SENSORNET/MANCHESTER DISTRIBUTION PANEL 

8200-0712-01, REV. E 

INSTALLATION GUIDE 

1 of 5

 

SensorNet/Manchester 
Distribution Panel 

Installation Guide 

Figure 1. SensorNet/Manchester Distribution 

Panel 

 

ADACSNETD/ADACSNETDP 

About this Guide 

This installation guide explains how to install the 
SensorNet/Manchester Distribution Panel. 

If you need assistance... 

Contact your Sales Representative. 

Warning and Cautions 

WARNING: 

RISK OF ELECTRIC 

SHOCK! Disconnect AC power to 
the panel. 

CAUTION-Electrostatic Sensitive 
Device:

 Follow proper handling 

procedures to prevent component failure. 

 

© 2008 Sensormatic Electronics Corp. 

About the Product 

The SensorNet/Manchester Distribution Panel 
provides signal amplification for the SensorNet and 
Manchester multi-point dome control 
communications and has 16 secondary device 
ports (two connectors per port) to accommodate 
home-run dome wiring or multiple daisy-chained 
connections to domes, J-boxes, or other 
distribution panels. 

Each of the ports has an LED that indicates data is 
being received. Since Manchester communication 
is simplex (one-way) communication, received data 
is never present on the 16 secondary device ports; 
therefore, the LEDs for ports 1, 2, and 3 will be 
constantly ON with ports 4 through 16 OFF to 
indicate the unit is in Manchester mode. 

Figure 2. Distribution Panel components 

 

 

 

 

 

 

 

Note:

 The Noise Indicator may signal improper line 

termination, line noise, packets cut short, or other 
false carrier detection situations whenever a 
too-short packet fragment is detected. 

 

Output Data Connectors,

LEDS, and Switches 

Power 
Connecto

12–30V AC/DC

Noise Indicator 

Host Connectors, 
LEDs, and Switches 

SW1 DIP Switches 

 

Summary of Contents for ADACSNETD

Page 1: ... Manchester multi point dome control communications and has 16 secondary device ports two connectors per port to accommodate home run dome wiring or multiple daisy chained connections to domes J boxes or other distribution panels Each of the ports has an LED that indicates data is being received Since Manchester communication is simplex one way communication received data is never present on the 1...

Page 2: ...o ground Ensure metal to metal contact Configuration Considerations SW1 Switch Settings Pos 0 Setting 1 Setting 1 50µs Turnaround Time 1 50µs Turnaround Time 1 2 Manchester SensorNet 3 Not used Not used 4 Not used Not used 5 Not used Not used 6 Not used Not used 7 LED Test Mode 2 Normal Operation 8 State Machine Test Mode 3 Normal Operation Notes 1 Turnaround time Normally SW1 position 1 is set to...

Page 3: ... equipment Input frequency 47 63Hz Allowable drop out 150ms Power connector pin assignments Pin Label Notes 1 and 3 12V 30V AC DC Connect 12 30V AC or DC power to these pins in any polarity 2 Ground Used for surge protection and data line shields Surge Protection SensorNet Manchester Ports Transient Voltage Suppressors TVS Break Down Voltage 7 6 9 3Vdc Peak Current 40A Capacitance 2000pf 1kHz Gas ...

Page 4: ...hield not used Pin 1 S Black wire Pin 2 S White wire Pin 3 Ground Shield used Terminating Resistor 120Ω switch selectable 120Ω switch selectable Physical Layer RS 485 transformer isolated 2 wire RS 485 transformer isolated 2 wire Data Encoding FM 0 Manchester Link Layer Framing SDLC HDLC Proprietary Link Layer Channel Bi directional half duplex Simplex Collision Avoidance Polling by primary host c...

Page 5: ...de the very best in customer service and support Dealers should contact American Dynamics at 800 507 6268 or 561 912 6259 or on the web at www americandynamics net WARRANTY DISCLAIMER Sensormatic Electronics Corporation makes no representation or warranty with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose N...