AIR FLOW MEASURING KIT
The American ALDES
air
fl
ow measuring kit is designed to measure
air
fl
ow accurately in ducting. Utilizing the Ampli
fl
ow sensor by Nailor-
Hart Industries, it is three times as sensitive as a Pitot tube, allowing
the measurement of very low velocities. The design also averages the
variations in velocity pressure across the diameter of the duct, to provide
a mean air
fl
ow reading.
The Air
fl
ow Measuring
Kit is comprised of the
following items:
Ampli
fl
ow sensors for 6”
•
and 8” ducting.
Dwyer Magnehelic
•
pressure gauge, 0-0.25 in.
w.g. range.
Flexible tubing to connect
•
pressure gauge to sensors
Air
fl
ow Table to convert
•
pressure readings to
air
fl
ow in cfm.
FEATURES:
Ampli
fl
ow
®
sensor*:
Multi-point readings eliminate need for pitot tube traverses.
•
Adaptable to round, oval or rectangular duct.
•
Accurate low velocity readings—provides 3 times the pressure reading
•
of a Pitot tube at the same velocity.
Dwyer Magnehelic
®
—an industry standard in differential pressure
measurement.
Accuracy of measurement: Plus or minus 4% of full scale at 70 F.
•
Can accept overpressure up to 15 PSI.
•
Comes with mounting stand, 1/8 tubing connectors, probe for static
•
pressure measurements, plastic storage case.
Dual scale readings for pressure (in. w.g.) and velocity (FPM) when
•
used with a Pitot tube.
BALANCING PROCEDURE
Prior to balancing, make sure that:
All sealing of the ductwork system
•
has been completed.
All of the HRV’s components are in
•
place and functioning properly.
Balancing dampers are fully open.
•
Adjustment of air
fl
ows at the
•
individual grilles should be done
prior to balancing the total supply
and exhaust air
fl
ows. A smoke
pencil maybe used to indicate
relative air
fl
ows at the supply or
exhaust grilles.
Set the pressure gauge on a level
1.
surface, near the duct location where
the air
fl
ow is to be measured. Check
to see it reads zero, with no air
fl
ow
across the sensor. If not, use a small
screwdriver to adjust the meter. See
the Dwyer instructions packaged
with the Magnehelic gauge.
Insert the Ampli
fl
ow sensor into
2.
a straight section of duct, with the
arrow pointing in the direction
of the air
fl
ow. To avoid air
fl
ow
turbulence and incorrect readings,
the
fl
ow sensor should be located
at least three (3) diameters
downstream from elbow, balancing damper, etc. If
fl
exible ducting
is used, it may be advisable to insert the Ampli
fl
ow sensor into a
short collar of metal duct.
Be sure to connect the low and high pressure taps on the gauge to the
3.
corresponding taps on the Ampli
fl
ow sensors.
Turn the unit to HIGH speed. (Note: it may be necessary to reduce
4.
the speed if the pressure gauge is driven off scale. No damage
will result, the gauge is capable of 15 PSI, much higher than the
maximum scale reading.)
Find the air
fl
ow from the column matching the duct diameter and the
5.
pressure reading on the upper scale of the gauge.
After taking readings of both the stale air to the HRV/ERV duct and
6.
the fresh air to the house duct, the duct with the lower cfm should
be left alone, while the duct with the higher reading should be
dampered back to match the lower reading.
Remove the
fl
ow sensor from the duct and seal the holes with
7.
approved duct tape. The sensor may be left in place to check air
fl
ows
later.
Return the unit to appropriate fan speed for normal operation. Note:
8.
Air
fl
ows may be measured in smaller diameter ducts by taping over
the sensor holes on the tubing that are exposed outside the duct.
Failure to close them will result in low readings.
*Ampli ow
®
is a Registered Trademark of Nailor-Hart Industries.
Magnehelic
®
is a Registered Trademark of Dwyer Instruments,
Inc.
Place sensing probe a minimum of 3
diameters downstream from blower, elbows,
or dampers.
NOTE: Duct connections may vary,
depending on model.
AIRFLOW TABLE FOR AMPLIFLOW SENSOR
Delta
P In.
W.G.
Velocity
FPM
CFM 4”
Diam.
CFM 5”
Diam.
CFM 6”
Diam.
CFM 7”
Diam.
0.005
150
13
20
29
40
0.010
212
19
29
42
57
0.015
260
23
35
51
69
0.020
300
26
41
59
80
0.025
335
29
46
66
90
0.030
367
32
50
72
98
0.035
397
35
54
78
106
0.040
424
37
58
83
113
0.045
450
39
61
88
120
0.050
474
41
65
93
127
0.055
497
43
68
98
133
0.060
520
45
71
102
139
0.065
541
47
74
106
145
0.070
561
49
77
110
150
0.075
581
51
79
114
155
0.080
600
52
82
118
160
0.085
618
54
84
121
165
0.090
636
56
87
125
170
0.095
654
57
89
128
175
0.100
671
59
91
132
179
0.105
687
60
94
135
184
0.110
704
61
96
138
188
0.115
719
63
98
141
192
0.120
735
64
100
144
196
0.125
750
65
102
147
200
0.130
765
67
104
150
204
Delta
P In.
W.G.
Velocity
FPM
CFM 4”
Diam.
CFM 5”
Diam.
CFM 6”
Diam.
CFM 7”
Diam.
0.135
779
68
106
153
208
0.140
794
69
108
156
212
0.145
808
70
110
159
216
0.150
822
72
112
161
220
0.155
835
73
114
164
223
0.160
849
74
116
167
227
0.165
862
75
117
169
230
0.170
875
76
119
172
234
0.175
887
77
121
174
237
0.180
900
79
123
177
241
0.185
912
80
124
179
244
0.190
925
81
126
182
247
0.195
937
82
128
184
250
0.200
949
83
129
186
254
0.205
960
84
131
189
257
0.210
972
85
133
191
260
0.215
984
86
134
193
263
0.220
995
87
136
195
266
0.225
1006
88
137
198
269
0.230
1017
89
139
200
272
0.235
1028
90
140
202
275
0.240
1039
91
142
204
278
0.245
1050
92
143
206
281
0.250
1061
93
145
208
283
Ampli
fl
ow
Sensor
Ampli
fl
ow
Sensor
28
Summary of Contents for Heat Recovery Ventilator HRV 120SRD
Page 35: ......