TASK 4 (EtherNet/IP Option)
I
MPLICIT
C
OMMUNICATIONS
W
ITHOUT
AN
EDS
4.1 Host System Configuration
RSLogix 5000 is used to configure both the ControlLogix and CompactLogix platforms. When using these plat-
forms, you have the option of using a separate Ethernet Bridge module or an Ethernet port built into the processor.
If the Ethernet port is built into processor, the only step you have to take before adding the RBE2-8 is to create a
new project with the correct processor or modify an existing project. Once this is done, the Ethernet port will auto-
matically appear in the Project Tree. If you are using an Ethernet bridge module, you will have to add it to the I/O
Configuration tree before adding the driver to your project.
Refer to your Rockwell Automation documentation if you need instructions for configuring the ethernet port.
4.2 Add the RBE2-8
You can add the RBE2-8 to the project once the Ethernet port (built-in or bridge module) is configured.
1) Right click on the Ethernet port and then click on “New Module...” in the pop-up menu.
Figure T4.1 Adding an AMCI RBE2-8
An AMCI RBE2-8 requires a host controller to issue output updates to it. This
chapter tells you how to configure implicit connections in EtherNet/IP systems
that do not use EDS files. If you instead wish to use explicit messaging, refer to
the next chapter for information on using message instructions.
Rockwell Automation’s RSLogix 5000 version 20 software is used for the example
installation in this chapter.
Summary of Contents for RBE2-8
Page 14: ...RBE2 8 INTRODUCTION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 14 Notes ...
Page 30: ...PROTOCOL SPECIFIC INFORMATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 30 Notes ...
Page 48: ...MODBUS TCP CONFIGURATION RBE2 8 User Manual ADVANCED MICRO CONTROLS INC 48 Notes ...
Page 54: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC ...