background image

 

 

7.9

 

Selecting the measured vibration signal estimate 'AU‘ 

 

The AVM 1002DX module enables measuring RMS or 0-PEAK values of vibration acceleration or 
velocity. 

 

 

ATTENTION! The configuration must be confirmed using SW1 and SW2 configuration switches 
described in the following chapter. 

 

 

To select desired estimate one should perform the following procedure: 

 

1.

 

Press 

UP/DN

. Afterwards the 

OK

 LED will blink rapidly, which indicates entering into the 

device menu. 

 

2.

 

By pressing 

UP

/

DN

 set the ‘

AU

 on the display. 

 

3.

 

Confirm by pressing the 

SET

 button. 

 

4.

 

Use the 

UP

/

DN

 buttons to select one of the following option: 

 

»

 

PU

 – 0-PEAK value of the velocity signal,

 

 

»

 

rU

 – RMS value of the velocity signal,

 

 

»

 

PA

 – 0-PEAK value of the acceleration signal,

 

 

»

 

rA

 – RMS value of the acceleration signal.

 

 

5.

 

To confirm the change, press the 

SET

 button. 

 

7.10  Relay output state configuration 'uA‘, ‘uU’ 

 

The AVM 1002DF has a special feature to control relay output state (normally open or normally closed). 

 

The configuration can be done independently for warning and alarm output. 

 

To configure relay output state one should perform the following procedure: 

 

1.

 

Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the 
device menu. 

 

2.

 

By pressing UP/DN set on the display letters ‘uU’ for the warning relay or ‘uA’ for the alarm 
relay. 

 

3.

 

Confirm by pressing the SET button. 

 

4.

 

Use the UP/DN buttons to select the desired configuration: ‘no’ or ‘nc’

 

5.

 

To confirm the change, press the SET button. 

 

The table below displays the effects of the possible settings: 

 

 

selected 

     

    

relay output state 

    

 

 

      

  

startup or 

    

no warning 

   

sensor error 

   

warning or 

 

configuration 

    

power OFF 

  

    

  

   

 

 

 

   

   

module error 

 

   

or alarm 

   

(if enabled) 

    

alarm active 

   

      

   

     

   

    

 

 

      

     

       

       

        

 

 

no 

    

open 

  

open 

    

open 

    

closed 

     

closed 

 

 

 

   

 

   

 

 

   

 

 

   

 

 

    

 

 

 

nc 

    

open 

  

open 

    

closed 

   

open 

    

open 

 

 

 

 

   

 

   

 

 

   

 

 

   

 

 

    

 

 

 
 

Figure 7-1 The effects of the possible settings 

 
 
 
 
 

 

11

 

AV MONITOR 1002DX 

Summary of Contents for AV MONITOR 1002DX

Page 1: ...2 Krakow Poland T 48 12 362 97 60 S 48 12 362 97 63 info amcvibro com KRS No 0000618618 REGON No 364497010 VAT No 6772403385 www amcvibro com AV MONITOR 1002DX CONDITION MONITORING SYSTEM WITH RELAY O...

Page 2: ...the threshold activation delay d 8 7 5 Setting up the latch of alarm or warning threshold violation L 8 7 6 Signaling of the sensor failure CA CU 9 7 7 Setting up the correction of values indicated by...

Page 3: ...urement calculation of RMS or 0 PEAK values configurable warning and alarm relay outputs with the delay of the output build in connector for AC voltage signal from the x vibration sensor 10 Vpp DIN ra...

Page 4: ...Peak Indicator of the selected measured value Green LEDs acc acceleration vel velocity Alarm outputs indicators Red LED ALARM the alarm threshold exceeded alarm output ON Yellow LED WARNING the warnin...

Page 5: ...3 Module dimensions 4 Mounting AVM 1002DX modules are designed for mounting on 35 mm DIN rain in an upright position Figure 4 1 Example of 3 AVM 1002DX modules mounted on DIN rail 5 AV MONITOR 1002DX...

Page 6: ...into testing procedure Subsequently all display s segments and LEDs will flash for a short period of time If everything is operating properly then green OK LED is pulsing with a frequency of approxima...

Page 7: ...values indicated by the module Er turning display off on sensor failure AU selection of vibration signal estimate ATTENTION In some types of AVM 1002DX modules some of the above functions are not act...

Page 8: ...confirm by pressing the SET button 7 4 Setting up of the threshold activation delay d In the AVM 1002DX module the user can define how long the alarm threshold or the warning threshold should be exce...

Page 9: ...OK LED will blink rapidly which indicates entering into the device menu 2 By pressing UP DN set the CA on the display 3 Confirm by pressing the SET button 4 Use the UP DN buttons to select the ON opt...

Page 10: ...decimal point on the right display 5 To confirm the change press the SET button 7 8 Turning display off on sensor failure Er The AVM 1002DX module enables to mask the incorrect measurement values in t...

Page 11: ...T button 7 10 Relay output state configuration uA uU The AVM 1002DF has a special feature to control relay output state normally open or normally closed The configuration can be done independently for...

Page 12: ...is set by proper set up of configuration switches SW1 and SW2 Description of switches SW1 and SW2 is presented in the following table and Figure 8 1 Functions of configuration switches SW 1 SW2 S1 ON...

Page 13: ...d internal power loop The following configuration of the switches must be set SW1 SW2 OFF ON OFF OFF OFF ON OFF ON OFF OFF OFF ON ON OFF 1 8 1 6 WARNING The set up of the switches configuration should...

Page 14: ...9 Menu Graphical representation of menu structure is presented on the following figure 14 AV MONITOR 1002DX...

Page 15: ...n 4 W low pass filter DX 1 and 10 kHz 24 dB oct 4 th order DT no LPF filter high pass filter DX 3 and 10 Hz 12 dB oct 2 nd order DT no HPF filter insulation 1 kV DC 2 or 3 kV DC optionally current out...

Page 16: ...ent chromium polybrominated biphenyls polybrominated diphenyl ether or other battery related materials are limited to no more than trace amounts 10 2 Recycling Facilities When decommissioning out of u...

Reviews: