American Standard AZON1050AC52ZA Installation Manual Download Page 24

Installation Guide

24  

 11-HD15D1-5-EN

Example for determining System Mode:

ZONE 1 ZONE 2 ZONE 3 ZONE 4

Zone LV

60 (clg)

50 (clg)

60 (htg)

50 (htg)

Zone Size

.30

.45

.30

.65

Weighted LV

18

22.5

12

32.5

Cooling Sum

40.5

Heating Sum

44.5

System Mode

Heating

8.3.2 Capacity request (System LV)

System LV is used to determine how much capacity will 
be requested.  System LV is determined by the zone with 
largest load value in the current mode of operation. See 
Section 6.2 Load Value for heating and cooling tables for 
additional information regarding the load value ranges for 
different systems.

Example for determining System Load Value:

ZONE 1 ZONE 2 ZONE 3 ZONE 4

Zone LV

60 (clg)

50 (clg)

80 (clg)

50 (clg)

System LV

80

For VSPD outdoor units and modulating furnaces the 
System LV is scaled:

• 

SysLV 

 80 = Raw LV x 1.25

• 

SysLV > 80 = (Raw LV x .8333) + 33.33

• 

Zone LV is not scaled, only System LV

Example for determining Scaled System Load Value:

ZONE 1 ZONE 2 ZONE 3 ZONE 4

Zone LV

60 (clg)

50 (clg)

80 (clg)

50 (clg)

System LV

80

Scaled System LV

System LV (80) x 1.25 = 100

When zoning is applied the System LV may be inhibited for 
the following reasons:
• 

The sum of the calling zones is less than or equal to the 
current stage of capacity (compressor and gas furnace 
operation only)

• 

(VSPD systems only) Auxiliary Heat Clamp is enabled 
and the sum of the calling zones is less than or equal 
to the clamp setting (Installer Settings>Clamp LV for 
Auxiliary Heat)

For VSPD systems the speed of the compressor will be 
limited based on the air flow capacity of the calling zones. 
Oil return or other protection algorithms may override this 
clamp

8.3.3 Damper position

The position of the modulating dampers is determined by 
the amount of capacity each zone is requesting.
The damper position for each same mode calling zone 
follows the calculation below:
• 

Zone LV/ System LV = damper position

The minimum opening position is always 25% to reduce air 
whistling from a partially opened damper
Zones in the opposite or “off” mode are closed unless the 
system has calculated excess air.
Example of how Damper Positions are calculated for non-
VSPD and VSPD systems:

NON-VSPD

ZONE 1 ZONE 2 ZONE 3 ZONE 4

Zone LV

60 (clg)

50 (clg)

40 (clg)

50 (clg)

System LV

60

Damper Position

100%

83%

67%

83%

For non-VSPD systems one damper will always be full open 
on a call for capacity and the other dampers will modulate 
based on their load value.

VSPD

ZONE 1 ZONE 2 ZONE 3 ZONE 4

Zone LV

60 (clg)

50 (clg)

40 (clg)

50 (clg)

System LV

60

Scaled System LV

Sytem LV (60) x 1.25 = 

75

Damper Position

80%

67%

53%

67%

For VSPD cooling or compressor heating the scaling of 
the system load value will result in the dampers being in 
a less open position than non-VSPD systems. This partial 
restriction helps maintain static pressure for improved air 
flow distribution.

8.3.4 excess Air Management

The 1050 Control manages excess air without the need 
for bypass dampers, dump zones or position stops in the 
supply dampers.
The first method of managing excess air is to eliminate or 
reduce the excess through equipment stage control and air 
flow modulation 
• 

Equipment Stage Control – For systems with capacity 
control, the 1050 Control will limit the capacity request 
based on the sum of the calling zones size…insert 
chart
• 

For systems with capacity control, if the sum of the 
calling zones sizes are less than or equal to the 
current stage of capacity the system load value will 
be inhibited disallowing the next stage of operation

• 

For VSPD systems, the speed of the compressor 
will be limited based on air flow capabilities of the 
calling zones. This inhibit may be overridden during 
oil return mode or if the sum of the calling zones 
is less than the minimum compressor speed at the 

Summary of Contents for AZON1050AC52ZA

Page 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furth...

Page 2: ...rk Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 8 5 1 Power Up Sequence 8 5 2 Guided Setup Wizards 8 5 3 Installer Setup Screens 8 5 3 1 Group 1 Stan...

Page 3: ...minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized 2 Product Specifications 3 General Information...

Page 4: ...from the Internet router Tips to Help Maximize Signal Strength Mount the 1050 Control within 30 feet of wireless router Install 1050 Control with no more than three interior walls between it and the...

Page 5: ...ires extend through the Sub base See Figure 3 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4 of insulation from...

Page 6: ...nel B C R D ODT ODT RS RS R B D R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL INDOOR UNIT 1050 COMFORT CONTROL Heat Pump Multi Stage AC Caution Do not run Outdoor Remote sensor wire...

Page 7: ...unicating Controls w S9V2 Furnace and Comm Outdoor B C R D ODT ODT RS RS R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL S9V2 FURNACE OUTDOOR UNIT 1050 COMFORT CONTROL Caution Do not...

Page 8: ...ower Type Non Variable Variable Select the indoor blower type Constant Torque motors are considered non variable speed All Group 1 settings will be auto configured for fully communicating systems 5 Sy...

Page 9: ...when a voting zone is also requesting capacity Indoor Heating Airflow Offset above and below cooling airflow 1 50 50 0 The air flow offset is the difference between the design cooling air flow CFM per...

Page 10: ...a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A...

Page 11: ...uring 1st stage indoor heat operation 2nd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 Select of cycles per hour during 2nd stage indoor heat operation 3rd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 S...

Page 12: ...lect whether an outdoor temperature override is allowed Outdoor temperature sensor must be connected and enabled to allow this setting to be selected Ventilator Fan Action Ventilate with Blower Ventil...

Page 13: ...r cooling mode with a setpoint change greater than 2 Heating Aggressive Recovery 2 by Outdoor Temperature Enable Disable Select whether the 10 minute staging inhibit is disabled during heating mode wh...

Page 14: ...ower On Delay for variable speed blowers only 1 minute at 50 7 5 minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating...

Page 15: ...Disable Enable Enable defrost heater balance point for W3 only applicable when indoor heat is electric or hydronic Defrost Heater Balance Point W3 Setting 5 F 45 F Select an outdoor temperature to di...

Page 16: ...ler Code When an 1050 Control is connected to Nexia a Dealer Code can be entered to auto populate the dealer s contact information and logo The code is the dealer s registered phone number listed on A...

Page 17: ...Stage Gas Oil Heat LOAD VALUE RANGE COOLING 0 100 Single Stage Compressor 0 200 Two Stage VSPD Compressor A Load Value of 50 represents a request of 50 demand for single stage cooling units Y or 50 de...

Page 18: ...AGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 6 Stage Inhibits When the stage threshold is exceeded a stage inhibit is app...

Page 19: ...igured to only limit Day operation only limit Night operation or limit Day and Night operation to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Q...

Page 20: ...ort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 1050 Control has the ability to control a Whole House Dehumidifier through the normally open dry AUX Contacts on the optional...

Page 21: ...SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lockout Once enabled select an outdoor temperature which disables auxiliary heat anytime the outdoo...

Page 22: ...ilation only The ventilation run time per hour can be adjusted to meet ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the...

Page 23: ...default setting Trane or American Standard manufactured indoor unit with a variable speed blower branded Geothermal package units and oil furnaces are not supported Field supplied 24 volt transformer...

Page 24: ...on for each same mode calling zone follows the calculation below Zone LV System LV damper position The minimum opening position is always 25 to reduce air whistling from a partially opened damper Zone...

Page 25: ...odels If the 1050 Control still calculates excess air then the excess will be relieved following the rules below Relief Strategy 1 Divide the excess air evenly between the zones which are calling but...

Page 26: ...rect compressor speed and associated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must...

Page 27: ...ll is not immediately required Alert messages are not displayed on the home screen NORMAL Functionality may be lost but should recover or the information is for diagnostic purposes performance monitor...

Page 28: ...or speed currently operating Cool Current cooling set point per zone Load Value Numerical value used to determine how much capacity is required to meet set point For more information see 6 2 Load Valu...

Page 29: ...uipment 3 Check repair system Heating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is no...

Page 30: ...time of inactivity Screen Saver mode set to Black which turns of screen back light after a user selected time of inactivity Normal operation User may change screen saver from Black to Indoor Temperat...

Page 31: ...l interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following me...

Page 32: ...D1 5 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Reviews: