![American Panel IC+ Manual Download Page 5](http://html1.mh-extra.com/html/american-panel/ic/ic_manual_2924966005.webp)
3
Default set points:
High Alarm Trigger Point (AH)
Low Alarm Trigger Point
(AL)
Alarm Delay
(AD)
Cooler
45
o
F
32
o
F
40 Minutes
Freezer
20
o
F
‐25
o
F
Beer Cooler
34
o
F
30
o
F
4
Panic Alarm
Panic alarm is an optional feature on American Panel walk‐ins. If equipped with a Panic alarm, the walk‐in cabinet will have an
illuminated red push button installed on the interior of the cabinet and an alarm buzzer with LED light install on the exterior of the
cabinet.
To trigger the alarm, push the illuminated red button mounted inside the walk‐in cabinet and an audio/visual alarm buzzer will
illuminate and sound the alarm and the IC+ controller will display the panic alarm message. If IC+ is connected to the local Wi‐Fi
network, and setup as such, it will send an alarm message via e‐mail.
To clear the alarm, push and release the panic button to depress and then press the alarm mute button on the IC+.
5
Door Open Alarm
IC+ controllers monitor the status of the door. If the door is not fully closed or if left open for more than the pre‐set time (5 minutes
by default) the IC+ controller will display the alarm message and the onboard buzzer will sound. If IC+ is connected to the local WiFi
network, it will send an alarm message via e‐mail.
Close the door to reset the alarm.
6
Door Frame Heater and Window Heater Control
IC controller switches on the door frame heater and the window heater (if so equipped) when the air temperature drops
below the preset threshold of 45
o
F and then cycles them on and off based on a time cycle. On coolers, by default, the heaters stays
on for 35% of a 6‐minute cycle and then stays off for 65%, the cycle will repeat. The alarm’s set points and delay times are fully
programmable to user’s needs.
Default set points:
Heaters On (Pr)
Heaters Off
Heaters switched on below:
(tP)
Cooler
35% of a 6‐minute cycle
65% of a 6‐minute cycle
45
o
F
Freezer
100% of a 6‐minute cycle
0% of a 6‐minute cycle
Beer Cooler
65% of a 6‐minute cycle
35% of a 6‐minute cycle