AMC AMC-DTR Installation And Operation Instructions Manual Download Page 13

 AMC-DTR Sensor Transmitter User Manual 

 

6  

4.5  System Design Specifications 

Supply Voltage: 

10 to 30 volts 

Power Consumption: 

 

Catalytic Combustible Sensors (requires DTR-10-0233 I/O Power Supply and 3-wire operation): 
100 mA @ nominal 24 VDC 

  Toxic/Oxygen Sensors without Relays / Modbus Option (2-wire 4-20mA operation): 25 mA 

@ nominal 24 VDC. 

  Relays / RS-485 Modbus Option Board (requires DTR-10-0233 I/O Power Supply and 3-wire 

operation): 40 mA per relay (120 mA total with all 3 energized); RS-485 use adds 20mA 

Memory: 

Non-volatile E2 memory retains configuration values in the event of power outages. 

Loop Resistance at nominal 24 VDC power: 

650 ohms maximum in 2-wire mode 
750 ohms maximum in 3-wire mode. 

Relays (Optional): 

Three configurable form C (SPDT) relays rated for 5 amp at 30 VDC or 250VAC RESISTIVE. 

Relay 1 and Relay 2 level alarms are configurable for HIGH or LOW trip, for normally energized 
(Failsafe) or normally de-energized and for latching or non-latching.  

Relay  3  is  always  normally  energized for failsafe  operation  so  loss  of  power  to  the  AMC-DTR 
will be indicated as a “FAULT” condition.  Relay 3 is always non-latching.  

CAUTION:  

Relays are rated for RESISTIVE loads.  Inductive loads, such contactor coils or motors may 
cause contact arcing, which emits RFI into the sensor signals.  Use appropriate snubbers and 
MOV’s across inductive loads and keep wiring away from signal wires. 

 

 

4.6  Field Wiring Installation 

Maximum Field Wiring Lengths

 

Maximum wiring run 

with 250 Ohm Load 

Maximum wiring 

run with 250 Ohm 

Load 

Supply 10-32VDC 

Current@24VDC 

18AWG 

20AWG 

Max Curent 

with DTR-10-

0234 Option 

@24VDC 

18AWG 

20AWG 

DTR-EC 

20mA 

36000ft 

23000ft 

190mA 

4850ft 

3050ft 

DTR-CAT 

100mA 

9200ft 

5797ft 

270mA 

3400ft 

2100ft 

DTR-DS 

120mA 

7680ft 

4830ft 

290mA 

3100ft 

2000ft 

DTR-ST 

400mA 

2340ft 

1449ft 

570mA 

1600ft 

1000ft 

DTR-10-0234 option 
includes three 5 AMP 
Alarm Relays and RS-485 
Modbus 

 

 

 

 

 

 

 
For  other  field  wiring  setups,  contact  the  factory  for  further  information.    Note  when  using 
modbus communication feature total wire loops should not exceed 1000ft/300M remote power 
supplies may be necessary for some configurations to ensure a minimum of 10VDC. 
 

Summary of Contents for AMC-DTR

Page 1: ...ting instructions completely and carefully before starting Filename Manual_amc DTR ver 2 5 doc Copyright July 18 2011 AMC The Armstrong Monitoring Corporation 215 Colonnade Road South Ottawa Ontario C...

Page 2: ...AMC DTR Sensor Transmitter User Manual...

Page 3: ...tallation with Smart Simple Sensor Definition 11 4 9 1 Electrochemical Sensor Wiring to the DTR 10 0232 Display 12 4 9 2 Catalytic Bead Sensor Wiring to the DTR 10 0233 I O Power Supply 13 4 9 3 Remot...

Page 4: ...nfiguration Menus 22 7 4 Alarm Settings 23 7 4 1 Relay Configuration if equipped 24 7 5 Sensor Information 25 7 6 CLOCK DELAY Setup 26 7 7 LCD Contrast Adj 26 7 8 HELP Screen 26 7 9 Diagnostics 26 7 1...

Page 5: ...5 5777 1 2 LIABILITY All AMC products must be installed and maintained according to instructions Only qualified personnel should install and maintain the equipment AMC shall have no liability arising...

Page 6: ...7 or through contacts at www armstrongmonitoring com or through email directly at support armstrongmonitoring com 1 5 MODIFICATIONS AND SUBSTITUTIONS Due to an ongoing development program AMC reserves...

Page 7: ...er Power Supply Requirement 10 to 30 VDC Sensor Part Number Sensor Serial Number Optional Sensor Part Number Optional Sensor Serial Number 2 2 Factory Settings Sensor 1 Sensor 2 Gas Type Range Zero Ga...

Page 8: ...use the AMC DTR if its enclosure is damaged or cracked or has missing components Make sure the cover internal PCB s and field wiring are securely in place before operation Use only a sensor assembly c...

Page 9: ...rson without opening the enclosure A standard real time clock calendar feature allows data logging of calibrations and alarm events for recall to the LCD readout or over the serial port A separate PC...

Page 10: ...92 0 01 Part 1 for Toxic Monitors 4 3 Sensor Location Factors such as air movement gas density in relation to air emission sources and environmental variables affect correct sensor location Air moveme...

Page 11: ...enclosure as shown in Figure 2 Figure 3 shows dimensions with the dual local sensor Y included ALL DIMENSIONS IN INCHES 0 276 Dia 2 Places 3 4 NPT Hub 2 Places SENSOR HOUSING 4 96 5 00 4 94 Figure 2 A...

Page 12: ...I O Power Supply board generates voltages needed for LCD backlight relays RS 485 ModBus and catalytic bead LEL sensor and is required with any of these I O functions The enclosure is equipped with tw...

Page 13: ...is always normally energized for failsafe operation so loss of power to the AMC DTR will be indicated as a FAULT condition Relay 3 is always non latching CAUTION Relays are rated for RESISTIVE loads I...

Page 14: ...ce must supply the loop power in 2 wire 4 20mA modes Be sure the receiver to be used supports this type of operation Instructions Unscrew the cover on the AMC DTR explosion proof enclosure Loosen the...

Page 15: ...t signals See Figure 6 below Instructions Unscrew the cover on the AMC DTR explosion proof enclosure Loosen the 2 thumbscrews holding the display assembly in place and remove it A small ribbon cable i...

Page 16: ...l wires External wiring to TB3 Remote Alarm Reset should be shielded and protected from noise spikes to prevent false Alarm Reset Figure 7 DTR 10 0234 Alarm Relays Modbus Option Instructions Unscrew t...

Page 17: ...DTR 10 0250 Option Description The optional DTR 10 0250 Isolated 4 20mA option Figure 9 provides dual 4 20mA outputs that are electrically isolated from sensor inputs and the 24 VDC power source Each...

Page 18: ...l and catalytic bead smart sensors both plug into the Smart Sensor Housing that connects to AMC DTR electronics with its 8 conductor Smart Sensor Interface cable CAUTION Smart sensor housing with elec...

Page 19: ...Connect the simple electrochemical sensor to TB2 on the DTR 10 0232 Display board Note the colour of the wires for proper installation Or connect the smart electrochemical sensor to S1 the DTR 10 023...

Page 20: ...the simple catalytic bead sensor to TB1 on the DTR 10 0233 I O Power Supply board Note the colour of the wires for proper installation Or connect the smart catalytic bead sensor to S1 the DTR 10 0233...

Page 21: ...Shown For DTR 10 0233 power supply boards that have been modified to accept a 4 20mA input use the following wiring diagram for connection information For AMC 2 wire transmitters connect Transmitters...

Page 22: ...ly Sensor Volts Digital Pot Balance Adjust Digital Pot Bridge Amplifier Simple Catalytic Bead LEL Sensor Reference Active Smart Catalytic Bead LEL Sensor Memory Device Smart Sensor Serial Interface Vd...

Page 23: ...EL Monitor Start Up AMC DTR LEL Monitors are factory equipped with a local Simple or Smart Catalytic Bead LEL sensor which rarely require adjustments other than routine calibrations to provide accurat...

Page 24: ...ctive sensor Remember that this is only a coarse check and precision calibrations are performed in Routine Sensor Calibrations described in the following section 6 1 5 3 Initial Toxic Oxygen Monitor S...

Page 25: ...during calibration Local AMC DTR alarm relays if equipped are inhibited during CAL MODE CAL MODE automatically exits if no keystrokes are detected after 5 minutes Follow these AMC DTR calibration gui...

Page 26: ...d The CAL MODE information screen top of the chart is available for advanced users to see Offset Gain calibration constants and live analog to digital converter A D counts Span Gas calibration values...

Page 27: ...n operator ACKNOWLEDGE pressing the UP RESET key 6 2 1 ALARM 3 Understanding Fault Level Operation The A3 alarm is typically dedicated to FAULT conditions indicating sensor failures or out of measurem...

Page 28: ...user s particular application AMC DTR menus may be configured from the magnetic keypad in 5 10 minutes per transmitter For installations consisting of numerous points an interface device is offered to...

Page 29: ...0 Re a d o u t De a d b a n d 0 T r a c k Ne g a t i v e NO L i n e a r i z a t i o n D a t a B a c k u p Co n f i g Re s t o r e Co n f i g or Up l o a d S e n s o r Da t a UP DOWN S Y S T E M CONF...

Page 30: ...ides 100 output To prevent accidental data entry a special keystroke sequence of 4 consecutive UP keys are required to enter this menu E n t e r K e y S e q u e n c e t o a c c e s s me n u NE X T k e...

Page 31: ...t of range Dead Band has a minimum value of 1 and a maximum value of 10 It is useful for preventing alarm cycling when the monitored value is hovering around the set point EXAMPLE With a range of 0 10...

Page 32: ...f 2 2 C A L D a t e 0 4 0 5 0 4 U P D OWN t o s c r o l l N E X T t o E X I T I N S T A L L N E W S E N S OR Hi s t o r i c a l C A L d a t a Wi l l b e D e l e t e d E D I T t o A c c e p t N E X T...

Page 33: ...25 shows the menu for these items C L OCK DE L A Y S E T UP T i me 12 3 5 4 2 Da t e 0 4 2 2 0 4 Wa r m U p S e c 12 0 Ca l P u r g e S e c 10 0 Figure 25 Clock Calendar Delay Timer Menu 7 7 LCD Contr...

Page 34: ...p u t 4 0 mA E D I T t o c h a n g e N e x t t o e x i t EDIT A C T I V A T E RE L A Y S R e l a y 1 OF F R e l a y 2 OF F R e l a y 3 OF F Figure 27 Diagnostics Menus 7 10 RS 485 MODBUS Setup The RS...

Page 35: ...Chan 2 Status 31006 4 NA 16 bit status words bit assignment for each channel ALARM1_BELOW BIT0 ALARM2_BELOW BIT1 ALARM3_BELOW BIT2 ALARM1_LATCH BIT3 ALARM2_LATCH BIT4 ALARM3_LATCH BIT5 ALARM3_ACTIVE...

Page 36: ...g units read as bytes Byte Variables PreAmp Gain Ch1 40433 3 NA PreAmp Gain Ch2 40434 3 NA 2 bytes representing Pre Amp HiByte and PGA LoByte settings Firmware Version Version 40435 40436 3 NA 4 ASCII...

Page 37: ...X 41042 4 NA Chan 1 D2A MIN 41043 4 NA Chan 1 D2A MAX 41044 4 NA Chan 2 A2D MIN 41045 4 NA Chan 2 A2D MAX 41046 4 NA Chan 2 D2A MIN 41047 4 NA Chan 2 D2A MAX 41048 4 NA Min and Max calibration points...

Reviews: