background image

 

 

3. Components of the detector configuration 

 

The detector configuration uses the following elements: 

1.  Potentiometer - adjusts the range of the MW detector  
2.  Three-position ON/OFF potentiometer - selection of additional functions 
3.  The „tamper disable” jumper 

 
1.Potentiometer – to adjust the range of the MW detector 
Adjust the microwave range using the potentiometer.  

 

 

Turning the potentiometer to the „ +” → position increases the range, while turning the potentiometer to the „-” 
→ position reduces the range of the microwave detector. Next, close the detector and check the area of the 
sensor  operation.  Re-open  the  cover of  the  detector  and  adjust  the  microwave  range.  It  is  recommended  to 
increase the microwave range no more than necessary. This is to avoid false alarms. 
Caution!  Detection  sensitivity  of  microwave  path  should  be  adjusted  to  the  size  of  the  protected  space. 
Microwaves can penetrate gypsum walls, doors, etc., which may generate false alarms. 
 
2. Three-position ON/OFF potentiometer - selection of additional functions 
The following functions can be activated with the dip-switch: 

 

turning of the microwaves,  

 

alarm memory 

 

DUO-MASK function.  

See description below in Table 1. 

 

 

 
 
 

 
 
 
 
Table 1 Elements of the detector configuration. 

Dip-switch switches 

Description of the function 

ON 

Disabling  the  MW  detector  ON.  This  function  is  implemented  by 
the  B  /  S.  control  input.  The  B  /  S  input  of  the  detector  must  be 
connected  to one  of  the  control  panel  outputs and  programmed 
to supply the B / S terminal with the +12VDC when the system is 
disarmed  (the  detector  will  be  switched  off).  On  the  other  hand, 
when  the  system  is  armed,  the  control  panel  output  should  be 
programmed so that the B / S terminal shall be shorted to ground 
or disconnected (in this case the detector will operate). 

DIP 1  
Turning off (disabling) the 
MW function 

OFF 

Disabling the MW detector OFF  
(continuous operation of the MW microwave detector). 

Summary of Contents for MOUSE 01

Page 1: ...r operation is shown in the Figure 5a and 5b The anti masking function is based on the microwave sensor If the microwave sensor detects any object in a distance of several centimeters from the detector it is interpreted as an attempt to block the detector and causes the opening of the NC anti masking relay for about 2 seconds 2 Installation of the detector The detector should be mounted by a quali...

Page 2: ... with a description of the available functions can be found in the following pages 6 Close the lid of the sensor CAUTION When closing the cover of the detector check whether the spring of the micro switch tamper is correctly pressed into the tapered socket in the lid The field of view of the detector should not be partially or completely obstructed 7 Connect the supply voltage and wait until the L...

Page 3: ... the protected space Microwaves can penetrate gypsum walls doors etc which may generate false alarms 2 Three position ON OFF potentiometer selection of additional functions The following functions can be activated with the dip switch turning of the microwaves alarm memory DUO MASK function See description below in Table 1 Table 1 Elements of the detector configuration Dip switch switches Descripti...

Page 4: ...th PIR and WM detectors in case of intruder detection 3 The tamper disable jumper If the tamper indicating enclosure opening will be used in addition to the tamper indicating detachment from the wall remove the JP jumper Turning off the microwaves an example of use of the function The use of dual element detectors especially when using the PIR and MW detectors in the AND mode alarm by both detecto...

Page 5: ...1 Power supply 9 15VDC Power consumption Alarm Standby 26 0mA 18 5mA 13 8VDC Sensor range up to 14m Operating angle 90 PIR Sensor 2 components Lens 29 areas in 5 levels Microwave frequency 10 525GHz Emission of microwave signals 1mW impulses Alarm signaling time 4s Alarm type AND OR Tamper protection opening of the detector detachment from the wall YES YES Creep zone detection YES Maximum load of ...

Page 6: ... equipment especially when resulting from failure to comply with the recommendations and requirements contained in the manual It is necessary to periodically test the signaling device The majority of Intrusion Detection Systems indicates malfunctioning of the signaling devices and informs the user with an appropriate message on the LCD keypad or LED light on the LED display In case of such situati...

Page 7: ...venience however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has beenconditionally accepted due to the breaking warranty terms by the claimant 7 All the services are carried out at the service centre of the manu...

Reviews: