7.11 Measurement duration ‘C’
This parameter is responsible for the refresh rate of the LED display and value on 4..20 mA current
output. When this parameter is set, the module has to be restarted. It is possible to change the value
from 0.1 to 1 s, every 0.1 s.
8. Measurement parameter configuration
Measurement parameter configuration is set by proper set-up of configuration switches
SW1
and
SW2
. Description of switches
SW1
and
SW2
is presented in the following table and
Figure 8-1
:
Functions of configuration switches
SW 1
SW2
S1 – ON, HPF =10 Hz (OFF = 3 Hz)
S1 – ON, range 10 (OFF, range 100)
S2 – range 100
S2 – ON, range 25 (OFF, range 100)
S3 – range 10
S3 – ON - acceleration (OFF - velocity)
S4 – range 25
S4 – ON - RMS (OFF - PEAK)
S5 – DX: LPF = 1 kHz
S5 – ON, internal power 24 V for 4..20 mA
S6
– LPF = 10 kHz
S6 – ON, external power supply for 4..20 mA
S7 – acceleration
S8 – velocity
12
AV MONITOR 1002DX