2

*

Selection of installation positions for outdoor unit

*

To install the outdoor unit at the places which can stand the load of the machine weight and will

 not cause big vibrations and noises;

To install the unit at the places not to be exposed to rain or direct sunshine, and the places with

 good ventilation;

The noises generated from the unit will not affect the neighboring places;

Do not install the unit on non-metal frame;

Not to install the unit at the places where there might occur the generation, inflow, stay or 

leakage of inflammable gases;

Pay attention to the drainage of the condensed water from the base plate during operations;

To avoid the air outlet being directly against the wind.

Detailed space requirements around the outdoor unit

1. When there are obstacles above 

the unit

2. When the front (air outlet) is open

3. When there are obstacles only in 

the front (air outlet)

4. When there are obstacles at the front and rear sides.

5. When there are obstacles all around 

the unit on four sides.

Although the top side is open, the 

installation is not to be done if there 

are obstacles all around.

Space for maintenance

Shown as in the following figure. Keep 

the maintenance space in front of the 

unit.

500mm(1'8") min

100mm(4") min

500mm(1'8") min

200mm(8") min

500mm(1'8") min

  500mm
(1'8")min

200mm
(8")min

Space for maintenance

At least two sides should 

be kept open.

200mm(8") min

300mm(1') min

1000mm(3'4") min

100mm(4") min

INSTALLATION & REPAIR GUIDE

Split Wall-Mounted air conditioner

Summary of Contents for UCHW-H09AF2

Page 1: ......

Page 2: ......

Page 3: ...he unit during operation the fire alarm device might be erroneously triggered by the warm air from the unit Above 100mm 4 Left side 150mm 6 and above Right side 150mm 6 and above Ceiling Wall hanging...

Page 4: ...ions To avoid the air outlet being directly against the wind Detailed space requirements around the outdoor unit 1 When there are obstacles above the unit 2 When the front air outlet is open 3 When th...

Page 5: ...rfaces if the humidity is very high 4 Installation of indoor unit Pass the connection wires connecting pipelines and drain pipe through the wall hole Hang the indoor unit on the hooks at the top of th...

Page 6: ...ity center of the unit is not at the installation center special caution should be taken when using hoisting cables to lift it up During shipping the outdoor unit must not be slanted to over 45 degree...

Page 7: ...9 000 BTU 12 000 BTU MODEL 9 000 BTU 12 000 BTU MODEL 18 000 BTU 24 000 BTU MODEL...

Page 8: ...INSTALLATION REPAIR GUIDE Split Wall Mounted air conditioner...

Page 9: ...is suitable for non quick coupler No dust foreign articles air or moisture should be allowed to enter the air conditioning system Careful attention should be paid when pipeline connection for outdoor...

Page 10: ...Air Purging Air purging With Vacuum Pump 8...

Page 11: ......

Page 12: ...10...

Page 13: ...wall hole to prevent rain water from entering Finishing touches Connect to the power source check if the function selection keys on the remote controller are working properly Check if the room tempera...

Page 14: ...on or increased operation noise Do not leave obstacles near the outlet and inlet If irregular sound is heard during operation consult with your distributor Inspection and Maintenance Note Above self c...

Page 15: ......

Page 16: ......

Reviews: