background image

 

PN 05606

 

04/2020

 

1.  Move the extinguisher to within approximately 30 feet (9 m) for 50 lb., 40 feet (12 m) for 150 lb. of the 

fire site. Keep the extinguisher upright.

 

NOTE: The model 600 extinguisher may be operated in either the vertical or reclined position; 

however, it will discharge more agent in the vertical position. The model 695 MUST be 

operated in the UPRIGHT position.

 

2. 

Twist and pull the pull pin. Open cylinder discharge valve by rotating (pulling) the valve lever toward 
the hose 90°. The hose is now pressurized with chemical.

 

3. 

Pull discharge nozzle, with lever in the closed position, from the mount and extend the hose from the 

storage rack.

 

4. 

Stand back 15 feet (4 m) to 30 feet (10 m) from the fire, and aim the nozzle at the base of flames 

nearest you. Open nozzle by pulling handle toward you (be prepared for a discharge recoil by holding 

the nozzle firmly).

 

5. 

Sweep side to side across the base of the fire and past both edges. Progressively follow up until the 

fire is extinguished. Work the fire away from you while being alert for flashbacks. Move closer as the 

fire is extinguished but not so close as to scatter or splash the burning materials.

 

6. 

When the fire is out, push the nozzle lever forward to the closed position.

 

7.

 

Evacuate and ventilate the area immediately after extinguishing the fire. The fumes and smoke from 

any fire may be hazardous and can be deadly.

 

WARNING: SYMPTOMS OF OVER

-

EXPOSSURE TO PURE HALON ARE DIZZINESS, IMPAIRED 

COORDINATION, AND REDUCED MENTAL ACUITY. PERSONS SUFFERING FROM 

OVER

-

EXPOSURE  SHALL  BE  IMMEDIATELY  REMOVED  TO  FRESH  AIR.  IF 

UNCONSCIOUS,  GIVE  RESPIRATION  AND  OBTAIN  MEDICAL  AID.  USE  OF 

ADRENALIN OR SIMILAR DRUGS SHALL BE AVOIDED.

 

 
 
 
 
 

SHUTDOWN

 

CAUTION:  BEFORE  PERFORMING  THE  SHUTDOWN  PROCEDURE  AND  PREPARING 

TO  MOVE  THE  EXTINGUISHER  TO  THE  RECHARGE  LOCATION, 

DETERMINATION  MUST  BE  MADE  THAT  THE  FIRE  IS  COMPLETELY 

EXTINGUISHED AND THERE IS NO DANGER OF A FLASHBACK.

 

1.

 

Rotate cylinder discharge valve lever 90° to the closed position. Install pull pin to prevent accidental 
actuation while transporting to recharge location.

 

2.

 

Remove residual agent from hose.

 

CAUTION: Do not leave Halon 1211 in the hose as over

-

pressurization and deterioration 

of the hose may occur.

 

3. 

Return the extinguisher to the upright position.

 

4.

 

Coil  the  hose  onto  the  storage  rack,  and  position  the  nozzle  into  the  mount  in  preparation  for 

transport to the recharge location.

 

 

 

MODEL 695

 

MODEL 600

 

Discharge Time (approx.)

 

35 seconds

 

43 seconds

 

Range (Agent Throw)

 

25 to 35 feet

 

35 to 40 feet

 

Hose Length

 

25 feet

 

50 feet

 

Summary of Contents for 600

Page 1: ...BE DUPLICATED USED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESS WRITTEN CONSENT OF AMEREX CORPORATION NOTES 1 THIS COVERSHEET FOR INFORMATIONAL PURPOSES ONLY DO NOT PRINT THIS PAGE IN MANUAL 2 DESCRIPTION MANUAL OWNER S SERVICE FOR 50 150 HALON 1211 WHEELED EXTINGUISHERS 3 ACTUAL PRINTED MATERIAL TO CONSIST OF ATTACHED 4 OVERALL SIZE OF PRINTED DOCUMENT PAGES 8 1 2 X 11 ON 20 LB PAPER 5 PRINTED MATE...

Page 2: ...N OPERATING SERVICING INSTRUCTIONS MANUAL PN 05606 WHEELED STORED PRESSURE HALON 1211 EXTINGUISHERS MODELS 600 695 AMEREX CORPORATION DOES NOT SERVICE MAINTAIN OR RECHARGE FIRE EXTINGUISHERS THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY NO INSTRUCTION MANUAL CAN ANTICIPATE ALL POSSIBLE MALFUNCT...

Page 3: ... gauge The pressure gauge shall be in the green zone 200 10 psi range the method used to determine proper agent fill is by weighing the extinguisher and comparing to weight recorded when initially installed or when previously recharged NOTE Halon 1211 is a liquefied gas that generates its own vapor pressure Temperature can affect the pressure gauge reading Normal properly charged markings are corr...

Page 4: ...he fire is out push the nozzle lever forward to the closed position 7 Evacuate and ventilate the area immediately after extinguishing the fire The fumes and smoke from any fire may be hazardous and can be deadly WARNING SYMPTOMS OF OVER EXPOSSURE TO PURE HALON ARE DIZZINESS IMPAIRED COORDINATION AND REDUCED MENTAL ACUITY PERSONS SUFFERING FROM OVER EXPOSURE SHALL BE IMMEDIATELY REMOVED TO FRESH AI...

Page 5: ...sting or internal maintenance is required MAINTENANCE PROCEDURE 1 Clean extinguisher to remove dirt grease or foreign material Check to make sure that the instruction pictogram is securely fastened and legible Inspect the cylinder for corrosion abrasion dents or weld damage If any damage is found and you doubt the integrity of the cylinder hydrostatically test to factory test pressure using the pr...

Page 6: ...Properly coil the hose on the rack and install the nozzle with the lever in a closed position on the mount NOTE When assembling the hose to the agent cylinder or nozzle to the hose tighten the coupling turn after contacting the hose gasket 12 Inspect the wheels on to insure they rotate freely Lubricate as required 13 Check carriage assembly for loose nuts bolts frame distortion or damage Check wel...

Page 7: ...lean the O ring seating groove in the cylinder neck If any rust is evident remove by using a fine emery cloth 200 grit Clean the surface and lubricate the entire sealing area with a thin film of V 711 or equivalent Install the valve assembly in extinguisher cylinder Hand tighten firmly 8 Use the Getz HR 1 system to purge the residual air from the extinguisher cylinder RECHARGE NFPA 10 is the repla...

Page 8: ... depressurized Leakage repairs will require depressurization and removal of the valve assembly Use Getz HR 1 or other approved recharge recovery system to depressurize extinguisher PROBLEM CORRECTIVE ACTION 1 Pressure gauge reads high or low Temperature may have affected pressure see temperature pressure relationship chart 2 Leak through valve Remove valve assembly downtube spring and valve stem a...

Reviews: