background image

2 T

OUCH 

T

RACKER

 with Multiplexer

8000-0982-02, Rev. C

AD T

OUCH 

T

RACKER

 16

Installation Instructions

2 1

3

5 4

J-Box #1

EIM #1

DB9 (M)

RJ45

RJ45

P1

P2

P3

P4

P5

P6

P8

UniCard 

 P3

RJ45

RJ45

EIM #2

J1

J2

J3

ASSY 

0301-0340-01 REV-

E1

3 2 1

J1

J2

J3

E1

3 2 1

1-2 TE RMINATE D
2-3 UNT ERMINATE D

3

2 1

 5  2

14  25

DB25 (M)

power

s-vhs

vcr

cam 1

cam 2

cam 3

cam 4

cam 5

cam 6

cam 7

cam 8

cam 9

cam 10

in

out

cam 11

cam 12

cam 13

cam 14

cam 15

cam 16

12 VDC

main monitor

call mon

ASSY 
0301-0340-01 REV-

3 2 1

UniCard 

 P3

2 1

3

5 4

P1

P2

P3

P4

P5

P6

P8

2

1

3

5 4

2

1

3

5 4

J-Box #2

remot e

alarm

Color    Pin  

Function

Orange 1 

Host 

A

Yellow 2 

Host 

B

Orange 3 

Auxiliary 

A

Yellow 4  Auxiliary 

B

J-Box P8

Color    Pin  

Function

Orange 1  SensorNet 

A

White 2 

28Vac

Red 3  Ground

Black 4 

28 

Vac

Yellow 5  SensorNet 

B

J-Box P1-P6

Color    Pin  

Function

Orange 1  SensorNet 

A

Yellow 2  SensorNet 

B

Black 

24 Vac A

Red 4  Ground

White 

24 Vac B

UniCard

P3 Wiring 

Call

OUCH

 T

RACKER

 

Main

OUCH

 T

RACKER

 

EIM DB9

Color Pin 

  Function

Black 5  Ground
Red 2 Transmit

Multiplexer DB25

Color Pin 

  Function

Black 14  Ground
Red 25 Receive

Multiplexer

(with DB25 Connector) 

UNTERMINATED

TERMINATED

24  Vac A

24  Vac B

Ground

24  Vac A

24  Vac B

Ground

NOTE:
AD T

OUCH 

T

RACKER

 16 supports up

to 2 controllers. Terminate E1 on the
EIM that is on an end point of the
SensorNet network.

NOTE:
The maximum combined
SensorNet cable length is
1219m (4000').

Multiplexer with DB25,

 continued