AI
SERIES STEAM BOILER WITH T100 CONTROL
INSTALLATION INSTRUCTIONS
4211-195 05-22-12
Page 7
For service or assistance contact Amerec Technical Support between 7:00 am and 5:00 pm Paci
fi
c time at
1-800-363-0251
AMEREC AI BOILER RATINGS
CATALOG #
UL-MODEL #
WATTS
VOLTS PHASE AMPS
MAX ROOM SIZE
CU FT [CU M]
STEAM
LB-HOUR
DIMENSIONS
L W H
AI12
12-208
12 000
208
1
59
500
[14]
36
17
1
/
2
x 20
3
/
4
x 23
1
/
4
[444.5 x 527.0 x 590.6]
3
34
12-240
240
1
51
3
30
12-415
415
3
18
12-480
480
3
15
AI18
18-208
18 000
208
1
88
750
[21]
54
3
51
18-240
240
1
76
3
44
18-415
415
3
26
18-480
480
3
22
AI24
24-208
24 000
208
1
116
1000
[28]
73
3
68
24-240
240
1
101
3
59
24-415
415
3
34
24-480
480
3
29
AI30
30-208
30 000
208
3
84
1250
[35]
91
17
1
/
2
x 27 x 24
[444.5 x 685.8 x 609.6]
30-240
240
73
30-415
415
43
30-480
480
36
AI36
36-208
36 000
208
3
101
1500
[43]
109
36-240
240
88
415
51
36-480
480
43
AI42
42-208
42 000
208
3
118
1750
[50]
127
42-240
240
102
415
59
42-480
480
51
AI48
48-240
48 000
240
3
117
2000
[57]
145
415
68
48-480
480
58
Notes
:
• All models use 120VAC 60 Hz or 240V~ 50 Hz control circuits.
• 208V, 240V and 400V models supply 120V (OR 240V to control circuit internally, 480V models require a separate 120V service.
o For 208V, 240V and 415V models, run power wires + Ground and a 14AWG Neutral for controls.
o For 480VAC units, run 3 power wires + Ground and run a 120V service for the control circuit.
• All models: no internal heating circuit fuses are needed; a panel mounted 3A fuse provided for the control circuit
• Use only copper wire, rated 75°C or better.
• Install all wiring per local and national codes.