20 Gear Drive, Plymouth Ind. Park, Terryville, CT 06786
Tel: (860) 585-1254 Fax: (860) 584-1973 http://www.amci.com
59
EtherNet/IP Task
E
THER
N
ET
/IP E
XPLICIT
M
ESSAGING
6.1 Custom Assembly Instances
Each NR60E2 supports two custom assemblies to read data from the unit. Each NR60E2 also supports six
custom assemblies to write configuration data or commands to the unit.
In addition to the custom assemblies, the NR60E2 also implements the Position Sensor Object as defined in
revision 2 of the CIP specification. Explicit messaging can be used to access all of the attributes defined by
the Position Sensor Object. Additional information on the Position Sensor Object can be found in the
section, starting on page 67.
6.1.1 Read Assemblies
Two custom assemblies are available to read data from the NR60E2.
Table T6.1 Read Message Instruction Attributes
6.1.2 Write Assemblies
Six custom assemblies are available to write data to the NR60E2.
Table T6.2 Write Message Instruction Attributes
† Restore Factory Defaults does not affect the IP addressing information. Parameter values are restored to RAM. A
separate Save to Flash command is required to save the factory defaults to flash memory.
All controllers that support EtherNet/IP support explicit messaging. When using
explicit messaging, Message Instructions must be added to your program to com-
municate with the NR60E2. Explicit messaging must be used to configure the
device or preset the position value.
Rockwell Automation controllers which are programmed with the RSLogix 500
software only support explicit messaging. A MicroLogix 1100 will be used as an
example in this chapter. In Rockwell Automation systems, RSLogix 500 version
8.0 or above is required to configure Message Instructions to communicate with
an EtherNet/IP device. Message Instructions do not work correctly in version 10 of
RSLogix 500.
Service Type
Service
Code
(hex)
Class
(hex)
Attribute
(hex)
Instance
(decimal)
Size
(Bytes)
Read Position
Read Assembly
E
4
3
1
4
Read Position
and Velocity
Read Assembly
E
4
3
3
8
Service Type
Service
Code
(hex)
Class
(hex)
Attribute
(hex)
Instance
(decimal)
Size
(Bytes)
Configure NR60E2
Set_Attribute_Single
10
4
3
103
12
Preset Position
Set_Attribute_Single
10
23
13
1
4
Save to Flash
Custom
16
23
0
0
0
Restore from Flash
Custom
15
23
0
0
0
Restore Factory Defaults
†
Custom
5
23
0
0
0
Reset
Custom
5
1
0
1
0
Summary of Contents for NR60E2
Page 1: ...MICRO CONTROLS INC ADVANCED U s e r M anual E2 Technology E2 Technology Manual 940 0D161...
Page 6: ...TABLE OF CONTENTS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 6 Notes...
Page 20: ...NR60 SPECIFICATIONS NR60E2 User Manual ADVANCED MICRO CONTROLS INC 20 Notes...
Page 44: ...PROTOCOL SPECIFIC INFORMATION NR60E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Page 52: ...IMPLICIT COMMUNICATIONS WITH AN EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 52 Notes...
Page 58: ...IMPLICIT COMMUNICATIONS WITHOUT EDS EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 58 Notes...
Page 70: ...CIP POSITION SENSOR OBJECT EtherNet IP Protocol ADVANCED MICRO CONTROLS INC 70 Notes...
Page 90: ...PROFINET CYCLIC DATA FORMATS PROFINET Protocol ADVANCED MICRO CONTROLS INC 90 Notes...
Page 98: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...