SPEEDDOME OPTIMA LT INDOOR CAMERA DOME
8200-0181-01, REV. E
INSTALLATION AND SERVICE GUIDE
5 of 14
SensorNet Line Termination
SensorNet communication protocols require line
termination. Accessing slide switch S1 through the
hole in the top of the dome, terminate the dome
furthest from the video controller or junction box by
moving the switch to the “terminated” position. All
other domes along the line must be unterminated.
Manchester and RS-422 protocols do not require
line termination.
Setting the Camera Address
Accessed through the hole in the top of the dome
are rotary switches SW1, SW2, and SW3 are used
to set the dome address.
Protocol address ranges are as follows:
SensorNet 1-255
Manchester
1-64
RS-422 1-99
For example, for address 107, set SW3 to 1, SW2
to 0 (black dot), and SW1 to 7.
Compatibility with the VM96 Controller
If using a VM96 controller, the controller must be
Version 5.2 or higher.
Power-Up Routine
After power is connected to the dome, the dome
performs a homing routine. During the homing
process, the camera will pan and then either:
•
Go to the start point of the “apple peel” pattern,
or
•
If powered up once before, to the last position in
memory.
Once the camera stops, the camera is online and
is ready to be controlled.
Synchronizing Domes
To prevent picture rolling when switching from
camera to camera, all domes can be synchronized
to the ac source. A V-phase adjustment at the
control console enables the dome to sync to any
line phase.
Save Packaging Material
Should the camera dome need to be sent to a
repair center, use the packaging that the dome was
shipped in.