American Standard 2TEE3F62A1000A Installer'S Manual Download Page 10

10

18-GE06D1-4

Installer’s Guide

COOLING OFF - DELAY OPTIONS

SWITCH SETTINGS

SELECTION

NOMINAL
AIRFLOW

5 - OFF

6 - OFF

NONE

SAME

5 - ON

6 - OFF

1.5 MINUTES

100% *

5 - OFF

6 - ON

3 MINUTES

50%

5 - ON

6 - ON

ENHANCED**

50 - 100%

  * - This setting is equivalent to the BAY24X045 relay benefit.

 ** - This ENHANCED MODE selection provides a ramping up

and ramping down of the blower speed to provide improved
comfort, quietness, and potential energy savings.  The graph
shows the ramping process.

OFF

OFF

50%

80%

100% if necessary

50%

Dehumidify

Fast Coil Cooling
and Heating

Efficiency

7.5

minutes

3

minutes

1

minute

FAN OPERATION (CFM)

COMPRESSOR OPERATION   ON

OFF

as required

J. AIRFLOW ADJUSTMENT

CAUTION

!

Disconnect power to the air handler before changing
dip switch positions. Failure to follow this procedure
may result in equipment damage.

Blower speed changes are made on the ECM Fan Con-
trol mounted on the control box. The ECM Fan Control
controls the variable speed motor.

There is a bank of 8 dip switches (See Figure 17). The
dip switches work in pairs to match the airflow for the
outdoor unit size (tons), cooling airflow adjustment, Fan
off-delay options, and heating airflow adjustment. The
switches appear as shown in Figure 18.

If the airflow needs to be increased or decreased, see
the Airflow Label on the air handler or the Blower Per-
formance Table in the Service Facts.

Information on changing the speed of the blower motor
for your specific outdoor model size is in the Blower
Performance Table.

Be sure to set the airflow for the correct tonnage.
Refer to blower housing for correct setting.

Switches

1 - 4

Cooling Airflow

Switches

5 - 6

Fan Off Delay Options

Switches

7 - 8

Auxiliary Heat

If the optional humidistat is used, remove R-BK jumper
from the low voltage terminal board (not shown) and in-
stall the humidistat between R and BK. (Jumper R to O
for cooling-only/non-heat pump systems with a humidis-
tat.)

INDOOR BLOWER TIMING

The FAN-OFF period is set on the ECM Fan Control
board by dip switches #5 and #6. The blower off-delay
settings are as follows:

IMPORTANT:
Leave dip switch 5 & 6 in the "as-shipped" position
during system start-up and check out. Afterwards, ad-
just as desired.

DIP SWITCHES (AS SHIPPED)

COOLING

HEATING

AIRFLOW

FAN OFF

DELAY

AUXILIARY

HEAT SPEEDS

Figure 18

From Dwg. 800796a

CFM 
SELECTION
LIGHT 

DIP 
SWITCHES

ECM FAN CONTROL

Figure 17

Summary of Contents for 2TEE3F62A1000A

Page 1: ...or or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or h...

Page 2: ...aintained as stated on the air handler rating nameplate 10 If the unit is installed without a return air duct ap plicable local codes may limit this air handler to in stallation only in a single story...

Page 3: ...ater or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 12 Make sure there are provisions...

Page 4: ...enough to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same d...

Page 5: ...tab i When supplementary heaters are used accessory subbase TAYBASE102 for 2 4TEE3F62 must be used See Figure 1 j If a return duct is connected to the air handler it must be the same dimensions as th...

Page 6: ...n on the outline drawing Use 2 5 clear stickers provided to seal all unused electrical knockouts See Figure 8 k After ductwork connections are made seal air tight and per Local codes HORIZONTAL RIGHT...

Page 7: ...outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers provided to seal all unused...

Page 8: ...tion is the primary drain See Figure 14 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection Figure 14 BRAZE SHIELD Figure 13 Two secondary drain connections are provided for the differ...

Page 9: ...of the cross brace in the center of the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat...

Page 10: ...size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 18 If the airflow needs to be increased or decreased see the Airflow La...

Page 11: ...GLE SPEED AIR HANDLERS WITH 2 STAGE HEAT PUMP 2 STAGE HEAT AUTOMATIC OR MANUAL CHANGE OVER COMFORT CONTROL From Dwg 21B801073 COMFORT CONTROL AUTO 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER...

Page 12: ...CONTROL MANUAL 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER COOLING O D SECTION SINGLE SPEED COOLING O D SECTION SINGLE SPEED AIR HANDLER WITH 2 STAGE COOLING UNIT 2 STAGE HEAT AUTOMATIC CHANG...

Page 13: ...18 GE06D1 4 13 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3F62...

Page 14: ...14 18 GE06D1 4 Installer s Guide 2 4TEE3F62 AIR HANDLERS H W 21 0 Model No H W 2TEE3F62A1000A 62 75 24 4TEE3D62B1000A 62 75 24...

Page 15: ...ed against the following checklist 1 Make sure power is OFF at power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit...

Page 16: ...ntinuous product and product data improvement it reserves the right to change design and specifications without notice American Standard Inc 6200 Troup Highway Tyler TX 75707 For more information cont...

Reviews: