American Standard 2TEE3D31A1000A Installer'S Manual Download Page 13

18-GE10D1-5

13

Installer’s Guide

p.

Openings where field wiring enters the
cabinet must be completely sealed.

 Location

of power entry is shown on the outline drawing.
Use 2.5" clear stickers provided to seal all unused
electrical knockouts. See Figure 16.

q. After ductwork connections are made, seal air-

tight and per Local codes.

D. DUCT CONNECTIONS

The supply and return air ducts should be connected to
the unit with flame retardant duct connectors. Convert-
ible duct flanges are provided on the discharge opening
to provide a “flush fit” for 3/4" or 1-1/2" duct board appli-
cations, see the Outline drawing on page 20 for sizes of
the duct connections. After the duct is secured, seal
around the supply duct to prevent air leakage.

NOTE: No sheetmetal screws may be used to attach re-
turn ductwork on the side.

NOTE: On units with sheetmetal returns: Return plenum
must be flanged. Sheetmetal screws must be 1/2" in
length or shorter to ensure no contact with air cleaner
or components. Self-tapping screws are supplied with
the unit in the accessory pack. See Figure 17.

NOTE: If the convertible duct flanges are not used, they
must be removed and discarded for proper airflow.

NOTE: Any duct board return connection can be made
to the sides of the unit using tape or mastic.

E. REFRIGERANT PIPING

IMPORTANT:
Refrigerant piping must be routed to maintain service
access to blower compartment and provide easy re-
moval of filter access panel and COLLECTION CELL.

1.

Refrigerant connections are made outside the
cabinet.

NOTE: TXV bulb MUST be protected (wrap a wet rag
around the suction line between the TXV bulb and the
braze joint) or removed, while brazing the tubing. Over-
heating of the sensing bulb will affect the functional
characteristics and performance of the air handler.

BRAZE SHIELD

Figure 20

NOTE: Penetration around the Refrigerant lines must
be sealed and Electrical inlets must be sealed at both
the low and the high voltage.

2.

Installation of refrigerant lines is covered in the
installation instructions packaged with the outdoor
unit. Evacuation, leak testing and brazing proce-
dures are included in those instructions. Read those
instructions before starting installation of refriger-
ant lines.

F.  BRAZING TO EVAPORATOR SECTION

NOTE: A brazing shield is provided in the information
pack accompanying this unit. This shield fits over the
refrigerant fittings while brazing. Wet the shield before
brazing. See Figure 20.

IMPORTANT:
Do NOT unseal refrigerant tubing until ready to cut and
fit refrigerant lines.

1.

Remove both sealing caps from indoor coil.

2.

Field supplied tubing should be cut squared-off, en-
suring the tube is still round and free of burrs at
the connecting end. Clean the tubing to prevent
contaminants from entering the system.

3.

Run refrigerant tubing into the stub sockets of in-
door unit coil. 

Refrigerant line openings must be

completely sealed.

4.

Braze and evacuate according to indoor and outdoor
installation instructions.

5.

Seal around refrigerant lines.

PAINTED AREAS OF UNIT MUST BE SHIELDED
DURING BRAZING

G. CONDENSATE DRAIN PIPING

NOTE: Make certain that the unit has been installed in a
level position to ensure proper draining.

Summary of Contents for 2TEE3D31A1000A

Page 1: ...r local distributor or the manufacturer as listed on the air handler name plate These Air Handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertibl...

Page 2: ...rs are suitable for installation in a closet alcove or utility room with free non ducted air return using the area space as a return air plenum With ducted supply air if the minimum clearances to comb...

Page 3: ...d to and claims made against the transporta tion company immediately Check to be sure all major components are in the unit Any missing parts should be reported to your supplier at once and replaced wi...

Page 4: ...that do not have a grill or return air duct installation will re quire the use of either BAYPLNM120 TASB215 TASB235 or TASB260 depending on cabinet size TASB accessories can be purchaed from Miami Tec...

Page 5: ...flow Ionizing pins must face downward into the return air stream and electrical contacts must be on the left side of the unit n Reinstall FIELD CHARGER retainer bracket o Install COLLECTION CELL as sh...

Page 6: ...GE10D1 5 Installer s Guide Figure 8 FIELD CHARGER Removal Figure 6 COLLECTION CELL Removal Figure 7 FIELD CHARGER Retainer Bracket Removal Figure 10 Drip Pan Foam Removal Figure 9 Protector Plate Rem...

Page 7: ...e of the drain pan See Figure 14 Fill the bend in the baffle which fits the in ner edge of the drain pan with non acetic acid RTV type adhesive sealant before installing the baffle Ensure sealant is d...

Page 8: ...cal contacts and ac tuator tab are on the right side of the unit t Install filter panel with thumbscrews u Openings where field wiring enters the cabinet must be completely sealed Location of power en...

Page 9: ...15 CAUTION When installing the narrow coil baffle make sure to align the baffle up with the holes so NOT to puncture the coil tubing f The coil is then inserted back into the cabinet on the opposite...

Page 10: ...he front of the unit to re move d Unit is shipped from the factory in the upflow or horizontal right configuration Unit conversion is not required e If the unit is suspended it must be supported from...

Page 11: ...NFLOW UPFLOW Actuator Tab Actuator Tab Electrical Contacts Electrical Contacts Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL Figure 18 COLLECTION...

Page 12: ...ttom side Electrical Contacts on Bottom side Electrical Contacts on Bottom side FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL HORIZONTAL RIGHT Actuator Tab Electrical Contacts Electrical...

Page 13: ...e made outside the cabinet NOTE TXV bulb MUST be protected wrap a wet rag around the suction line between the TXV bulb and the braze joint or removed while brazing the tubing Over heating of the sensi...

Page 14: ...t a clean out tee or cross be installed in the primary drain line for future main tenance See Figures 22 23 4 Do not use reducing fittings in the condensate drain lines 5 Slope the drain lines downwar...

Page 15: ...onnectors are provided for use with supplementary heaters IMPORTANT When supplementary heaters are installed inspect to insure that all packaging material has been removed J AIRFLOW ADJUSTMENT CAUTION...

Page 16: ...shock do not perform any servicing other than that contained in these operating instructions unless you are qualified to do so NOTE System Information Before cleaning the coil or ducts in the air hand...

Page 17: ...Push a block of foam down over the FIELD CHARGER Pin as in Figure 28 6 Rotate the foam block on the FIELD CHARGER Pin See Figure 29 7 Use the foam block to clean the faceplate opening edges 8 Repeat...

Page 18: ...R HANDLER AIR HANDLER 2 STAGE 2 STAGE AIR CONDITIONER AIR CONDITIONER COMFORT CONTROL COMFORT CONTROL 2 STAGE HEAT 2 STAGE HEAT 1 STAGE COOL 1 STAGE COOL VARIABLE SPEED VARIABLE SPEED AIR HANDLER AIR...

Page 19: ...ORT COMFORT CONTROL CONTROL VARIABLE SPEED VARIABLE SPEED AIR HANDLER AIR HANDLER HEAT PUMP HEAT PUMP O D SECTION O D SECTION SINGLE SPEED SINGLE SPEED 2 4TEE3D31 37 40 49 65A AIR HANDLERS WITH SINGLE...

Page 20: ...20 18 GE10D1 5 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3D31 37 40 49 65A1000A From Dwg D802101 Rev 5...

Page 21: ...Installer s Guide H W 21 0 2 4TEE3D31 37 40 49 65A AIR HANDLER DIMENSIONAL DATA Model No H W 2 4TEE3D31A 43 00 21 50 2 4TEE3D37A 45 00 23 50 2 4TEE3D40A 51 75 26 00 2 4TEE3D49A 57 90 26 00 2 4TEE3D65...

Page 22: ...22 18 GE10D1 5 Installer s Guide EXPLODED VIEW From Dwg D802038g05 Rev 11...

Page 23: ...ly for correct requirements per unit nameplate 8 Inform owner of proper procedure for cleaning COLLECTION CELL 9 Energize the system and carefully observe its opera tion make any necessary adjustment...

Page 24: ...TX 75707 For more information contact your local dealer distributor 02 08 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design an...

Reviews: