American Standard 2A7A8 Installer'S Manual Download Page 3

Pub. No. 11-AC14D1-6

PAGE 3

INSTALLER'S GUIDE

8. Close valve on HCFC-22 supply cylinder. Close valves on
manifold gauge set and remove refrigerant charging hoses from
liquid and gas pressure tap ports.

NOTE:  A 3/16" Allen wrench is required to open liquid line
service valve. A 1/4" Open End or Adjustable wrench is
required to open gas line valve. A 3/4" Open End wrench is
required to take off the valve stem cap.

9. The liquid line shut-off valve can now be opened. Remove shut-
off valve cap. Fully insert hex wrench into the stem and back out
counterclockwise until valve stem just touches rolled edge (ap-
proximately five [5] turns) observing 

WARNING

 statement on

page 2. See Figure 3.

10. Replace liquid service pressure tap port cap and valve stem
cap. These caps 

MUST BE REPLACED

 to prevent leaks. Re-

place valve stem and pressure tap cap finger tight, then tighten an
additional 1/6 turn.

11. The gas valve can now be opened. For a ball type gas valve,
open the gas valve by removing the shut-off valve cap and turning
the valve stem 1/4 turn counterclockwise, using 1/4" Open End or
Adjustable wrench. See Figure 4. For brass gas line service valve
opening, follow 9 and 10 above. See Figure 5.

12. The gas valve is now open for refrigerant flow. Replace valve
stem cap to prevent leaks. Again, these caps 

MUST BE RE-

PLACED

 to prevent leaks. Replace valve stem and pressure tap

cap finger tight, then tighten an additional 1/6 turn. See Figure 4.

If refrigerant lines are longer than 15 feet and/or a different
size  than recommended, it will be necessary to adjust system
refrigerant charge upon completion of installation. See the unit
Service Facts.

E. ELECTRICAL CONNECTIONS

▲ 

WARNING:

 When installing or servicing

this equipment, ALWAYS exercise basic safety precau-
tions to avoid the possibility of electric shock.

1. Power wiring and grounding of equipment must comply with
local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration trans-
mission may create a noise problem within the structure.

6. The use of color coded low voltage wire is recommended to
simplify connections between the outdoor unit, the AccuLink™
control and the indoor unit.

Table 1 — NEC Class II Wiring

NOTE:  The maximum total cable length for the entire Comfort
Control communicating system is 500 ft. 18 AWG.

7. Mount the AccuLink™ control in accordance with instruction
included with the AccuLink™ control. Wire per appropriate hookup
diagram (included in these instructions).

F. COMPRESSOR START-UP

After all electrical wiring is complete, SET THE ACCULINK™
CONTROL SWITCH IN THE OFF POSITION SO COMPRES-
SOR WILL NOT RUN, and apply power by closing the system

Use soap bubbles or other leak-checking methods to see that all field
joints are leak-free! If not, 

release pressure

; then repair!

SYSTEM EVACUATION

NOTE:  Since the outdoor unit has a refrigerant charge, the gas and
liquid line valves must remain closed.

1. Upon completion of leak check, evacuate the refrigerant lines and
indoor coil before opening the gas and liquid line valves.

2. Attach appropriate hoses from manifold gauge to gas and
liquid line pressure taps.

NOTE:  Unnecessary switching of hoses can be avoided and
complete evacuation of all lines leading to sealed system can be
accomplished with manifold center hose and connecting branch
hose to a cylinder of HCFC-22 and vacuum pump.

3. Attach center hose of manifold gauges to vacuum pump.

4. Evacuate until the micron gauge reads no higher than
350 microns.

5. Close off valve to vacuum pump and observe the micron gauge.
If gauge pressure rises above 500 microns in one (1) minute, then
evacuation is incomplete or system has a leak.

6. If vacuum gauge does not rise above 500 microns in one (1)
minute, the evacuation should be complete.

7. With vacuum pump and micron gauge blanked off, open valve
on HCFC-22 cylinder and charge refrigerant lines and indoor coil
with vapor to tank pressure of HCFC-22 supply.

NOTE:  DO NOT VENT REFRIGERANT INTO THE
ATMOSPHERE.

CAP

1/4 TURN ONLY
COUNTERCLOCKWISE
FOR FULL OPEN 
POSITION

VALVE STEM

GAS LINE CONNECTION

UNIT SIDE
OF VALVE

PRESSURE TAP PORT

GAS LINE BALL SERVICE VALVE

4

GAS LINE SERVICE VALVE

5

AccuLink™ Control Wiring

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

250 FT

Summary of Contents for 2A7A8

Page 1: ... sion number 3 The support pad must NOT be in direct contact with any structure Unit must be positioned a minimum of 12 from any wall or surrounding shrubbery to insure adequate airflow Clear ance must be provided in front of control box access panels any other side requiring service access to meet National Electrical Code Also the unit location must be far enough away from any structure to preven...

Page 2: ...The liquid line valve is not a back seating valve see WARNING at top of next column WARNING Extreme caution should be ex ercised when opening the Liquid and Gas Line Service Valves Turn valve stem counterclockwise only until the stem contacts the rolled edge See Figures 3 and 5 No torque is required Failure to follow this warning will result in abrupt release of system charge and may result in per...

Page 3: ...al conduit whenever vibration trans mission may create a noise problem within the structure 6 The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit the AccuLink control and the indoor unit Table 1 NEC Class II Wiring NOTE The maximum total cable length for the entire Comfort Control communicating system is 500 ft 18 AWG 7 Mount the AccuLink control...

Page 4: ... R E S T R IC T E D I D A IR F L O W R E F C IR C U IT R E S T R IC T IO N S O D F A N S P E E D S W IT C H TROUBLESHOOTING CHART WHAT TO CHECK B BK Y2 Y1 O R D W1 W3 G W2 B D B R D X2 Y2 Y1 O AccuLink COMFORT CONTROL 24VAC HOT 24VAC Common DATA AccuLink INDOOR UNIT AccuLink OUTDOOR UNIT FIELD WIRING DIAGRAM COMMUNICATING INDOOR UNIT COMMUNICATING OUTDOOR UNIT 6 main disconnect switch This will ac...

Page 5: ... If the system charge is correct the CHARGED LED will turn on and remain on for one 1 hour Once charged the system will exit Charge Assist and control will return to the Comfort Control If the system charge is low the ADD LED will turn on and stay on up to one 1 hour or until enough refrigerant is added to reach the required system charge level and turn on the CHARGED LED When the ADD LED is on th...

Page 6: ...1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 711 28 2A7A8036C 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 711 28 2A7A8048C 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 711 28 2A7A8060C 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 711 28 ...

Page 7: ...Fittings properly insulated 3 Have all Refrigerant Lines been secured and isolated properly 4 Have passages through masonry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain ...

Page 8: ...Pub No 11 AC14D1 6 02 08 Technical Literature Printed in U S A American Standard Heating Air Conditioning Troup Highway Tyler TX 75707 9010 ...

Reviews: