13
IMPORTANT
: Even though a minimum of only 12-inches is required, 18-inches or more is suggested.
The additional clearance is advantageous for ease of installation and service.
IMPORTANT
: When fire sprinkler systems are located above the dryers, a minimum of 18-inches
above the dryer console (module) is required. Dryers may be positioned side wall
to side wall however, a 1/16" minimum allowance is required between dryers (or wall)
for ease of installation and maintenance. Allowances
must be
made for the opening
and closings of the control door and the lint door.
D. FRESH AIR SUPPLY
When the dryer is operating, it draws in room air, heats it, passes this air through the basket (tumbler), and
exhausts it out of the building. Therefore, the room air
must be
continually replenished from the outdoors. If the
make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail
switch "fluttering" problems may result, as well as premature motor failure from overheating.
Air supply (make-up air)
must be
given careful consideration to assure proper performance of each dryer. An
unrestricted source of air is necessary for each dryer. An air flow of 1,200 cfm (cubic feet per minute)
must be
supplied to each gas and electric dryer and 1,350 cfm (cubic feet per minute)
must be
supplied to each steam
dryer. As a general rule, an unrestricted air entrance from the outdoors (atmosphere) of a minimum of 1-1/2
square feet is required for each dryer.