROCEDURE R O T A C I D N I C I T S O N G A I D D E L N G I W O L S G N I H S A L F T A E H R O F L L A C O N L A M R O N T S A F G N I H S A L F T A E H R O F L L A C L A M R O N N O S U O U N I T N O C L O R T N O C E C A L P E R F F O S U O U N I T N O C R E W O P K C E H C S E H S A L F 2 E M A L F O N T U O K C ...

Page 22: ...ach heating season Visually inspect the unit to ensure that the airflow required for combustionandcondensercoilisnotobstructedfromtheunit Inspect the control panel wiring to verify that all electrical connections are tight and that the wire insulation is intact Check the operation of the gas ignition system as follows Turn off the gas supply with the unit operating to verify that the gas valve clo...

Page 23: ...facturing defect within the third through twentieth year from the date of original purchase Warrantor will furnish with out charge a replacement heat exchanger Any local transportation related service labor and diagnosis calls are not included This warranty does not cover failure of your Combination Gas Electric Air Conditioner if it is damaged while in your possession or if the failure is caused ...

Page 24: ...ough fifth year from the date of original purchase Warrantor will furnish without charge a replacement heat exchanger Warrantor s obligations and liabilities under this warranty are limited to furnishing F O B War rantor factory or warehouse at Warrantor designated shipping point freight allowed to Buyer s city replacement parts for Warrantor s products covered under this warranty Warrantor shall ...

Reviews: