American Standard AZON1050AC52ZA Installation Manual Download Page 22

Installation Guide

22  

 11-HD15D1-5-EN

7.6  Humidifier Operation

The 1050 Control has the ability to control a humidifier. 
Humidification is only enabled while in heating mode of 
operation. Control options are:

• 

RH Control – When the indoor humidity is less than 
the heating target relative humidity, a request for 
humidification is sent to the indoor unit.

• 

Frost Control – The 1050 Control references the 
outdoor temperature and structure integrity to offset 
the heating target relative humidity. This helps to 
limit the risk of frost or condensation from forming 
on interior walls and windows. A scale of 1 to 10 is 
provided based on the insulation properties and 
expected leakage of the home (1=Leaky with poor 
insulation, 10=Very Tight with good insulation). An 
outdoor temperature sensor must be connected and 
enabled for frost control to be available.

Frost Control Structure Integrity Scale

Leaky, Poor Insulation

Average

Good Insulation, Tight

1

2

3

4

5

6

7

8

9

10

The 1050 Control can be setup to allow humidification 
anytime in heating mode or only when actively heating. 
The airflow during Humidifier-only is factory set to 100% 
but can be adjusted between 35%-100% (this requires a 
variable speed indoor blower). All humidifier control options 
are located in the Installer Setup>Accessories Settings. 
When zoning is applied, all dampers open fully on a for 
humidification only.

7.7  Stage Inhibits 

The 1050 Control utilizes a Stage Inhibit to limit equipment 
staging. This inhibit can be defeated in the following two 
manners.

7.7.1 Aggressive recovery

Greater than 2

°

Setpoint Change

Disables stage inhibits in heating and cooling mode anytime 
the setpoint is adjusted more than 2°F

7.7.2 Heating Aggressive recovery

By Outdoor Temperature

Disable stage inhibit in heating mode only when the outdoor 
temperature falls below the selected outdoor temperature.
Note: If Aggressive Recovery is enabled, Heating 
Aggressive Recovery is disabled.

7.8  Ventilation Operation

The 1050 Control has the ability to control a Ventilation 
system through the normally open dry AUX Contacts on 
the optional Relay Panel. The blower can be interlocked 
on a call for ventilation. The blower speed during a call for 

ventilation only will be the same as the continuous fan setting 
for units with a variable speed indoor blower. When zoning 
is applied, all dampers open fully on a call for ventilation 
only. The ventilation run time per hour can be adjusted to 
meet ASHRAE 62.2 standards. A temperature override can 
be set to prevent ventilation operation when the outdoor 
temperature exceeds the minimum or maximum outdoor 
temperature selections. If outdoor temperature overrides 
are enabled the user can select to accumulate the missed 
ventilation run time. Options are below:

• 

Accumulate missed ventilation run time in 4 
hour increments and make up when the outdoor 
temperature is within the min/max settings.

• 

Accumulate missed ventilation run time in 24 
hour increments and make up when the outdoor 
temperature is within the min/max settings

• 

Accumulate missed ventilation run time in 4 hour 
increments and make up at the end of 4 hour period.

• 

Accumulate missed ventilation run time in 24 hour 
increments and make up at the end of 24 hour period.

All Ventilation control options are located in the 
Installer Setup>Accessories Settings.

7.9  Warm Air Discharge

[Disabled when zoning is applied] 

Enabling Warm Air 

Discharge will reduce the variable speed blower air flow 
by 20% when in compressor heating operation. Warm 
Air Discharge only applies to compressor heating and is 
disabled when hydronic, fossil fuel or electric heat (including 
supplemental heat) modes are activated. Warm Air Discharge 
can be enabled in Installer Setup>Comfort Settings.

7.10  Wet Heat (Hydronic) Operation

A hot water coil can be applied to either a variable speed 
or non-variable speed indoor unit. The hot water coil can 
be the sole source of heat or used as auxiliary heat when 
applied with a heat pump. When applied with a heat pump, 
wet heat is considered auxiliary heat and will operate in-
conjunction with heat pump heat. Switching the system 
mode to emergency heat would disable the heat pump and 
cycle the wet heat only. 
When using BK to control a variable speed air handler, 
the blower speed during wet heat only heating will vary 
based on the system load value. The airflow will range 
from 35% to 100% depending on the system load value. 
When applied with a heat pump, the blower speed during 
heat pump and wet heat operation will be the higher of the 
two air flows. When not using BK for variable speed blower 
control, the air handler will determine air flow. There are 
separate blower “On” and “Off” delays for wet heat in the 
1050 Control. 
The 1050 Control is designed to operate forced air systems 
and should not be applied to non-forced air systems (radiant 
floors, radiators, etc…)
The hydronic heat blower delay options can be accessed 
by navigating to Installer > Setup > Airflow Settings.

Summary of Contents for AZON1050AC52ZA

Page 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furth...

Page 2: ...rk Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 8 5 1 Power Up Sequence 8 5 2 Guided Setup Wizards 8 5 3 Installer Setup Screens 8 5 3 1 Group 1 Stan...

Page 3: ...minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized 2 Product Specifications 3 General Information...

Page 4: ...from the Internet router Tips to Help Maximize Signal Strength Mount the 1050 Control within 30 feet of wireless router Install 1050 Control with no more than three interior walls between it and the...

Page 5: ...ires extend through the Sub base See Figure 3 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4 of insulation from...

Page 6: ...nel B C R D ODT ODT RS RS R B D R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL INDOOR UNIT 1050 COMFORT CONTROL Heat Pump Multi Stage AC Caution Do not run Outdoor Remote sensor wire...

Page 7: ...unicating Controls w S9V2 Furnace and Comm Outdoor B C R D ODT ODT RS RS R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL S9V2 FURNACE OUTDOOR UNIT 1050 COMFORT CONTROL Caution Do not...

Page 8: ...ower Type Non Variable Variable Select the indoor blower type Constant Torque motors are considered non variable speed All Group 1 settings will be auto configured for fully communicating systems 5 Sy...

Page 9: ...when a voting zone is also requesting capacity Indoor Heating Airflow Offset above and below cooling airflow 1 50 50 0 The air flow offset is the difference between the design cooling air flow CFM per...

Page 10: ...a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A...

Page 11: ...uring 1st stage indoor heat operation 2nd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 Select of cycles per hour during 2nd stage indoor heat operation 3rd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 S...

Page 12: ...lect whether an outdoor temperature override is allowed Outdoor temperature sensor must be connected and enabled to allow this setting to be selected Ventilator Fan Action Ventilate with Blower Ventil...

Page 13: ...r cooling mode with a setpoint change greater than 2 Heating Aggressive Recovery 2 by Outdoor Temperature Enable Disable Select whether the 10 minute staging inhibit is disabled during heating mode wh...

Page 14: ...ower On Delay for variable speed blowers only 1 minute at 50 7 5 minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating...

Page 15: ...Disable Enable Enable defrost heater balance point for W3 only applicable when indoor heat is electric or hydronic Defrost Heater Balance Point W3 Setting 5 F 45 F Select an outdoor temperature to di...

Page 16: ...ler Code When an 1050 Control is connected to Nexia a Dealer Code can be entered to auto populate the dealer s contact information and logo The code is the dealer s registered phone number listed on A...

Page 17: ...Stage Gas Oil Heat LOAD VALUE RANGE COOLING 0 100 Single Stage Compressor 0 200 Two Stage VSPD Compressor A Load Value of 50 represents a request of 50 demand for single stage cooling units Y or 50 de...

Page 18: ...AGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 6 Stage Inhibits When the stage threshold is exceeded a stage inhibit is app...

Page 19: ...igured to only limit Day operation only limit Night operation or limit Day and Night operation to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Q...

Page 20: ...ort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 1050 Control has the ability to control a Whole House Dehumidifier through the normally open dry AUX Contacts on the optional...

Page 21: ...SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lockout Once enabled select an outdoor temperature which disables auxiliary heat anytime the outdoo...

Page 22: ...ilation only The ventilation run time per hour can be adjusted to meet ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the...

Page 23: ...default setting Trane or American Standard manufactured indoor unit with a variable speed blower branded Geothermal package units and oil furnaces are not supported Field supplied 24 volt transformer...

Page 24: ...on for each same mode calling zone follows the calculation below Zone LV System LV damper position The minimum opening position is always 25 to reduce air whistling from a partially opened damper Zone...

Page 25: ...odels If the 1050 Control still calculates excess air then the excess will be relieved following the rules below Relief Strategy 1 Divide the excess air evenly between the zones which are calling but...

Page 26: ...rect compressor speed and associated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must...

Page 27: ...ll is not immediately required Alert messages are not displayed on the home screen NORMAL Functionality may be lost but should recover or the information is for diagnostic purposes performance monitor...

Page 28: ...or speed currently operating Cool Current cooling set point per zone Load Value Numerical value used to determine how much capacity is required to meet set point For more information see 6 2 Load Valu...

Page 29: ...uipment 3 Check repair system Heating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is no...

Page 30: ...time of inactivity Screen Saver mode set to Black which turns of screen back light after a user selected time of inactivity Normal operation User may change screen saver from Black to Indoor Temperat...

Page 31: ...l interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following me...

Page 32: ...D1 5 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Reviews: