American Standard 2TEE3F62A1000A Installer'S Manual Download Page 6

6

18-GE06D1-4

Installer’s Guide

If the unit is not suspended it must be supported
as mentioned above and isolated carefully to pre-
vent sound transmission. Vibration isolators (pur-
chased locally) must be placed under the unit.

f. It is always recommended that an auxiliary drain

pan be installed under a horizontal air handler
(See Condensate Piping) to prevent possible dam-
age to ceilings.

g. Isolate the auxiliary drain pan from the unit or

from the structure.

h. Connect the auxiliary drain line to a separate

drain line (no trap is needed in this line) and ter-
minate according to national and local codes.

i. If a return duct is connected to the air handler, it

must be the same dimensions as the return
opening shown in the outline drawing on page
13.

j. Openings where field wiring enters the

cabinet must be completely sealed. Location
of power entry is shown on the outline drawing.
Use 2.5" clear stickers provided to seal all unused
electrical knockouts. See Figure 8.

k. After ductwork connections are made, seal air-

tight and per Local codes.

HORIZONTAL RIGHT

a. For maximum efficiency and Customer ease of

filter maintenance, it is recommended that a
properly sized remote filter grille be installed
for horizontal applications. Airflow should not ex-
ceed the face velocity of the filter being used.
The factory installed filter should then be
removed from the unit.

b. Unit is shipped from the factory in the upflow or

horizontal right configuration. Unit conversion is
not required.

Remove
and 
Discard

Replace
with 
Narrow
Baffle

FOR MAXIMUM EFFICIENCY ON

HORIZONTAL LEFT,

UPFLOW AND DOWNFLOW

Figure 10

X

X

7/8" GASKET

SCREWS TO 
REMOVE COIL

SCREWS TO 
REMOVE COIL

DISCARD
DRIP TRAY

1/2" GASKET
INSIDE SURFACE
OF BAFFLE

7/8" GASKET

SECT. X-X

(TYP. BOTH SIDES)

FILL WITH SEALANT

WATER

BLOW-OFF

BAFFLES

ATTACH WITH

2 SCREWS

EACH SIDE

WATER

DIVERTER

BAFFLES

(5-ton only)

TRIANGULAR
BAFFLE

FRONT 
SHIELD

DOWNFLOW BAFFLE KIT

Figure 9

Summary of Contents for 2TEE3F62A1000A

Page 1: ...or or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or h...

Page 2: ...aintained as stated on the air handler rating nameplate 10 If the unit is installed without a return air duct ap plicable local codes may limit this air handler to in stallation only in a single story...

Page 3: ...ater or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 12 Make sure there are provisions...

Page 4: ...enough to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same d...

Page 5: ...tab i When supplementary heaters are used accessory subbase TAYBASE102 for 2 4TEE3F62 must be used See Figure 1 j If a return duct is connected to the air handler it must be the same dimensions as th...

Page 6: ...n on the outline drawing Use 2 5 clear stickers provided to seal all unused electrical knockouts See Figure 8 k After ductwork connections are made seal air tight and per Local codes HORIZONTAL RIGHT...

Page 7: ...outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers provided to seal all unused...

Page 8: ...tion is the primary drain See Figure 14 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection Figure 14 BRAZE SHIELD Figure 13 Two secondary drain connections are provided for the differ...

Page 9: ...of the cross brace in the center of the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat...

Page 10: ...size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 18 If the airflow needs to be increased or decreased see the Airflow La...

Page 11: ...GLE SPEED AIR HANDLERS WITH 2 STAGE HEAT PUMP 2 STAGE HEAT AUTOMATIC OR MANUAL CHANGE OVER COMFORT CONTROL From Dwg 21B801073 COMFORT CONTROL AUTO 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER...

Page 12: ...CONTROL MANUAL 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER COOLING O D SECTION SINGLE SPEED COOLING O D SECTION SINGLE SPEED AIR HANDLER WITH 2 STAGE COOLING UNIT 2 STAGE HEAT AUTOMATIC CHANG...

Page 13: ...18 GE06D1 4 13 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3F62...

Page 14: ...14 18 GE06D1 4 Installer s Guide 2 4TEE3F62 AIR HANDLERS H W 21 0 Model No H W 2TEE3F62A1000A 62 75 24 4TEE3D62B1000A 62 75 24...

Page 15: ...ed against the following checklist 1 Make sure power is OFF at power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit...

Page 16: ...ntinuous product and product data improvement it reserves the right to change design and specifications without notice American Standard Inc 6200 Troup Highway Tyler TX 75707 For more information cont...

Reviews: