background image

 

PN 16303

 

04/2020

 

12. Replace the extinguisher on the wall hanger or in the vehicle bracket making sure that it fits the bracket 

properly and the bracket is securely attached –

 

replace the bracket if necessary.

 

RECHARGE

 

WARNING:

 

 

a.

 

Before attempting to disassemble, be sure the extinguisher is completely depressurized.

 

b.

 

Use a regulated nitrogen pressurizing source. Set the regulator no more than 125 psi (862 kPa).

 

c.

 

Check  and  calibrate  regulator  gauge  at  frequent  intervals.  The  regulator  gauge  shall  be  used  to 

determine when the intended charging pressure has been reached. Do not use the extinguisher for 

this purpose.

 

d.

 

Never  leave an extinguisher  connected to a regulator  of a high

-

pressure source for an extended 

period  of  time.  A  defective  regulator  could  cause  the  cylinder  to  rupture  due  to  excessive 

pressure.

 

RECHARGING PROCEDURE

 

1.

 

Perform steps 1 through 10 of the "Maintenance

-

Service Procedure" section.

 

2.

 

Discharge all remaining pressure and contents, making sure that there is no remaining pressure. Do not 

top off or reuse water.

 

3.

 

Remove  the  valve  assembly  and  disassemble  by  removing  downtube  assembly  (use  a  wrench  on  the 

brass retainer, not the plastic tube), spring, and valve stem assembly. Remove the collar O

-

ring from the 

valve and plastic fill tube from the cylinder.

 

4.

 

Thoroughly clean all parts of the disassembled valve with a soft bristle brush or soft cloth. Blow the valve 

out with air or nitrogen. Inspect the spring and downtube assembly, and replace parts if worn or damaged. 

Replace the valve stem and collar O

-

ring. Lubricate the collar O

-

ring and small O

-

ring on the valve stem 

with  V

-

711  (do  not  lubricate  the  valve  stem  seal).  Inspect  the  downtube.If  it  is  cracked  or  deformed 

replace with proper downtube. Inspect downtube O

-

ring, replace if necessary.

 

5.

 

Rinse the cylinder with clean water and inspect the interior following CGA Visual Inspection Standard C

-

6.

 

6.

 

Firmly replace the plastic fill tube and fill cylinder with DE

-

IONIZED WATER to the bottom of the fill tube. 

(Model B270 1.8 U.S. gals./6.81 liters Amerex Charge 670)(Model B272 2

-

½ U.S. gals/9½ liters Amerex 

Charge 671).

 

NOTE:  THE USE OF DE

-

IONIZED WATER CONFORMING TO NFPA 10 IS REQUIRED.

 

7.  Install a "Verification of Service" collar around neck of cylinder. Install valve assembly to the cylinder and 

properly align.

 

CAUTION:  HAND  TIGHTEN  THE  VALVE  COLLAR  NUT  100

-

125  IN  LBS.  MAX  (1.15

-

1.44  KG/M. 

OVER TIGHTENING WITH A WRENCH WILL DAMAGE THE VALVE.

 

8.    Install  a  PN  09492  Fill  Adapter  (High  Performance)  to  the  male  valve  outlet  (where the  hose  assembly 

attached) and pressurize with nitrogen to 100 psi (690 kPa).The pressure regulator shall be set to no more 

than 125 psi (862 kPa). Remove Fill Adapter.

 

CAUTION:  DO NOT USE COMPRESSED AIR TO PRESSURIZE THIS EXTINGUISHER.

 

9.

 

Check  the  collar,  gauge,  cylinder  welds,  and  valve  orifice  for  leaks  using  a  leak  detection  fluid  or  a 

solution of soapy water. Remove leak detection fluid from the valve assembly by blowing out with air and 

wipe exterior of the extinguisher to dry.

 

10.

 

Install house and wand assembly into the operating valve.

 

NOTE:  CAREFULLY  POSITION  THE  HOSE  TO  A  NATURAL  ANGLE  BEFORE  TIGHTENING  THE 

HOSE  FEMALE  SWIVEL  NUT.  TORQUE  SWIVEL  NUT  LIGHTLY  USING  15/16"  WRENCH. 

INSTALL IN HOSE CLIPS.

 

Summary of Contents for B270

Page 1: ...S D FIRES OR ANY FLAMMABLES THAT WILL REACT WITH WATER PROTECT FROM FREEZING OWNER S SERVICE MANUAL INSTALLATION OPERATING SERVICING INSTRUCTIONS MANUAL PN 16303 WATER MIST PORTABLE EXTINGUISHERS MODEL B270 B272 AMEREX CORPORATION DOES NOT SERVICE MAINTAIN OR RECHARGE FIRE EXTINGUISHERS THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION MAINTENANCE AND RECH...

Page 2: ...her for damaged missing or substitute parts Only factory replacement parts are approved for use on Amerex fire extinguishers 3 Weigh the extinguisher and compare with weight printed in the Maintenance section on the nameplate label Recharge extinguisher if weight is not within indicated allowable tolerances 4 Check the date of manufacture printed on the extinguisher label nameplate or on the agent...

Page 3: ...the valve stem and collar O ring Lubricate the collar O ring and small O ring on the valve stem with V 711 do not lubricate the valve stem seal Inspect the downtube If it is cracked or deformed replace with proper downtube Inspect downtube O ring replace if necessary 5 Rinse the cylinder with clean water and inspect the interior following CGA Visual Inspection Standard C 6 6 Firmly replace the pla...

Page 4: ...an all valve parts after depressurization and valve removal PROBLEM CORRECTIVE ACTION 1 Leak at collar O ring Remove valve assembly clean collar knurled nut thoroughly 2 Leak through valve Check valve stem seating area for scratches or foreign matter Clean seating area with a tooth brush and soft cloth Install new valve stem assembly 3 Leak around gauge Remove gauge clean threads and reinstall usi...