H. STEAM INFORMATION
It is your responsibility to have
ALL
steam plumbing connections made by a qualified professional to assure that
the installation is adequate and conforms to local and state regulations or codes.
IMPORTANT:
Failure to comply with the requirements stipulated in this manual can result in
component failure, which will VOID THE WARRANTY.
NOTE:
The dryer is manufactured with a pneumatic (piston) damper system, which requires an
external supply of clean, dry, and regulated air (80 PSI +/- 10 PSI [5.51 bars +/- 0.68 bars]).
Refer to
Steam Damper Air System Connections
,
Section H
,
item 4
.
1. Steam Coil PH Level
The normal PH level for copper type steam coils
must be
maintained between a value of 8.5 to 9.5. For
steel type steam coils the PH level
must be
maintained between a value of 9.5 to 10.5. These limits are
set to limit the acid attack of the steam coils.
IMPORTANT:
Coil failure due to improper PH level will VOID THE WARRANTY.
2. Steam Requirements, High Pressure
a. Inlet ----1-1/4” supply line connection --- qty. one (1) at top manifold.
b. Return --1-1/4” return line connection --- qty. one (1) at bottom manifold.
3. Installation Instructions
To insure that an adequate supply of steam is provided, be sure that the steam supply and steam return lines
are sized and laid out as stipulated in this manual. Inadequate steam supply and steam return lines are sized
and laid out as stipulated in this manual. Inadequate steam supply and steam return lines or improper steam
plumbing will result in poor performance and can cause component failure. Clean, dry, and regulated steam
must be
provided to the dryer.
IMPORTANT:
Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.
Operating Steam Pressure
Maximum
125 psig
862.84 kPa
Minimum
100 psig
689.47 kPa
Heat Input (Normal Load)
13 Bhp
Consumption (Approximate)
450 lbs/hr
202.2 kg/hr
Shaded areas are stated in metric equivalents